PENROSE HOSPITAL FACILITIES | H02 | C | 03/25/2024 | HO2 -- 5 YR 7/22 -- CAT1 -- 9/23 -- OTIS & SERVICE -- DID NOT SEE ANY LOGS IN MCP OF SUSPENSION ROPES BEING REPLACED FROM PRIOR ELEVATOR INSPECTION 6 MONTHS AGO -- 60 DAYS TO ADDRESS TO PREVENT ELEVATOR REMOVED FROM SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2046174) | BENH | BENH | | H02 | C | 8032521 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/27/2023 | ANNUAL 1/23 -- OTIS & SERVICE -- COUNTERWEIGHT SUSPENSION ROPES AT THE 9TH FLOOR ARE READING .474 INCHES & ROUGED, MINIMUM ALLOWABLE DIAMETER IS .484 INCHES -- ALL SUSPENSION ROPES WILL NEED TO BE REPLACED -- 60 DAYS TO ADDRESS -- PIT NEEDS CLEANING (Receipt #1992601) | BENH | BENH | | H01 | C | 7869583 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/28/2023 | H02 -- ACCEPTANCE AND 5YR 07/2022 -- OTIS AND SERVICE --/ SEE #N80537 FOR ITEMS THAT NEED ADDRESSED | MIKEM | MIKEM | | H02 | C | 7700606 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/22/2022 | ELEVATOR UNDER MODERNIZATION (Receipt #1901473) | BENH | BENH | | H01 | C | 7526692 |
PENROSE HOSPITAL FACILITIES | H06 | C | 07/07/2022 | WITNESSED ACCEPTANCE TO MODERNIZATION - SEE #N80537 FOR ITEMS THAT NEED ADDRESSED (Next 5 year date moved to 9/2027 to align cars in group and H01 RV) | ROBERTV | ROBERTV | | H06 | C | 7437903 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/02/2022 | ELEVATOR UNDER MODERNIZATION - PERMIT #N80357 | ROBERTV | ROBERTV | | H02 | C | 7287025 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2021 | 5YR -- 1/19 -- CAT1 -- 6/21 -- OTIS AND SERVICE. UNIT OUT OF SERVICE AT TIME OF INSPECTION. COMPENSATION ROPE TENSIONING HAS NOT BEEN PERFORMED (2ND NOTICE). MISSING ANNUAL TEST TAGS AT CONTROLLER. (NOTE: DRIVE MACHINE SHEAVE IS AT MAXIMUM GROOVE WEAR AND DRIVE MACHINE BLOWER HAS BEEN ELECTRICALLY DISCONNECTED) (Receipt #1808086) | ROBERTV | ROBERTV | | H01 | C | 7112621 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/12/2021 | H02 -- 5YR -- 1/19 -- CAT1 -- 4/20 -- OTIS AND SERVICE. CHECK PREVIOUS LISTED ITEMS AT H01 cat 1 6/21 | ROBERTV | ROBERTV | | H02 | C | 6898788 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/23/2020 | 5YR -- 1/19 -- CAT1 -- 4/20 -- OTIS AND SERVICE. COMPENSATION ROPES NEEDS TO BE TENSIONED. CAR TOP OPERATING STATION WORKS INTERMITTENTLY. (Receipt #1715709) | ROBERTV | ROBERTV | | H01 | C | 6717136 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/20/2020 | H02 -- FOLLOW UP SCHEDULED WITH TKE FOR 60 DAYS FOR ITEMS LISTED IN PREVIOUS INSPECTION REPORT cat 1 4/20 | ROBERTV | ROBERTV | | H02 | C | 6517026 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/23/2019 | 5YR 1/19--OTIS W/ TKE SERVICE--BACK COUNTERWEIGHT ROLLER COMING APART (Receipt #1631871) | CALE | CALE | | H01 | C | 6343793 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/2019 | 5 YEAR 1/19 OTIS, HO2 | ERIC | ERIC | | H02 | C | 6141510 |
PENROSE HOSPITAL FACILITIES | H06 | C | 01/16/2019 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS AND ALARM BELL NOT WORKING, CLEAN PITS (Receipt #1571351) | ERIC | ERIC | | H06 | C | 6086084 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2018 | 5YR--9--13--OTIS --AND TKE SERVICE --ROPE STRETCHED AND ALLOWING THE COUNTER WEIGHT TO HIT THE BUFFER (Receipt #1539340) | JOHNW | JOHNW | | H01 | C | 5970986 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/29/2018 | 5YR--9--13--OTIS --TKE --ANNUAL 12--17--LOCKBOX ON THIS MECH ROOM AND 8 & 9 | JOHNW | JOHNW | | H02 | C | 5802318 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/22/2017 | 5YR -- 9/13 -- OTIS W/ TKE SERVICE. ANNUAL CATEGORY 1 TESTING DUE WITHIN 30 DAYS (Receipt #1454605) | ROBERTV | ROBERTV | | H01 | C | 5633677 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/23/2017 | H02 -- 5YR -- 9/13 -- OTIS W/ TKE SERVICE | ROBERTV | ROBERTV | | H02 | C | 5453370 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/27/2016 | 5 YEAR 9/13 OTIS. ROPES HAVE BEEN REPLACED (Receipt #1365411) | ERIC | ERIC | | H01 | C | 5303397 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/2016 | 5YR---9--13--OTIS MISSING ANNUAL TAG --SUSPENSION ROPES ARE ROUGHED AND BEYOND THEIR LIMITS ROPES MUST BE REPLACED--NEED MCP IN MACHINE ROOM | ERIC | ERIC | | H02 | C | 5160496 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2015 | 5YR -- 9/13 -- OTIS. MISSING ANNUAL TAG, COUNTERWEIGHT SIDE SUSPENSION ROPES AT 8TH FLOOR ARE WORN BEYOND LIMIITS (MUST BE REPLACED), COUNTERWEIGHT ROLLERS DAMAGED (Receipt #1290280) | ROBERTV | ROBERTV | | H01 | C | 5047171 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2015 | 5YR--9--13--OTIS --MISSING ANNUAL TAG--ROPES ARE WORN BEYOND LIMITS 8TH FLOOR --COUNTER WEIGHT ROLLER DAMAGE | JOHNW | JOHNW | | H02 | C | 4926351 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/2014 | 5YR--9--13--OTIS --ROPE WORN BEYOND LIMITS AT THE 8TH FLOOR--COUNTER WEIGHT ROLLERS DAMAGED (Receipt #1222671) | JOHNW | JOHNW | | H01 | C | 4824318 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/25/2014 | 5 YR 9/13 H02 | ERIC | ERIC | | H02 | C | 4708025 |
PENROSE HOSPITAL FACILITIES | H06 | C | 09/23/2013 | WITNESSED 5 YEAR SAFETY TEST. NEED CAR TOP STOP SWITCH, NUMBER HOISTWAY DOORS, ROPES NEED TO BE CLEANED, CLEAN MACHINE ROOM AND SECONDARY MACHINE SPACE AND HAS DAMAGED PICKUP ROLLER AT 12 (Receipt #1155306) | ERIC | ERIC | | H06 | C | 4608467 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/16/2013 | HO1 COINCIDES WITH HO6 (Receipt #1155300) | ERIC | ERIC | | H01 | C | 4608463 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/2013 | 5YR--7--08--OTIS --ROPES NEED TO BE CLEANED -----------------------------CAB LIGHT CIRCUIT BOTTOM OF THE STAIRS LEADING TO THE MECH ROOM | JOHNW | JOHNW | | H02 | C | 4491919 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/19/2012 | 5 YR 7-08--OTIS (Receipt #1082920) | TOM | TOM | | H01 | C | 4392050 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/27/2012 | 5 YR 7-08--OTIS | TOM | TOM | | H02 | C | 4290607 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/21/2011 | 5 YR 7-08--OTIS (Receipt #1003041) | TOM | TOM | | H01 | C | 4215305 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/09/2011 | 5 YR 7-08--OTIS--PHONE INCAR NOT WORKING | TOM | TOM | | H02 | C | 4129106 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/13/2010 | 5 YR 7-08--OTIS (Receipt #936129) | TOM | TOM | | H01 | C | 4049129 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/25/2010 | 5 yr 7-08--otis | TOM | TOM | | H02 | C | 3960102 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2009 | 5 YR 7-08 OTIS (Receipt #878686) | TOM | TOM | | H01 | C | 3892317 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2009 | 5YR 7-08--OTIS | TOM | TOM | | H02 | C | 3818680 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/25/2008 | 5yr--7--08--otis (Receipt #828023) | TOM | TOM | | H01 | C | 3746592 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/20/2008 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H02 | C | 428733 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/26/2007 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H01 | C | 428725 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/2007 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H02 | C | 428718 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/2006 | 5YR--5--03--OTIS--ALARM INOP | JOHNW | JOHNW | | H01 | C | 428709 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2006 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H02 | C | 428701 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/28/2005 | RP--5--03--OTIS--ALARM IN CAR NOT WORKING | JOHNW | JOHNW | | H01 | C | 428693 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2005 | 5 YR 5-03--OTIS--CK ALARM NEXT INSP | TOM | TOM | | H02 | C | 428686 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2004 | 5 YR--5--03--OTIS--FAN ON MACHINE OUT OF BALANCE -- ALARM OUT--CARPET ON THE ROPES IS WORN OUT AND HANGING DOWN IN THE MACHINE | JOHNW | JOHNW | | H01 | C | 428679 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2004 | ALARM IN CAR INOP | TOM | TOM | | H02 | C | 428670 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/27/2002 | 5 YR 6-98--OTIS | TOM | TOM | | H01 | C | 428663 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/29/2002 | 5 YR 6-98--OTIS | TOM | TOM | | H02 | C | 428655 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/28/2001 | 5 YR 6-98--OTIS | TOM | TOM | | H01 | C | 428647 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/2001 | 5 YR 6-98--OTIS | TOM | TOM | | H02 | C | 428639 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/28/2000 | STILL NO 5 YR TAG | LES | LES | | H01 | P | 428630 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/29/1999 | NO 5 YR TAG | TOM | TOM | | H01 | P | 428622 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/15/1999 | | RUSS | RUSS | | H02 | C | 428461 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/02/1998 | | RUSS | RUSS | | H01 | C | 428454 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/1998 | | RUSS | RUSS | | H02 | C | 428447 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/23/1997 | | RUSS | RUSS | | H01 | C | 428610 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/18/1997 | | RUSS | RUSS | | H02 | C | 428602 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/10/1996 | | RUSS | RUSS | | H01 | C | 428594 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/29/1996 | fire serv test bombed | RUSS | RUSS | | H02 | R | 428584 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/13/1995 | f.s.not tested | RUSS | RUSS | | H01 | P | 428576 |
PENROSE HOSPITAL FACILITIES | H02 | P | 03/28/1995 | being modernized | RUSS | RUSS | | H02 | P | 428569 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/06/1994 | BEING MODERNIZED | RUSS | RUSS | | H01 | P | 428561 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/28/1994 | | RUSS | RUSS | | H02 | C | 428554 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/15/1993 | 5YR4-93 | RUSS | RUSS | | H01 | C | 428546 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/16/1993 | FIRE SERV. | RUSS | RUSS | | H02 | R | 428539 |
PENROSE HOSPITAL FACILITIES | H01 | R | 09/14/1992 | FR SERV.5YR8-88 | RUSS | RUSS | | H01 | R | 428534 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/25/1992 | F. SERV | RUSS | RUSS | | H02 | R | 428527 |
PENROSE HOSPITAL FACILITIES | H01 | R | 09/16/1991 | F.SERV. | RUSS | RUSS | | H01 | R | 428515 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/22/1991 | FR SERV | RUSS | RUSS | | H02 | R | 428507 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/13/1990 | PHN,FIRE SERV | RUSS | RUSS | | H01 | P | 428499 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/13/1990 | FR SERV | RUSS | RUSS | | H02 | R | 428491 |
PENROSE HOSPITAL FACILITIES | H01 | R | 09/21/1989 | ORDER: NEEDS FIRE SVC | RUSS | RUSS | | H01 | R | 428484 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/15/1989 | ORDER: NEED FIRE SERVICE | RUSS | RUSS | | H02 | R | 428476 |
PENROSE HOSPITAL FACILITIES | H16 | C | 09/07/1988 | INIT INSP, PERMIT ISS'D | RUSS | RUSS | | H16 | C | 428467 |