| Palmer Lake Fire | Original | A | 8/11/2026 | PLFIRE | PLFIRE | | Palmer Lake FD | Palmer Lake Fire | 2345878 |
| Energy | Original | D | 8/5/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2343671 |
| Mechanical | Original | D | 8/5/2026 | QUINTONW | QUINTONW | Disapproved: Provide make and model of equipment being used * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2343670 |
| Plumbing | Original | D | 8/5/2026 | SHANEN | SHANEN | Show shower pan dimensions, air barriers and water meter. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2343483 |
| Electrical | Original | D | 8/5/2026 | CONNERM | CONNERM | Specify and show location of potential PV pathway from roof to electric panel.
Verify locations of conduit and termination points serving the EV ready space.
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Show a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note requiring compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
High efficacy lighting amendment for R404.2 does not apply to the unamended 2021 IECC. Plan will need to fully comply with original R.404.2 for lighting controls * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2343463 |
| Electronic Plan | Original | / | 8/5/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2343451 |
| Construction | Original | D | 8/5/2026 | SHELLEY | SHELLEY | Attic conditioning, landings, combine framing plans, solar roof plan, see plans for all requirements. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2343418 |
| Electronic Plan | Original | / | 8/5/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2343375 |
| Enumeration | Original | D | 8/3/2026 | AMY | AMY | Palmer Lake is the addressing authority in Palmer Lake. Enumerations has 464 Virginia Ave for this lot. Can you please contact Palmer Lake via email to clarify the address and email that correspondence to me.The recorders for the permit need to match what Palmer Lake has. Amy@pprbd.org.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2341867 |
| Electronic Plan | Original | / | 8/3/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2341861 |
| | Original | / | 7/31/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/31/2026 for plan submitted 07/31/2026. Submit Date updated to now. Plan now open for review. | | | 2341774 |
| Energy | Original | / | 7/31/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2341765 |
| Floodplain | Original | N | 7/31/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7108202013) | | Floodplain | 2341764 |