| Stormwater | Original | N | 9/17/2026 | GHUNTLEY | GHUNTLEY | Activity does not disturb an acre or more and is not part of a larger common plan of development. | | Stormwater | 2360491 |
| City Engr | Original | D | 9/16/2026 | DSOSA | DSOSA | Engineering Development Review has determined that a geological hazard waiver is acceptable for this project. The waiver must be submitted directly to EDRD through our electronic review system, ProjectDox. A link to ProjectDox and the user manual is provided below. https://coloradosprings.gov/stormwater/planreview
Application forms are available on the Public Works webpage: Public Works>City Engineering Hub>Engineering Standards and References>References and Research Tools https://coloradosprings.gov/public-works/page/engineering-standards-and-references
Once the waiver has been approved, please upload a copy of the signed waiver to the building permit plan set for City Engineering signoff.
Also, the following statement must be included on the architectural/structural plan for the retaining wall: “The private retaining wall system shall be designed by a Colorado registered professional engineer and the responsibility of the construction and maintenance lies with the developer and property owner. The City of Colorado Springs has not reviewed or approved the design, and the Owner(s) hereby releases and forever discharges, and agrees to indemnify, defend and hold harmless, the City of Colorado Springs, its officers, employees, administrators, representatives, agents, successors and assigns, from any and all damages, injuries or accidents which might arise from the retaining wall system or the Project after issuance of a Building Permit” | | City Engr | 2360429 |
| Zoning/Planning | Original | / | 9/16/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2360337 |
| Energy | Original | D | 9/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2360313 |
| Mechanical | Original | A | 9/16/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2360312 |
| Plumbing | Original | D | 9/16/2026 | SHANEN | SHANEN | All gas piping related items shall be on the mechanical plans. Remove all references to gas piping from the plumbing plans. Clarify plumbing note as it is intended for a prior to permit plan. Show the water meter location. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2360252 |
| Electrical | Original | D | 9/16/2026 | CONNERM | CONNERM | Specify and show potential PV pathway from roof to electric panel.
Verify locations of conduit and termination points serving the EV ready space.
Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Provide plan note stating there will be a 2-pole breaker space at the opposite end of the buss for Solar Ready. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2360226 |
| Electronic Plan | Original | / | 9/16/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2360225 |
| Construction | Original | A | 9/16/2026 | DOUGC | DOUGC | | | Construction | 2360215 |
| Enumeration | Original | D | 9/16/2026 | AMY | AMY | A separate address is required for a detached residence. Add the address of 1631 Berglind Road to each page. Do not use 1629 on any page. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2360195 |
| Electronic Plan | Original | / | 9/16/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2360189 |
| Electronic Plan | Original | / | 9/16/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2360176 |
| | Original | / | 9/16/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/16/2026 for plan submitted 09/16/2026. Submit Date updated to now. Plan now open for review. | | | 2360164 |
| Energy | Original | / | 9/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2360161 |
| Floodplain | Original | N | 9/16/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6308016006) | | Floodplain | 2360160 |