| County Zoning | Original | D | 11/20/2026 | DSDYOUNGER | DSDYOUNGER | Address Enumeration comments.
Accessory Living quarters Affidavit may be required if kitchenette has a 220 volts.
The form must be filled out completely to include the address of the accessory living quarters (typically different than main address), legal description, and tax schedule number. The affidavit must be signed and notarized by all property owners on title. This information can be found on the El Paso County Assessor’s parcel search page. The affidavit must then be recorded with the Clerk and Recorder’s office. Once the recorded affidavit is received, upload or include the recorded document with your plan set to Pikes Peak Regional Building Department.
Affidavit has been uploaded as an "other" document for your convenience. | | County Zoning | 2384958 |
| Electrical | Original | D | 11/20/2026 | CONNERM | CONNERM | Show location of electrical panel and emergency disconnect
Show compliance with R404.2 and R404.3
Specify and show potential PV pathway from attic to electric panel. If vertical pathway then specify so
Show locations of conduit and termination points serving the EV ready space.
Show an EV ready space noted in the garage
Provide a plan note stating a minimum 2-pole, 40 amp GFCI breaker, conduit, conductor, and receptacle is provided for an EV Charger
Provide a plan note stating there will be a 2-pole breaker space for each proposed combustion appliance
Provide plan note stating there will be a 2-pole breaker space at the opposite end of the buss for Solar Ready.
Provide a plan note stating compliance with 2021 IECC R402.4.6 limiting air leakage through electrical and communication outlet boxes installed in the building thermal envelope
Must have approved AM&M to submit under 2024 IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2384875 |
| Electronic Plan | Original | / | 11/20/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2384863 |
| Construction | Original | D | 11/20/2026 | SHELLEY | SHELLEY | IECC, options, solar ready plan, truss labeling, truss loading, stair landing; see plans for all comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2384840 |
| Energy | Original | / | 11/20/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2384836 |
| Energy | Original | / | 11/20/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2384653 |
| Electronic Plan | Original | / | 11/20/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2384651 |
| Enumeration | Original | D | 11/16/2026 | AMY | AMY | The title block was corrected to show the RANGE as 65 not 66. A stove under 220 volts is more like a kitchenette and would not be considered a dwelling unit. So, if this is still the case please put a note on the stove stating the voltage. If not, an address would need to be assigned to the separate living space, if at or above 220 volts. Please clarify. SEE HANDOUT ON PPRBD WEBSITE. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2382671 |
| Electronic Plan | Original | / | 11/16/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2382647 |
| | Original | / | 11/16/2026 | SYSTEM | SYSTEM | Plan Review fees paid 11/16/2026 for plan submitted 11/16/2026. Submit Date updated to now. Plan now open for review. | | | 2382574 |
| Energy | Original | / | 11/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2382563 |
| Floodplain | Original | N | 11/16/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5206008005) | | Floodplain | 2382562 |