| Black Forest Hazmat (CSFD) | Original | A | 11/24/2025 | BLKFSTFIRE | BLKFSTFIRE | | Flucas | Black Forest Hazmat (CSFD) | 2240961 |
| Electrical | Original | D | 10/30/2025 | CONNERM | CONNERM | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2231129 |
| Mechanical | Original | N | 10/30/2025 | TREVORH | TREVORH | Not Applicable; | | Mechanical | 2230805 |
| Construction | Original | A | 10/30/2025 | BPHILLIPS | BPHILLIPS | | | Construction | 2230758 |
| Electronic Plan | Original | / | 10/30/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2230755 |
| Submittal 2 | Original | / | 10/29/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2230117 |
| Black Forest Hazmat (CSFD) | Original | A | 10/22/2025 | BLKFSTFIRE | BLKFSTFIRE | Revisions are required before fire approval can be granted. The proposed installation shows two Tesla Powerwall units mounted in the garage; however, a scaled floor plan identifying the exact ESS location, mounting height, and clearances is missing. Per IFC 1207.3 and 1207.5, provide a dimensioned layout showing minimum three-foot working clearances, separation from doors, windows, ignition sources, and egress paths, and confirmation that the mounting surface is non-combustible or one-hour rated. If located where vehicles may impact, provide physical protection such as bollards per IFC 312. All energy-storage equipment must be UL 9540 listed and installed per manufacturer instructions, with disconnects clearly labeled and grouped together with PV and utility disconnects per IFC 1207.6 and 1204.3.3. Install reflective hazard placards at the main electrical service and entry points stating “Energy Storage System Inside” and “PV System Equipped with Rapid Shutdown” | Flucas | Black Forest Hazmat (CSFD) | 2227021 |
| Mechanical | Original | D | 10/15/2025 | TREVORH | TREVORH | Disapproved; Pending construction and Electrical review comment clarification. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2224447 |
| Electrical | Original | D | 10/15/2025 | CONNERM | CONNERM | Main bonding jumper needs to be moved GEC cannot be located in the load hub Provide all conductor and wire sizes * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2224218 |
| Electronic Plan | Original | / | 10/15/2025 | QUINTONW | QUINTONW | In Current Review by QUINTONW | | Electronic Plan | 2224206 |
| Electronic Plan | Original | / | 10/15/2025 | QUINTONW | QUINTONW | In Current Review by QUINTONW | | Electronic Plan | 2224205 |
| Electronic Plan | Original | / | 10/15/2025 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2224189 |
| Construction | Original | D | 10/15/2025 | BPHILLIPS | BPHILLIPS | Provide code/ climatic design criteria in connection documents file. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2224092 |
| Electronic Plan | Original | / | 10/15/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2224090 |
| Energy | Original | N | 10/13/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2223013 |
| Zoning | Original | N | 10/13/2025 | SYSTEM | SYSTEM | Zoning review is not required for roof-mounted PV solar projects in El Paso County. | | Zoning | 2223011 |
| Floodplain | Original | N | 10/13/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5128008012) | | Floodplain | 2223010 |