| Energy | Original | D | 1/30/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2261756 |
| Mechanical | Original | D | 1/30/2026 | DALEH | DALEH | Heat calcs R and U values do not match approved IECC Need manufacturers blower specs and coil specs that match friction loss work sheet Provide friction loss worksheet * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2261755 |
| Construction | Original | A | 1/29/2026 | SHELLEY | SHELLEY | | | Construction | 2261309 |
| | Original | / | 1/28/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2261044 |
| | Original | / | 1/28/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2260762 |
| Submittal 5 | Original | / | 1/28/2026 | QUINTONW | QUINTONW | Submittal #5 | | Submittal 5 | 2260761 |
| Energy | Original | D | 1/22/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2258848 |
| Mechanical | Original | D | 1/22/2026 | DALEH | DALEH | All insulation values on heat calcs must match approved IECC Need to provide friction loss work sheet Need to provide manufactures specs for all equipment, blower specs etc....128,00 See equipment certificate * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2258847 |
| | Original | / | 1/20/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2257863 |
| | Original | / | 1/20/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2257798 |
| Submittal 4 | Original | / | 1/20/2026 | QUINTONW | QUINTONW | Submittal #4 | | Submittal 4 | 2257797 |
| County Zoning | Original | A | 1/7/2026 | DSDYOUNGER | DSDYOUNGER | Review Complete. See comments below for: Single Family Dwelling, Driveway, BESQCP (see full review) | | County Zoning | 2254217 |
| County Zoning | Original | / | 1/7/2026 | DSDYOUNGER | DSDYOUNGER | Single Family Dwelling Approved (see full review) | | County Zoning | 2254143 |
| County Zoning | Original | / | 1/7/2026 | DSDYOUNGER | DSDYOUNGER | BESQCP Approved (see full review) | | County Zoning | 2254137 |
| County Zoning | Original | / | 1/7/2026 | DOTPIRZADEH2 | DOTPIRZADEH2 | Driveway Approved (see full review) | | County Zoning | 2254216 |
| Energy | Original | D | 1/6/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2253675 |
| Mechanical | Original | D | 1/6/2026 | DALEH | DALEH | Since the design has now gone to just a single family dwelling Only provide one heat calc for the entire home Only provide one duct design Only provide one equipment certificate * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2253674 |
| Electrical | Original | A | 1/5/2026 | CONNERM | CONNERM | | | Electrical | 2253086 |
| Electronic Plan | Original | / | 1/5/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2253084 |
| Plumbing | Original | A | 1/5/2026 | SHANEN | SHANEN | | | Plumbing | 2253082 |
| Enumeration | Original | A | 1/5/2026 | AMY | AMY | Single Family | | Enumeration | 2253074 |
| Construction | Original | A | 1/5/2026 | SHELLEY | SHELLEY | Second kitchen converted to kitchenette with NO PERMANENT COOKING APPLIANCE. Single family dwelling. | | Construction | 2253058 |
| | Original | / | 12/29/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2251628 |
| | Original | / | 12/29/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2251449 |
| Submittal 3 | Original | / | 12/29/2025 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2251448 |
| County Zoning | Original | D | 12/19/2025 | DSDYOUNGER | DSDYOUNGER | 1.) Per email correspondence with Vincent Grabowski (vincent@vincenzohomes.com) on 11/12/2025, Must provide the Franklin Investments LLC document naming person(s) authorized to sign on behalf of the LLC document is required. It must be uploaded to the plan set as an "other" document.
2.) Affidavidt must reflect the ALQ address assigned by Enumerations. 4156 Pinehurst Cir. Also for the notarized signature, the person authorized to sign must be listed not Franklin Investments LLC name again. Please see disapproved affidavit. Corrected affidavit will need to be signed, notarized and recorded. | | County Zoning | 2250508 |
| Energy | Original | D | 12/18/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2249800 |
| Mechanical | Original | D | 12/18/2025 | DALEH | DALEH | Provide separate duct design drawings showing one for ADU and one for main house, do not combine on one design for better clarity Indicate location radiation dampers or fire dampers will be required when penetrating rated walls and ceilings Waiting on rated assemblies per building plan reviewer No further review * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2249799 |
| Electronic Plan | Original | / | 12/16/2025 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2248139 |
| Electrical | Original | A | 12/16/2025 | CONNERM | CONNERM | | | Electrical | 2247929 |
| Electronic Plan | Original | / | 12/16/2025 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2247927 |
| Construction | Original | D | 12/16/2025 | SHELLEY | SHELLEY | Still have issues with rated construction. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2247893 |
| Enumeration | Original | A | 12/15/2025 | AMY | AMY | 4154 & 4156 Pinehurst Circle was added to every sheet of this plan. 4154 to the south-east and 4156 to the north-west. | | Enumeration | 2247648 |
| Electronic Plan | Original | / | 12/15/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2247607 |
| Submittal 2 | Original | / | 12/15/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2247368 |
| Energy | Original | D | 10/16/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2224783 |
| Mechanical | Original | D | 10/16/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2224782 |
| Enumeration | Original | D | 10/16/2025 | AMY | AMY | Will this be a 2 family dwelling or single family. The basement is not separated space. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2224780 |
| County Zoning | Original | D | 10/10/2025 | DSDYOUNGER | DSDYOUNGER | 1.) Walden Preserve PUD Guidelines does not allow for Two Family Dwelling. See site plan for snippet from PUD Development Guidelines.
2.) If a second kitchen will be within Single Family Dwelling an Accessory Living Quarters Affidavit will be required. The form must be filled out completely to include the address, legal description, and tax schedule number. The affidavit must be signed and notarized by all property owners on title. This information can be found on the El Paso County Assessor’s parcel search page. The affidavit must then be recorded with the Clerk and Recorder’s office. Once the recorded affidavit is received, upload or include the recorded document with your plan set to Pikes Peak Regional Building Department.
**Must provide the document(s) showing who is/are the authorized person(s) to sign on behalf of FRANKLIN INVESTMENTS LLC
Special Provisions for Attached Accessory Living Quarters for Permanent Occupancy. Attached accessory living quarters may be utilized for permanent occupancy provided it conforms to all standards for accessory living quarters listed above and the following requirements: • Exterior Appearance Single-Family in Character. The exterior appearance of the structure shall be that of an architecturally integrated single-family dwelling unit.
• Interior Connection Required. The living quarters shall include the ability to access the main dwelling unit through interior connections, which may include access through a garage attached to the principle dwelling. | | County Zoning | 2222489 |
| Plumbing | Original | A | 10/10/2025 | SHANEN | SHANEN | | | Plumbing | 2222279 |
| Electrical | Original | D | 10/9/2025 | CONNERM | CONNERM | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2221489 |
| Electronic Plan | Original | / | 10/9/2025 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2221488 |
| Zoning/Planning | Original | / | 10/8/2025 | DSDYOUNGER | DSDYOUNGER | In Current Review by DSDYOUNGER | | Zoning/Planning | 2221387 |
| Construction | Original | D | 10/8/2025 | SHELLEY | SHELLEY | Need clarifications on dwelling separation. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2221371 |
| Electronic Plan | Original | / | 10/8/2025 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2221196 |
| Enumeration | Original | A | 10/6/2025 | AMY | AMY | | | Enumeration | 2220184 |
| Electronic Plan | Original | / | 10/6/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2220182 |
| | Original | / | 10/6/2025 | SYSTEM | SYSTEM | Plan Review fees paid 10/06/2025 for plan submitted 10/06/2025. Submit Date updated to now. Plan now open for review. | | | 2220174 |
| Energy | Original | / | 10/6/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2220162 |
| Floodplain | Original | N | 10/6/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6115010013) | | Floodplain | 2220161 |