PENROSE HOSPITAL FACILITIES | H02 | C | 03/25/2024 | HO2 -- 5 YR 3/23 -- ANNUAL 3/23 -- OTIS & SERVICE -- NOTE: ANNUAL TRACTION SAFETY TEST IS DUE BY THE END OF THE MONTH -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2046154) | BENH | BENH | | H02 | C | 8032465 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2023 | 5 YR 3/23 -- ANNUAL 3/23 -- OTIS & SERVICE -- INSPECTION WAS SKIPPED SINCE ELEVATOR WAS WITNESSED EARLIER THIS YEAR (Receipt #1990225) all MOD items addressed, 11/21/23 DS | BENH | BENH | | H01 | C | 7862742 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/2023 | H02 -- 5YR -- 3/2023 -- CAT1 -- 3/2023. OTIS AND SERVICE. ACCEPTANCE TO MOD COMPLETED | ROBERTV | ROBERTV | | H02 | C | 7702682 |
PENROSE HOSPITAL FACILITIES | H06 | C | 03/08/2023 | WITNESSED ACCEPTANCE TO MOD -- SEE MOD PERMIT FOR ANY ITEMS NEEDING ADDRESSED. | ROBERTV | ROBERTV | | H06 | C | 7702687 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/22/2022 | 5 YEAR 1/19 -- ANNUAL 1/22 -- OTIS & SERVICE -- STOP SWITCH HANDLE FOR CAR TOP INSPECTION STATION HAS BROKEN OFF -- MISSING TEST TAGS ON CONTROLLERS IN MACHINE ROOM (Receipt #1901468) | BENH | BENH | | H01 | C | 7526677 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/02/2022 | H02 -- 5YR -- 1/19 -- CAT1 1/22 -- OTIS AND SERVICE. ITEMS HAVE BEEN ADDRESSED PER OTIS | ROBERTV | ROBERTV | | H02 | C | 7287744 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2021 | 5YR -- 1/19 -- CAT1 -- 6/21 -- OTIS AND SERVICE. REAR HOISTWAY FASCIA NEEDS TO BE RE-SECURED TO WALL FROM 2ND FLOOR LANDING SILL TO PIT - (CLEARANCE FROM FASCIA TO CAR PLATFORM CANNOT EXCEED 1.5 INCHES). HOISTWAY FASCIA ABOVE 2ND FLOOR HEADER NEEDS ADJUSTED TO NOT EXCEED 1.5 INCHES FROM CAR PLATFORM. SOS SWITCH LINKAGE ATTACHMENT AT CAR TOP NEEDS TO BE RETAINED CORRECTLY W/ WASHERS AND COTTER PINS. COUNTERWEIGHT THRU ROD RETAINERS ARE LOOSE. GOVERNOR ROPE NEEDS TO BE SHORTENED (2ND NOTICE). 2ND FLOOR REAR BOTTOM DOOR GIBS ARE NOT LOCATED IN THE LANDING SILL A MINIMUM 1/4' (2ND NOTICE)........... 60 DAYS TO ADDRESS. PERMIT TO OPERATE CANNOT BE ISSUED UNTIL ITEMS ARE ADDRESSED. (Receipt #1808070) (cat 1 -- 1/2022, items have been addressed per Otis RV)) | ROBERTV | ROBERTV | | H01 | C | 7112546 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/12/2021 | H02 -- 5YR -- 1/19 -- CAT1 -- 4/20 -- OTIS AND SERVICE. CHECK PREVIOUS LISTED ITEMS AT H01 | ROBERTV | ROBERTV | | H02 | C | 6898764 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/23/2020 | 5YR -- 1/19 -- CAT1 -- 4/20 -- OTIS AND SERVICE. GOVERNOR ROPE NEEDS TO BE SHORTENED. DOOR OPERATOR CHAIN NEEDS LUBRICATION OR REPLACED. NEED COMPLETE MAINTENANCE CONTROL PROGRAM. 2ND FLOOR REAR BOTTOM DOOR GIBBS ARE NOT DOWN IN LANDING SILL MINIMUM 1/4 INCH. CAR TOP AND PIT NEEDS CLEANED. 12TH FLOOR HALL CALL WORKS INTERMITTENTLY. (Receipt #1715707) | ROBERTV | ROBERTV | | H01 | C | 6717134 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/20/2020 | H02 -- FOLLOW UP SCHEDULED WITH TKE FOR 60 DAYS FOR ITEMS LISTED IN PREVIOUS INSPECTION REPORT cat 1 4/20 | ROBERTV | ROBERTV | | H02 | C | 6517023 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/18/2019 | 5YR 1/19--OTIS W/ TKE SERVICE (Receipt #1630971) | CALE | CALE | | H01 | C | 6340090 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/2019 | 5 YEAR 1/19 OTIS, HO2 | ERIC | ERIC | | H02 | C | 6141492 |
PENROSE HOSPITAL FACILITIES | H06 | C | 01/17/2019 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS AND ALARM BELL NOT WORKING. (Receipt #1571343) | ERIC | ERIC | | H06 | C | 6086058 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2018 | 5YR--9--13--OTIS --TKE SERVICE --ANNUAL 6--18----LOCKBOX ON ELEVATOR MECH ROOM 4,5,AND 6 (Receipt #1539328) | JOHNW | JOHNW | | H01 | C | 5970954 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/29/2018 | 5YR --9--13--OTIS --TKE SERVICE --ANNUAL 8--16 EXPIRED --LOCKBOX ON MECH ROOM 8 & 9--ALARM BELL NOT WORKING | JOHNW | JOHNW | | H02 | C | 5802201 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/22/2017 | 5YR -- 9/13 -- LAST ANNUAL 8/16 -- OTIS W/ TKE SERVICE. ALARM BELL NOT WORKING, ANNUAL CATEGORY 1 TESTING DUE WITHIN 30 DAYS........... NOTE: ROPES HAVE BEEN REPLACED. (Receipt #1454603) | ROBERTV | ROBERTV | | H01 | C | 5633670 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/24/2017 | ELEVATOR WAS REMOVED FROM SERVICE BY INSPECTOR DUE TO UNDERSIZED ROPES THAT WERE TO BE REPLACED AND HAVE YET TO BE. TOP LEFT CENTER GUIDE RAIL ROLLER NEEDS REPLACED AND REALIGNED. SUSPENSION ROPES ARE EXTREMELY THIN ON THE COUNTERWEIGHT SIDE BETWEEN FLOORS 8 AND 9 | ROBERTV | ROBERTV | | H02 | C | 5454744 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/27/2016 | 5YR -- 9/13 -- OTIS. ROPES SCHEDULED FOR REPLACEMENT IN OCTOBER 2016. (Receipt #1365824) | ROBERTV | ROBERTV | | H01 | C | 5303252 |
PENROSE HOSPITAL FACILITIES | HE16 | C | 08/29/2016 | WORN AND UNDERSIZED SUSPENSION ROPES NOTED AT INSPECTION DATED 3/22/2016 HAVE YET TO BE REPLACED, ROPES NEED TO BE REPLACED BY COMPLIANCE DATE TO AVOID SERVICE INTERRUPTION. | ROBERTV | ROBERTV | | HE16 | C | 5280625 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/2016 | 5YR--10--13--OTIS --ROPE ROUGH AND ROPES ARE BEYOND THEIR LIMITS, NEEDS REPLACED. --ALARM IN CAB NOT WORKING --NEED MCP IN MACHINE ROOM | ERIC | ERIC | | H02 | C | 5160477 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2015 | 5YR -- 10/13 -- OTIS. MISSING ANNUAL TAG, TOP OF CAR ROLLER DAMAGED, ALARM NOT WORKING IN CAB, MONITOR GOVERNOR ROPE ON FUTURE INSPECTIONS. (Receipt #1290266) | ROBERTV | ROBERTV | | H01 | C | 5047161 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2015 | 5YR--10--13--OTIS--MISSING ANNUAL TAG | JOHNW | JOHNW | | H02 | C | 4926329 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/2014 | 5YR--10--13--OTIS--TOP OF CAR ROLLER DAMAGED --ALARM NOT WORKING IN CAB--PHONE DOOR FALLING OFF THE HINGES (Receipt #1222655) | JOHNW | JOHNW | | H01 | C | 4824282 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/25/2014 | 5 YR 10/13 H02 | ERIC | ERIC | | H02 | C | 4708020 |
PENROSE HOSPITAL FACILITIES | H06 | C | 10/28/2013 | WITNESSED 5 YEAR SAFETY TEST. COUNTER WEIGHT RUNBY LESS THAN REQUIRED 6" (3") , SUSPENSION ROPES NEED TO BE CLEANED, NEED FLOOR NUMBERS ON HOISTWAY DOORS AND NEED CALL STATION FIRE SIGN AT BASEMENT LANDING (Receipt #1162848) | ERIC | ERIC | | H06 | C | 4630799 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2013 | CAR OUT OF SERVICE FOR REPAIRS (Receipt #1156806) | ERIC | ERIC | | H01 | C | 4612811 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/2013 | 5YR --7--08--OTIS | JOHNW | JOHNW | | H02 | C | 4492052 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/19/2012 | 5 YR 7-08--OTIS ALARM IN CAR NOT WORKING / POST FIRE SIGNS AT ALL LANDINGS (Receipt #1082918) | TOM | TOM | | H01 | C | 4392048 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/26/2012 | 5 YR 7-08--POST FIRE SIGNS AT ALL LANDINGS / ALARM IN CAR NOT WORKING | TOM | TOM | | H02 | C | 4290604 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/21/2011 | 5 YR 7-08--OTIS--FIRE SIGNS STILL MISSING (Receipt #1003039) | TOM | TOM | | H01 | C | 4215302 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/09/2011 | 5 YR 7-08--OTIS--POST FIRE SIGNS AT ALL LANDINGS | TOM | TOM | | H02 | C | 4129101 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/13/2010 | 5 YR 7-08--OTIS PHONE IN CAR NOT WORKING (Receipt #936125) | TOM | TOM | | H01 | C | 4049126 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/25/2010 | 5 yr 7-08--otis | TOM | TOM | | H02 | C | 3960099 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2009 | 5 YR 7-08--OTIS POST CAR NUMBER IN CAR (#2) (Receipt #878684) | TOM | TOM | | H01 | C | 3892315 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2009 | 5YR 7-08--OTIS | TOM | TOM | | H02 | C | 3818678 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/25/2008 | 5yr--7--08--otis (Receipt #828021) | TOM | TOM | | H01 | C | 3746578 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/20/2008 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H02 | C | 427915 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/26/2007 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H01 | C | 427907 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/2007 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H02 | C | 427900 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/2006 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H01 | C | 427891 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2006 | 5YR--5--03--OTIS--ALARM INOP | JOHNW | JOHNW | | H02 | C | 427883 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/2005 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H01 | C | 427876 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2005 | 5 YR- 5-03--OTIS | TOM | TOM | | H02 | C | 427867 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2004 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H01 | C | 427859 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2004 | 5 YR 5-03--OTIS--ALARM IN CAR INOP--NUMBER MACHINE IN MACH RM | TOM | TOM | | H02 | C | 427851 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/27/2002 | OTIS | TOM | TOM | | H01 | C | 427843 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/29/2002 | 5 YR 6-98--OTIS | TOM | TOM | | H02 | C | 427835 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/28/2001 | 5 YR 6-98--OTIS--PHONE INOP | TOM | TOM | | H01 | P | 427827 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/2001 | 5 YR 6-98--OTIS | TOM | TOM | | H02 | C | 427819 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/28/2000 | | LES | LES | | H01 | C | 427811 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/1999 | 5 YR 6-98 | TOM | TOM | | H01 | C | 427803 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/16/1999 | | RUSS | RUSS | | H02 | C | 427619 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/03/1998 | | RUSS | RUSS | | H01 | C | 427611 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/1998 | | RUSS | RUSS | | H02 | C | 427604 |
PENROSE HOSPITAL FACILITIES | H01 | R | 09/29/1997 | nds fire service | RUSS | RUSS | | H01 | R | 427795 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/18/1997 | still needs f. service | RUSS | RUSS | | H02 | R | 427787 |
PENROSE HOSPITAL FACILITIES | H01 | R | 09/10/1996 | nds fire service | RUSS | RUSS | | H01 | R | 427779 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/29/1996 | f.s., | RUSS | RUSS | | H02 | R | 427771 |
PENROSE HOSPITAL FACILITIES | H01 | R | 09/13/1995 | nds.fire serv. | RUSS | RUSS | | H01 | R | 427763 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/28/1995 | no change | RUSS | RUSS | | H02 | R | 427755 |
PENROSE HOSPITAL FACILITIES | H01 | R | 09/07/1994 | NDS FIRE SERVICE | RUSS | RUSS | | H01 | R | 427747 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/28/1994 | | RUSS | RUSS | | H02 | C | 427739 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/15/1993 | 5YR4-93 | RUSS | RUSS | | H01 | C | 427731 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/16/1993 | FIRE SERV. | RUSS | RUSS | | H02 | R | 427718 |
PENROSE HOSPITAL FACILITIES | H01 | R | 09/14/1992 | FR SERV,5YR8-88 | RUSS | RUSS | | H01 | R | 427692 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/25/1992 | F.SERV | RUSS | RUSS | | H02 | R | 427684 |
PENROSE HOSPITAL FACILITIES | H01 | R | 09/16/1991 | F.SERV. | RUSS | RUSS | | H01 | R | 427675 |
PENROSE HOSPITAL FACILITIES | H02 | P | 03/25/1991 | FR SERV,PHN NOT NEC | RUSS | RUSS | | H02 | P | 427668 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/13/1990 | PHN,FIRE SERV | RUSS | RUSS | | H01 | P | 427660 |
PENROSE HOSPITAL FACILITIES | H02 | P | 03/13/1990 | FR SERV | RUSS | RUSS | | H02 | P | 427651 |
PENROSE HOSPITAL FACILITIES | H01 | R | 09/21/1989 | ORDER: NEEDS FIRE SVC | RUSS | RUSS | | H01 | R | 427643 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/16/1989 | ORDER:NEED FIRE SERVICE | RUSS | RUSS | | H02 | R | 427635 |
PENROSE HOSPITAL FACILITIES | H16 | C | 09/07/1988 | INIT INSP, PERMIT ISS'D | RUSS | RUSS | | H16 | C | 427627 |