| CO Springs DRE | Original | D | 10/27/2026 | SSADLER | SSADLER | Upload the pre application summary that was provided. Upload the approval letter and the approved stamped plans for the administrative adjustment (ADRF-26-0052). Provide a recorded deed dated prior to February 1951 to show lot of record. | | CO Springs DRE | 2375642 |
| Energy | Original | D | 10/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2374960 |
| Mechanical | Original | D | 10/26/2026 | QUINTONW | QUINTONW | Disapproved see equipment cert for all disapproval comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2374959 |
| Plumbing | Original | A | 10/23/2026 | SHANEN | SHANEN | | | Plumbing | 2374454 |
| City Engr | Original | D | 10/23/2026 | HVO | HVO | EDRD has determined geological hazards exist in this area and requires a Geologic Hazard Report. Please submit it to EDRD through our electronic review system called ProjectDox. Below is a link to ProjectDox and a user manual. https://coloradosprings.gov/stormwater/planreview
Once it has been approved please upload the approved file with building submission. | | City Engr | 2374426 |
| Zoning/Planning | Original | / | 10/23/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2374423 |
| Floodplain | Original | D | 10/23/2026 | KEITH | KEITH | The proposed addition is located within the Cheyenne Creek floodway. A "No-Rise" certification and supporting technical report are required. This report must be prepared and stamped by a registered Colorado Professional Engineer (PE) to demonstrate that the development will cause zero increase (0.00 feet) to the established floodway elevations. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Floodplain | 2374332 |
| Electrical | Original | D | 10/22/2026 | CONNERM | CONNERM | Show locations of conduit and termination points serving the EV ready space.
Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
Show compliance with IECC R404.2 and R404.3 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2374229 |
| Construction | Original | D | 10/22/2026 | DOUGC | DOUGC | Preliminary review ONLY. IECC was submitted under the 2024 code cycle, disapprove to allow for resubmittal. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2374207 |
| | Original | / | 10/22/2026 | SYSTEM | SYSTEM | Plan Review fees paid 10/22/2026 for plan submitted 10/22/2026. Submit Date updated to now. Plan now open for review. | | | 2374204 |
| Energy | Original | / | 10/22/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2373918 |
| Fire | Original | / | 10/22/2026 | RBD GIS | RBD GIS | Parcel 7425121035 is within the Wildland Urban Interface (WUI). Fire Department Review is required. | | Fire | 2373916 |
| Floodplain | Original | / | 10/22/2026 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7425121035) | | Floodplain | 2373917 |