| Manitou Water | Original | A | 10/22/2026 | MSWATER | MSWATER | Conditional approval that Fire approves pressure, and traffic rated cover for shutoff is installed. | bschmittcms | Manitou Water | 2373942 |
| Manitou Waste Water | Original | D | 10/22/2026 | MSWATER | MSWATER | See Comments on cleanouts | bschmittcms | Manitou Waste Water | 2373939 |
| Manitou Fire | Original | A | 10/20/2026 | MSFIRE | MSFIRE | Ok per B Dorris | bdorris | Manitou Fire | 2372788 |
| Energy | Original | A | 10/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2372318 |
| Electrical | Original | A | 10/19/2026 | CONNERM | CONNERM | | | Electrical | 2372317 |
| Electronic Plan | Original | / | 10/19/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2372298 |
| | Original | / | 10/19/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2372286 |
| | Original | / | 10/16/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2371735 |
| Submittal 3 | Original | / | 10/16/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2371734 |
| Manitou Fire | Original | D | 10/15/2026 | MSFIRE | MSFIRE | Disapproved. B Dorris | bdorris | Manitou Fire | 2371630 |
| Manitou Waste Water | Original | D | 10/15/2026 | MSWATER | MSWATER | per customer request | CRoystonUtilities | Manitou Waste Water | 2371600 |
| Manitou Water | Original | D | 10/15/2026 | MSWATER | MSWATER | per customer request | CRoystonUtilities | Manitou Water | 2371599 |
| Manitou Zoning | Original | D | 10/15/2026 | MSZONING | MSZONING | Application has not received necessary City approvals for design as shown. (MSP, GEC, MCAC) | eringsred | Manitou Zoning | 2371597 |
| Manitou Zoning | Original | D | 10/15/2026 | MSZONING | MSZONING | per customer request | CStromberg | Manitou Zoning | 2371596 |
| Energy | Original | D | 10/8/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2368913 |
| Mechanical | Original | A | 10/8/2026 | QUINTONW | QUINTONW | Approved | | Mechanical | 2368912 |
| Electrical | Original | D | 10/8/2026 | CONNERM | CONNERM | Show compliance with IECC R404.2 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2368689 |
| Construction | Original | A | 10/8/2026 | BPHILLIPS | BPHILLIPS | | | Construction | 2368678 |
| Submittal 2 | Original | / | 10/8/2026 | TREYW | TREYW | Submittal #2 | | Submittal 2 | 2368631 |
| Manitou Water | Original | D | 9/30/2026 | MSWATER | MSWATER | No Size, type, location of service is shown on plans | bschmittcms | Manitou Water | 2365575 |
| Manitou Waste Water | Original | D | 9/30/2026 | MSWATER | MSWATER | No size, type, location of sewer service is shown on the plans | bschmittcms | Manitou Waste Water | 2365573 |
| Manitou Zoning | Original | D | 9/25/2026 | MSZONING | MSZONING | Minor Site Plan and GEC does not have approval yet. | eringsred | Manitou Zoning | 2363893 |
| Manitou Fire | Original | D | 9/25/2026 | MSFIRE | MSFIRE | Per B. Dorris | bdorris | Manitou Fire | 2363629 |
| Energy | Original | D | 9/22/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2362157 |
| Electrical | Original | D | 9/22/2026 | CONNERM | CONNERM | Specify and show potential PV pathway from attic to electric panel. If vertical pathway then specify so
Show locations of conduit and termination points serving the EV ready space.
Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Provide plan note stating there will be a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note stating compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
Remove amendments. No longer apply. Fully comply with IECC R404.1 and R404.2 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2362156 |
| Mechanical | Original | D | 9/22/2026 | QUINTONW | QUINTONW | Disapproved: Provide manufacture specifications for the equipment being used. See heat calcs and equipment certificate for all disapproval comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2362155 |
| Plumbing | Original | A | 9/22/2026 | SHANEN | SHANEN | | | Plumbing | 2362152 |
| Electronic Plan | Original | / | 9/22/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2362149 |
| Construction | Original | D | 9/22/2026 | BPHILLIPS | BPHILLIPS | An approved AM&M request form is required in order to use the 2024 IECC. Current adopted code is the 2021 IECC and CO MERSRC. Floor above garage must be insulated when garage is unheated. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2362142 |
| Electronic Plan | Original | / | 9/22/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2362067 |
| Enumeration | Original | N | 9/16/2026 | BECKYA | BECKYA | | | Enumeration | 2359951 |
| Electronic Plan | Original | / | 9/16/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2359949 |
| | Original | / | 9/15/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/15/2026 for plan submitted 09/15/2026. Submit Date updated to now. Plan now open for review. | | | 2359874 |
| Energy | Original | / | 9/15/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2359831 |
| Floodplain | Original | N | 9/15/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7405402044) | | Floodplain | 2359830 |