| WP Fire (CSFD Commercial) | Original | D | 11/18/2026 | NETCFIRE | NETCFIRE | | netcfire | WP Fire (CSFD Commercial) | 2383979 |
| WP Zoning | Original | D | 11/18/2026 | DBURGESS | DBURGESS | See 10/28/2026 WP Zoning review comments. | | WP Zoning | 2383608 |
| Energy | Original | D | 11/17/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2383484 |
| Mechanical | Original | D | 11/17/2026 | QUINTONW | QUINTONW | Disapproved: see equipment cert and heat calcs for disapproval comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2383483 |
| Electrical | Original | D | 11/17/2026 | CONNERM | CONNERM | Show an EV ready space noted in the garage * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2383463 |
| Electronic Plan | Original | / | 11/17/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2383438 |
| Construction | Original | A | 11/17/2026 | SHELLEY | SHELLEY | | | Construction | 2383404 |
| Energy | Original | / | 11/17/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2383402 |
| | Original | / | 11/17/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2383304 |
| | Original | / | 11/17/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2383169 |
| Submittal 3 | Original | / | 11/17/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2383168 |
| WP Fire (CSFD Commercial) | Original | D | 11/16/2026 | NETCFIRE | NETCFIRE | | netcfire | WP Fire (CSFD Commercial) | 2382728 |
| WP Zoning | Original | D | 10/28/2026 | DBURGESS | DBURGESS | SFR ZDP approved on 8/04/2026 & Grading Permit approved on 10/06/2026. Pending payment of Development Fees. Disapproved at this time to release plan set to address PPRBD reviewers comments. | | WP Zoning | 2376112 |
| Energy | Original | D | 10/27/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2375465 |
| Mechanical | Original | D | 10/27/2026 | QUINTONW | QUINTONW | Disapproved: AM&M must be submitted and approved for use of 2024 IECC. Provide the equipment cert designed to be used with 2024 IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2375464 |
| Electrical | Original | D | 10/26/2026 | CONNERM | CONNERM | Specify and show potential PV pathway from attic to electric panel. If vertical pathway then specify so * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2375377 |
| Electronic Plan | Original | / | 10/26/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2375361 |
| Construction | Original | D | 10/26/2026 | SHELLEY | SHELLEY | Still need to address crawlspace location, options and AMM for 2024 IECC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2375351 |
| Submittal 2 | Original | / | 10/26/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2375253 |
| WP Fire (CSFD Commercial) | Original | D | 9/21/2026 | NETCFIRE | NETCFIRE | Driveway is approved as designed. We will need to do a final inspection before CO.
Fire Department Impact fee of the 3590 Sf. will need to be paid 8,257.00 to NE Teller Fire before permit approval. | netcfire | WP Fire (CSFD Commercial) | 2361741 |
| WP Zoning | Original | D | 8/18/2026 | DBURGESS | DBURGESS | Pending approval of the SFR ZDP & Grading Permit - awaiting GP narrative. Also pending payment of Development Fees which will be determined when the SFR ZDP is issued. Disapproved at this time to release plan set to address PPRBD reviewers comments. | | WP Zoning | 2348884 |
| Energy | Original | D | 8/13/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2347381 |
| Electrical | Original | D | 8/13/2026 | CONNERM | CONNERM | Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Provide plan note stating there will be a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note stating compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2347380 |
| Electronic Plan | Original | / | 8/13/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2347378 |
| Mechanical | Original | D | 8/13/2026 | QUINTONW | QUINTONW | Disapproved: See Energy report for disapproval comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2347308 |
| Plumbing | Original | A | 8/13/2026 | SHANEN | SHANEN | | | Plumbing | 2347302 |
| Electronic Plan | Original | / | 8/13/2026 | QUINTONW | QUINTONW | In Current Review by QUINTONW | | Electronic Plan | 2347299 |
| Construction | Original | D | 8/13/2026 | SHELLEY | SHELLEY | See A1.2, A2.1. LIMITED STRUCTURAL REVIEW - see structural plans for all comments. AMM required to utilize 2024 IECC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2347295 |
| Electronic Plan | Original | / | 8/12/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2346714 |
| WP Floodplain | Original | N | 8/12/2026 | DBURGESS | DBURGESS | Verified not in a floodplain | | WP Floodplain | 2346394 |
| WP Enumeration | Original | A | 8/12/2026 | DBURGESS | DBURGESS | Parcel number & Tax number matches Teller County Assessor's published online data. Revised owner in plan record to match Quit Claim Deed under Teller County Clerk & Recorder's Reception No. 778477 dated 01/05/2026. Added PPRBD GIS mapping Address Point to match. | | WP Enumeration | 2346393 |
| | Original | / | 8/11/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/11/2026 for plan submitted 08/10/2026. Submit Date updated to now. Plan now open for review. | | | 2346096 |
| Energy | Original | / | 8/10/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2345316 |