| County Zoning | Original | A | 11/18/2026 | DSDYOUNGER | DSDYOUNGER | Review Complete. See comments below for: Single Family Dwelling, Driveway (see full review) | | County Zoning | 2383865 |
| County Zoning | Original | / | 11/18/2026 | EPCZONING | EPCZONING | Driveway Approved (see full review) | | County Zoning | 2383864 |
| Energy | Original | D | 11/17/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2383284 |
| Mechanical | Original | D | 11/17/2026 | QUINTONW | QUINTONW | Disapproved: see equipment certificate for comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2383283 |
| County Zoning | Original | / | 11/17/2026 | DSDYOUNGER | DSDYOUNGER | Single Family Dwelling Approved (see full review) | | County Zoning | 2383240 |
| Electronic Plan | Original | / | 11/17/2026 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 2383133 |
| Electronic Plan | Original | / | 11/17/2026 | ROBERTV | ROBERTV | In Current Review by ROBERTV | | Electronic Plan | 2383132 |
| Electronic Plan | Original | / | 11/17/2026 | QUINTONW | QUINTONW | In Current Review by QUINTONW | | Electronic Plan | 2383125 |
| Plumbing | Original | D | 11/13/2026 | SHANEN | SHANEN | See plumbing plan sheet 2 of 2 for disapproval comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2382116 |
| Electrical | Original | D | 11/13/2026 | CONNERM | CONNERM | Specify and show potential PV pathway from attic to electric panel. If vertical pathway then specify so
Show locations of conduit and termination points serving the EV ready space.
Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Provide plan note stating there will be a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note stating compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
Show compliance with IECC R404.2 and R404.3 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2382090 |
| Electronic Plan | Original | / | 11/13/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2382085 |
| Zoning/Planning | Original | / | 11/13/2026 | DSDYOUNGER | DSDYOUNGER | In Current Review by DSDYOUNGER | | Zoning/Planning | 2382081 |
| Construction | Original | D | 11/13/2026 | DOUGC | DOUGC | Architectural // Structural // IECC // Trusses * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2382078 |
| Electronic Plan | Original | / | 11/13/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2381965 |
| Enumeration | Original | A | 11/5/2026 | BRENT | BRENT | | | Enumeration | 2378882 |
| Electronic Plan | Original | / | 11/5/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2378876 |
| | Original | / | 11/4/2026 | SYSTEM | SYSTEM | Plan Review fees paid 11/04/2026 for plan submitted 11/04/2026. Submit Date updated to now. Plan now open for review. | | | 2378671 |
| Fire | Original | / | 11/4/2026 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2378646 |
| Energy | Original | / | 11/4/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2378645 |
| Floodplain | Original | N | 11/4/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 4102000016) | | Floodplain | 2378644 |