| Electrical | Original | A | 11/25/2025 | CONNERM | CONNERM | | | Electrical | 2241127 |
| Electronic Plan | Original | / | 11/25/2025 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2241117 |
| Submittal 3 | Original | / | 11/25/2025 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2241063 |
| Black Forest Fire (CSFD) | Original | A | 11/24/2025 | BLKFSTFIRE | BLKFSTFIRE | or the safety of occupants and first responders, the proposed PV solar and energy storage system must be installed in accordance with the 2015 International Fire Code and NEC requirements. Roof-mounted panels must maintain clear firefighter access pathways, and all conduits, disconnects, and rapid shutdown devices must be properly labeled and accessible. The energy storage system (ESS) shall be UL-listed, located in a well-ventilated area away from sleeping spaces, and protected from physical damage or moisture. Adequate working clearances, fire-rated separation (if indoors), and visible signage identifying the system type and shutdown points are required. Proper installation and labeling will ensure safe operation and allow emergency personnel to quickly and safely secure the system if needed | Flucas | Black Forest Fire (CSFD) | 2240963 |
| Mechanical | Original | N | 11/18/2025 | TCRIPPEN | TCRIPPEN | No mechanical scope | | Mechanical | 2237840 |
| Electrical | Original | D | 11/6/2025 | CONNERM | CONNERM | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2233870 |
| Construction | Original | A | 11/6/2025 | SHELLEY | SHELLEY | | | Construction | 2233851 |
| Submittal 2 | Original | / | 11/6/2025 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2233629 |
| Black Forest Fire (CSFD) | Original | A | 10/22/2025 | BLKFSTFIRE | BLKFSTFIRE | Please provide a floor plan identifying the exact location of the Energy Storage System (ESS) within the structure rather than a general site plan. The plan shall clearly indicate the battery model, mounting location, clearances to walls and openings, working space dimensions, and proximity to electrical equipment in accordance with 2021 IFC Section 1207, 605.11, and NFPA 855. Include details on ventilation, disconnecting means, and signage as applicable. Verify that ESS location maintains required separation from habitable spaces and ignition sources, and is consistent with manufacturer installation instructions and local amendments. Resubmit revised drawings showing this information for review and approval.
Verify that roof access and pathways comply with 2021 IFC Section 1204 and Fire access pathways shall be clearly dimensioned on the roof plan, with minimum 36-inch pathways along at least one side of each roof ridge an | Flucas | Black Forest Fire (CSFD) | 2227020 |
| Electrical | Original | D | 10/16/2025 | CONNERM | CONNERM | Must be located on outside north exterior wall per utility approval Conductors and ground are undersized (B) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2225033 |
| Construction | Original | D | 10/16/2025 | SHELLEY | SHELLEY | Provide a floor plan for ESS location, not a site plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2225017 |
| Electronic Plan | Original | / | 10/16/2025 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2225014 |
| Energy | Original | N | 10/16/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2224810 |
| Zoning | Original | N | 10/16/2025 | SYSTEM | SYSTEM | Zoning review is not required for roof-mounted PV solar projects in El Paso County. | | Zoning | 2224809 |
| Floodplain | Original | N | 10/16/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6211005006) | | Floodplain | 2224808 |