| Energy | Original | A | 8/31/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2354521 |
| Electrical | Original | A | 8/31/2026 | CONNERM | CONNERM | | | Electrical | 2354520 |
| Electronic Plan | Original | / | 8/31/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2354515 |
| Construction | Original | A | 8/31/2026 | BRIANB | BRIANB | | | Construction | 2354504 |
| Submittal 2 | Original | / | 8/31/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2354449 |
| WP Fire (CSFD Commercial) | Original | D | 8/26/2026 | NETCFIRE | NETCFIRE | Driveway is approved at 1% grade. Impact fees will be applied to this project for 2030 SF @ 2.30. Total fee is 4,669.00 | netcfire | WP Fire (CSFD Commercial) | 2352603 |
| WP Zoning | Original | D | 8/17/2026 | DBURGESS | DBURGESS | Pending payment of Development Fees. Disapproved at this time to release plan set to address PPRBD reviewers comments. | | WP Zoning | 2348187 |
| Energy | Original | D | 8/14/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2347855 |
| Mechanical | Original | A | 8/14/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2347854 |
| Electrical | Original | D | 8/12/2026 | CONNERM | CONNERM | Specify and show location of potential PV pathway from roof to electric panel.
Verify locations of conduit and termination points serving the EV ready space.
Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Provide plan note stating there will be a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note stating compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
High efficacy lighting amendment for R404.2 does not apply to the unamended 2021 IECC. Plan will need to fully comply with original R.404.2 for lighting controls
Must fully comply with R404.1. Amendment no longer applies
Show location of electrical panel and emergency disconnect. Mus comply with 230.85 NEC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2346852 |
| Electronic Plan | Original | / | 8/12/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2346843 |
| Plumbing | Original | A | 8/12/2026 | SHANEN | SHANEN | | | Plumbing | 2346767 |
| Construction | Original | D | 8/12/2026 | BRIANB | BRIANB | Provide solar ready roof plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2346741 |
| Electronic Plan | Original | / | 8/12/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2346388 |
| WP Floodplain | Original | N | 8/12/2026 | DBURGESS | DBURGESS | Verified not in a floodplain | | WP Floodplain | 2346372 |
| WP Enumeration | Original | A | 8/12/2026 | DBURGESS | DBURGESS | Address, owner, parcel number & Tax number matches Teller County Assessor's published online data. | | WP Enumeration | 2346371 |
| | Original | / | 8/11/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/11/2026 for plan submitted 08/11/2026. Submit Date updated to now. Plan now open for review. | | | 2346073 |
| Energy | Original | / | 8/11/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2345786 |