| Energy | Original | A | 8/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2346723 |
| Mechanical | Original | A | 8/12/2026 | QUINTONW | QUINTONW | Approved | | Mechanical | 2346722 |
| Energy | Original | / | 8/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2346720 |
| Energy | Original | D | 8/12/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2346681 |
| Mechanical | Original | D | 8/12/2026 | QUINTONW | QUINTONW | Disapproved Previous Comment not addressed: Provide product specifications for equipment being used. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2346680 |
| Construction | Original | A | 8/12/2026 | BPHILLIPS | BPHILLIPS | | | Construction | 2346576 |
| | Original | / | 8/12/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2346365 |
| | Original | / | 8/12/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2346360 |
| Submittal 4 | Original | / | 8/12/2026 | MELISSAF | MELISSAF | Submittal #4 | | Submittal 4 | 2346359 |
| Energy | Original | D | 8/11/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2346264 |
| Construction | Original | A | 8/11/2026 | BPHILLIPS | BPHILLIPS | | | Construction | 2346263 |
| Energy | Original | / | 8/11/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2346261 |
| Energy | Original | D | 8/11/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2346208 |
| Mechanical | Original | D | 8/11/2026 | QUINTONW | QUINTONW | Disapproved: See Heat calculations, Equipment Cert and IECC for all disapproval comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2346207 |
| Electrical | Original | A | 8/11/2026 | CONNERM | CONNERM | | | Electrical | 2346045 |
| Electronic Plan | Original | / | 8/11/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2346041 |
| Construction | Original | D | 8/11/2026 | BPHILLIPS | BPHILLIPS | Need to verify at least 5% energy savings in IECC supporting documents. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2346039 |
| | Original | / | 8/11/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2346014 |
| | Original | / | 8/11/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2345996 |
| Submittal 3 | Original | / | 8/11/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2345995 |
| County Zoning | Original | A | 8/7/2026 | DSDCHAMBERS | DSDCHAMBERS | Review Complete. See comments below for: Single Family Dwelling, Driveway (see full review) | | County Zoning | 2344887 |
| County Zoning | Original | / | 8/7/2026 | EPCZONING | EPCZONING | Driveway Approved (see full review) | | County Zoning | 2344886 |
| Energy | Original | D | 8/6/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2344434 |
| Mechanical | Original | D | 8/6/2026 | QUINTONW | QUINTONW | Disapproved: See heat calculations and Equipment certificate for all disapproval comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2344433 |
| Electronic Plan | Original | / | 8/6/2026 | QUINTONW | QUINTONW | In Current Review by QUINTONW | | Electronic Plan | 2344272 |
| County Zoning | Original | / | 8/6/2026 | DSDCHAMBERS | DSDCHAMBERS | Single Family Dwelling Approved (see full review) | | County Zoning | 2344885 |
| County Zoning | Original | / | 8/6/2026 | EPCZONING | EPCZONING | Single Family Dwelling Approved (see full review) | | County Zoning | 2344254 |
| Zoning/Planning | Original | / | 8/6/2026 | DSDCHAMBERS | DSDCHAMBERS | In Current Review by DSDCHAMBERS | | Zoning/Planning | 2344109 |
| Plumbing | Original | A | 8/6/2026 | SHANEN | SHANEN | | | Plumbing | 2344103 |
| Electrical | Original | D | 8/6/2026 | CONNERM | CONNERM | Specify and show location of potential PV pathway from roof to electric panel.
Show an EV ready space is noted in the garage
Verify locations of conduit and termination points serving the EV ready space.
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Show a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note requiring compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
Show compliance with IECC R404.2
Show location of emergency disconnect * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2344037 |
| Electronic Plan | Original | / | 8/6/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2344032 |
| Construction | Original | D | 8/6/2026 | BPHILLIPS | BPHILLIPS | IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2344020 |
| Electronic Plan | Original | / | 8/5/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2343850 |
| Enumeration | Original | A | 8/4/2026 | AMY | AMY | | | Enumeration | 2342872 |
| Electronic Plan | Original | / | 8/4/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2342868 |
| Submittal 2 | Original | / | 8/4/2026 | TREYW | TREYW | Submittal #2 | | Submittal 2 | 2342829 |
| Enumeration | Original | D | 8/4/2026 | AMY | AMY | Wrong address on Mechanical Duct Design, Heat Loss Cals & Equipment Cert. sheets * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2342751 |
| Electronic Plan | Original | / | 8/4/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2342738 |
| | Original | / | 8/4/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/04/2026 for plan submitted 08/04/2026. Submit Date updated to now. Plan now open for review. | | | 2342733 |
| Stormwater | Original | / | 8/4/2026 | SYSTEM | SYSTEM | You will need to contact Stormwater department for approval prior to permit. This department will not review the plan electronically. | | Stormwater | 2342728 |
| Energy | Original | / | 8/4/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2342727 |
| Floodplain | Original | N | 8/4/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 4119008003) | | Floodplain | 2342726 |