| CO Springs DRE | Original | D | 9/29/2026 | SSADLER | SSADLER | The site plan that was provided does not accurately show what is on site. The side setback for an ADU 5ft from the property line. Correct the site plan and resubmit. | | CO Springs DRE | 2364720 |
| City Engr | Original | D | 9/25/2026 | JDAGNILLO | JDAGNILLO | Engineering Development Review has determined a geologic hazard report required for this lot due to high expansive soils. This report must be submitted directly to EDR through our electronic review system called ProjectDox. Below is a link to ProjectDox and a user manual.
https://coloradosprings.gov/stormwater/planreview
EDR's review fee will be collected by ProjectDox and if the report requires a third party review such as Colorado Geological Survey (CGS), their review fees are invoiced and paid directly to the third party review agency.
Revised application forms are available on Public Works web-page. Public Works/City Engineering Hub/New Development/Standards and References/ "References and Research Tools" https://coloradosprings.gov/public-works/page/engineering-standards-and-references
Once report has been approved by the City, please upload a copy into this building permit plan set for City Engineering signoff on the builidng permit | | City Engr | 2363705 |
| Stormwater | Original | N | 9/24/2026 | JDUNCAN | JDUNCAN | Activity does not disturb an acre or more and is not part of a larger common plan of development. No stormwater scope of work. | | Stormwater | 2363318 |
| Energy | Original | D | 9/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2363295 |
| Mechanical | Original | D | 9/24/2026 | QUINTONW | QUINTONW | Disapproved: Need AM&M for use of 2024 IECC see equipment cert and IECC for disapproval comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2363294 |
| Plumbing | Original | D | 9/24/2026 | SHANEN | SHANEN | Reference 2021 IRC and 2021 IPC. Provide plumbing plans that comply with PPRBD requirements for residential plumbing plans. See link: https://www.pprbd.org/File/ByAlias/ResPlumbing * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2363080 |
| Electrical | Original | D | 9/24/2026 | CONNERM | CONNERM | Show locations of conduit and termination points serving the EV ready space.
Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Provide a plan note stating compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
If solar ready zones meet requirements: Specify and show potential PV pathway from attic to electric panel. If vertical pathway then specify so AND Provide plan note stating there will be a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Comply with R404.2 and R404.3 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2363036 |
| Zoning/Planning | Original | / | 9/23/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2362967 |
| Construction | Original | D | 9/23/2026 | SHELLEY | SHELLEY | IECC, wall types, stairs, foundation issues, see plans for all comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2362960 |
| Electronic Plan | Original | / | 9/23/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2362833 |
| Enumeration | Original | A | 9/23/2026 | BECKYA | BECKYA | The address for the new home is 310-B N 24th Street. We no longer assign 1/2 addresses to accessory dwelling units. The address was updated on all plan pages and the legal description and parcel number was added to the site plan. If any plan pages are disapproved and switched out, please, add the B to the plans prior to resubmitting. | | Enumeration | 2362773 |
| Electronic Plan | Original | / | 9/23/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2362772 |
| | Original | / | 9/23/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/23/2026 for plan submitted 08/21/2026. Submit Date updated to now. Plan now open for review. | | | 2362650 |
| Energy | Original | / | 8/21/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2351117 |
| Floodplain | Original | N | 8/21/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7411117001) | | Floodplain | 2351115 |