| | Original | / | 11/18/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2383791 |
| Submittal 3 | Original | / | 11/18/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2383789 |
| Ellicott Fire | Original | N | 11/13/2026 | ELLICOTTFIRE | ELLICOTTFIRE | This project is greater than 35 acres and therefore exempt from the adopted fire code and the Colorado Wildfire Resiliency Code. Ellicott Fire Protection District would appreciate a turn around at the mid point and end of the long driveway. | ELLICOTTFD | Ellicott Fire | 2382029 |
| County Zoning | Original | D | 11/3/2026 | DSDHILLS | DSDHILLS | Please Upload Approved Stormwater Permit. | | County Zoning | 2377909 |
| Energy | Original | D | 11/2/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2377312 |
| Electrical | Original | D | 11/2/2026 | CONNERM | CONNERM | Specify and show potential PV pathway from attic to electric panel. If vertical pathway then specify so * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2377311 |
| Electronic Plan | Original | / | 11/2/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2377301 |
| Zoning/Planning | Original | / | 11/2/2026 | DSDHILLS | DSDHILLS | In Current Review by DSDHILLS | | Zoning/Planning | 2377281 |
| Construction | Original | D | 11/2/2026 | BPHILLIPS | BPHILLIPS | Remove architectural and solar ready plans from structural file. Roof framing plan appears to be missing. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2377269 |
| Enumeration | Original | A | 10/29/2026 | BECKYA | BECKYA | | | Enumeration | 2376593 |
| Submittal 2 | Original | / | 10/29/2026 | TREYW | TREYW | Submittal #2 | | Submittal 2 | 2376559 |
| Ellicott Fire | Original | D | 10/5/2026 | ELLICOTTFIRE | ELLICOTTFIRE | No evidence of site plan review from Ellicott Fire could be found on epcdevplanreview.com. The driveway exceeds the maximum allowable access per 2021 IFC D103.4
Provide water supply that meets 2021 IFC Appendix B.
Provide decking material.
Show compliance with Colorado Wildfire Resiliency Code and state hazard level. | ELLICOTTFD | Ellicott Fire | 2366938 |
| Energy | Original | D | 9/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2363083 |
| Plumbing | Original | A | 9/24/2026 | SHANEN | SHANEN | | | Plumbing | 2363082 |
| Mechanical | Original | A | 9/23/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2362911 |
| County Zoning | Original | D | 9/23/2026 | DSDYOUNGER | DSDYOUNGER | 1.) Address Enumeration comments
2.) Must provide approve stamped Stormwater Permit Form. Contact Stormwater at Stormwater@elpasoco.com for assistance with obtaining approved form. | | County Zoning | 2362887 |
| Electrical | Original | D | 9/23/2026 | CONNERM | CONNERM | Specify and show potential PV pathway from attic to electric panel. If vertical pathway then specify so
Show locations of conduit and termination points serving the EV ready space.
Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Provide plan note stating there will be a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note stating compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
Remove previous IECC amendments from plans. No longer apply * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2362874 |
| Electronic Plan | Original | / | 9/23/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2362867 |
| Construction | Original | D | 9/23/2026 | BPHILLIPS | BPHILLIPS | Provide solar ready roof plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2362845 |
| Electronic Plan | Original | / | 9/23/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2362704 |
| Enumeration | Original | D | 9/17/2026 | AMY | AMY | Site plan: add the street name to the street, add the legal description, add the address of the property.
Architectural: If there is a stove/range or cooking appliance please clarify what it is and label the volts. Why I ask is due to this exception; Accessory Living Quarters - Lodging, which may include a kitchen, that is accessory to the principal dwelling which may be occupied only by occasional, non-paying guests of the family residing in the principal dwelling. Accessory living quarters are not considered dwelling units. The term does not include farm/ranch residence, caretakers quarters, or an additional dwelling. A stove under 220 volts is more like a kitchenette and would not be considered a dwelling unit. So, if this is still the case please put a note on the stove stating the voltage. If not, an address would need to be assigned if at or above 220 volts. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2360565 |
| Electronic Plan | Original | / | 9/17/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2360550 |
| | Original | / | 9/16/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/16/2026 for plan submitted 09/16/2026. Submit Date updated to now. Plan now open for review. | | | 2360434 |
| Energy | Original | / | 9/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2360423 |
| Floodplain | Original | N | 9/16/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 3400000468) | | Floodplain | 2360422 |