| CO Springs Hazmat | Original | A | 11/16/2026 | CSFIRE | CSFIRE | Previously approved. No issues. sds | smitty91 | CO Springs Hazmat | 2382592 |
| Electrical | Original | A | 11/13/2026 | CONNERM | CONNERM | | | Electrical | 2382111 |
| Construction | Original | N | 11/13/2026 | CONNERM | CONNERM | | | Construction | 2382108 |
| Electronic Plan | Original | / | 11/13/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2382101 |
| | Original | / | 11/13/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2382019 |
| | Original | / | 11/12/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2381730 |
| Submittal 5 | Original | / | 11/12/2026 | NICOLASV | NICOLASV | Submittal #5 | | Submittal 5 | 2381728 |
| CO Springs Hazmat | Original | A | 11/10/2026 | CSFIRE | CSFIRE | DFM-C-ES-26-00071 This battery is on the CSFD-previously approved UL 9540 list Sigen 6.0/9.0 kWh US - SigenStor-11.5-54.24 UL 9540 & 9540A – Ok to stack Plan Review previously approved | mark.stanwood@colora | CO Springs Hazmat | 2380417 |
| Electrical | Original | D | 11/6/2026 | CONNERM | CONNERM | Floor plan shows two 60A ac disconnects. One line only shows one. Please correct * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2379671 |
| Construction | Original | D | 11/6/2026 | CONNERM | CONNERM | This is not a UL9540 certificate. Provide letter of certification from NRTL. Cannot accept manufacturer spec for this * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2379670 |
| Electronic Plan | Original | / | 11/6/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2379662 |
| | Original | / | 11/5/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2379128 |
| | Original | / | 11/5/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2379108 |
| Submittal 4 | Original | / | 11/5/2026 | MELISSAF | MELISSAF | Submittal #4 | | Submittal 4 | 2379107 |
| Electrical | Original | D | 11/5/2026 | CONNERM | CONNERM | Comply with 706.15 (B). ESS must have an rapid shutdown device located at a readily accessible outside location * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2378836 |
| Construction | Original | D | 11/5/2026 | CONNERM | CONNERM | Document provided is not a UL9540 certificate letter. Provide one from NRTL * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2378834 |
| Electronic Plan | Original | / | 11/5/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2378825 |
| CO Springs Hazmat | Original | A | 11/4/2026 | CSFIRE | CSFIRE | Previously approved. DFM-C-ES-26-00071 | smitty91 | CO Springs Hazmat | 2378542 |
| | Original | / | 11/2/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2377518 |
| | Original | / | 11/2/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2377516 |
| Submittal 3 | Original | / | 11/2/2026 | NICOLASV | NICOLASV | Submittal #3 | | Submittal 3 | 2377515 |
| CO Springs Hazmat | Original | A | 11/2/2026 | CSFIRE | CSFIRE | DFM-C-ES-26-00071 previously approved FDMUS OK | mark.stanwood@colora | CO Springs Hazmat | 2377429 |
| Electrical | Original | D | 10/19/2026 | CONNERM | CONNERM | Show all ESS equipment on floor plan. Show compliance with 706.15 (B) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2372437 |
| Submittal 2 | Original | / | 10/19/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2372303 |
| CO Springs Hazmat | Original | A | 10/14/2026 | CSFIRE | CSFIRE | DFM-C-ES-26-00071 RES ESS INT CSFD DFM You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources. If you do not have an ACA account at the time of CSFD review, you will need to reach out to the CSFD DFM staff to link the review to your account. DFM Plan Review Fee: $296.00 ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | CO Springs Hazmat | 2370801 |
| Mechanical | Original | N | 10/5/2026 | QUINTONW | QUINTONW | N/A | | Mechanical | 2367146 |
| Electrical | Original | D | 10/5/2026 | CONNERM | CONNERM | Show all ESS equipment on floor plan. Show compliance with 706.15 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2366881 |
| Construction | Original | N | 10/5/2026 | CONNERM | CONNERM | | | Construction | 2366880 |
| Electronic Plan | Original | / | 10/5/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2366873 |
| | Original | / | 10/2/2026 | SYSTEM | SYSTEM | Plan Review fees paid 10/02/2026 for plan submitted 10/02/2026. Submit Date updated to now. Plan now open for review. | | | 2366479 |
| Energy | Original | N | 10/2/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2366439 |
| Floodplain | Original | N | 10/2/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7402401088) | | Floodplain | 2366438 |
| Stormwater | Original | / | 10/2/2026 | SYSTEM | SYSTEM | Parcel 7402401088 is within the Hillside Overlay (HS). Stormwater Review is required. | | Stormwater | 2366437 |