PENROSE HOSPITAL FACILITIES | H02 | C | 03/25/2024 | HO2 -- 5 YR 10/20 -- ANNUAL 10/23 -- TKE W/ OTIS SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2046134) | BENH | BENH | | H02 | C | 8032403 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2023 | 5YR -- 10/20 -- ANNUAL 12/22 -- TKE W/ OTIS SERVICE -- ELEVATOR WAS FAULTED OUT AT TIME OF INSPECTION -- HOLD PERMIT TO OPERATE UNTIL ELEVATOR IS BACK IN SERVICE AND OWNER HAS CONTACTED P.P.R.B.D. TO COME BACK OUT & RE-INSPECT (Receipt #1990197) | BENH | BENH | | H01 | C | 7862687 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/2023 | HO2 -- ANNUAL 12/22 -- TKE & OTIS -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7702317 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/21/2022 | 5 YEAR 10/20 -- ANNUAL 10/21 -- TKE W/ OTIS SERVICE -- EMERGENCY LIGHT & ALARM BELL ARE NONFUNCTIONAL WHEN CAB 110V IS DISCONNECTED -- EMERGENCY LIGHT COVER ON C.O.P. IS MISSING -- DRIVE MACHINE IS LEAKING OIL IN MACHINE ROOM (Receipt #1901181) (cat 1 -- 12/22, emergency light and alarm bell working per report, check remaining items at next inspection) | BENH | BENH | | H01 | C | 7525464 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/2022 | HO2 -- ANNUAL 10/21 -- TKE W/ OTIS SERVICE | BENH | BENH | | H02 | C | 7319569 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2021 | 5YR -- 10/20 -- TKE W/ OTIS SERVICE. "B" FLOOR DIRECTIONAL LANTERN NOT WORKING. SECURE CAR TOP ESCAPE HATCH. 3RD FLOOR HOISTWAY INTERMEDIATE CONNECTING CABLE NEEDS ATTENTION. (Receipt #1808125) (Cat 1 performed 10/2021) | ROBERTV | ROBERTV | | H01 | C | 7112796 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/12/2021 | H02 -- 5YR -- 10/20 -- OTIS AND SERVICE. | ROBERTV | ROBERTV | | H02 | C | 6898743 |
PENROSE HOSPITAL FACILITIES | H06 | C | 10/22/2020 | WITNESSED 5 YEAR SAFETY TEST. ROPES ARE ROUGED AND UNDERSIZED, SCHEDULED FOR REPLACEMENT (Ropes have been replaced per Otis 2/2021 RV) (Receipt #1723850) | ERIC | ERIC | | H06 | C | 6751192 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2020 | 5YR -- 11/15 -- CAT1 -- 4/20 -- OTIS W/ TKE KEYS AND OTIS SERVICE. ROUGED AND UNDERSIZED ROPES SCHEDULED TO BE REPLACED. 5 YEAR WITNESS TEST DUE 11/2020 (Receipt #1717601) | ROBERTV | ROBERTV | | H01 | C | 6725268 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/20/2020 | H02 -- FOLLOW UP SCHEDULED WITH TKE FOR 60 DAYS FOR ITEMS LISTED IN PREVIOUS INSPECTION REPORT cat 1 4/20 | ROBERTV | ROBERTV | | H02 | C | 6517014 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/23/2019 | 5YR 11/15--ANNUAL 11/17--OTIS W/ TKE SERVICE--REQUIRED ANNUAL TRACTION SAFETY TEST PAST DUE--NOTE: MONITOR ROPES DUE TO ROUGE APPEARING (Receipt #1632021) | CALE | CALE | | H01 | C | 6344378 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/27/2019 | 5 YEAR 11/15 OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 6146420 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2018 | 5YR--11--15--TKE SERVICE --ANNUAL 11--17--LOCKBOX ON MECH ROOM 4,5,AND 6 (Receipt #1539251) | JOHNW | JOHNW | | H01 | C | 5970814 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/28/2018 | 5YR --11--15--TKE --ANNUAL 11--17-------------------------------------------------LOCKBOX AT ELEVATORS 8 & 9---MISSING ANTI ROTATION CABLES ON CAR AND COUNTERWEIGHT | JOHNW | JOHNW | | H02 | C | 5801771 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/22/2017 | 5YR -- 11/15 -- OTIS W/ TKE MOD AND SERVICE. NEED ANTI-ROTATION CABLES ON CAR AND COUNTERWEIGHT ROPE SHACKLES. ANNUAL CATEGORY 1 TESTING DUE WITHIN 30 DAYS. (Receipt #1454564) | ROBERTV | ROBERTV | | H01 | C | 5633573 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/24/2017 | 5YR -- 11/15 -- OTIS W/ TKE MOD. NEED CATEGORY 1 TESTING PERFORMED | ROBERTV | ROBERTV | | H02 | C | 5454696 |
PENROSE HOSPITAL FACILITIES | HE16 | C | 03/16/2017 | Changed H01 to H02 to accommodate owner billing. | ROBERTV | ROBERTV | | HE16 | C | 5442632 |
PENROSE HOSPITAL FACILITIES | H02 | C | 09/27/2016 | 5YR -- 11/15 -- OTIS/TKE MOD AND SERVICE. EMERGENCY PHONE NOT WORKING | ROBERTV | ROBERTV | | H02 | C | 5303159 |
PENROSE HOSPITAL FACILITIES | H01 | C | 03/22/2016 | 5YR--11/15--OTIS --ELEVATOR HAS BEEN MODERNIZED --NEED MCP IN MACHINE ROOM (Receipt #1319609) | ERIC | ERIC | | H01 | C | 5160418 |
PENROSE HOSPITAL FACILITIES | H06 | C | 11/18/2015 | ACCEPTANCE TO MOD | ERIC | ERIC | | H06 | C | 5783971 |
PENROSE HOSPITAL FACILITIES | H02 | C | 09/21/2015 | 5 YEAR 9/13 OTIS. ROPES ARE ROUGING, HO2 | ERIC | ERIC | | H02 | C | 5042833 |
PENROSE HOSPITAL FACILITIES | H01 | C | 03/27/2015 | 5YR--9--13--OTIS --TAG GOVENOR--NEED ANNUAL TAG --ROPES ARE ROUGHING (Receipt #1252861) | JOHNW | JOHNW | | H01 | C | 4924543 |
PENROSE HOSPITAL FACILITIES | H02 | C | 09/29/2014 | 5YR--9--13--OTIS --TAG GOVENOR --ALARM IN CAB NOT WORKING --ROPES AR ROUGHING | JOHNW | JOHNW | | H02 | C | 4824207 |
PENROSE HOSPITAL FACILITIES | H01 | C | 03/31/2014 | 5YR- 9--13--OTIS--GOVENOR NOT TAGGED --ALARM BELL NOT WORKING --ROPES ARE ROUGING (Receipt #1186447) | JOHNW | JOHNW | | H01 | C | 4711372 |
PENROSE HOSPITAL FACILITIES | H02 | C | 09/23/2013 | H02 COINCIDES WITH H06 | ERIC | ERIC | | H02 | C | 4608485 |
PENROSE HOSPITAL FACILITIES | H06 | C | 09/18/2013 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS AND ALARM BELL NOT WORKING (Receipt #1155321) | ERIC | ERIC | | H06 | C | 4608487 |
PENROSE HOSPITAL FACILITIES | H01 | C | 03/22/2013 | 5YR--7--08--OTIS---ROPES ARE ROUGING NEED TO MONITOR FREQUENTLY. -----------------------5YR TAG ON #9 GOVENOR (Receipt #1118586) | JOHNW | JOHNW | | H01 | C | 4491932 |
PENROSE HOSPITAL FACILITIES | H02 | C | 09/19/2012 | 5 YR 7-08--OTIS ALARM IN CAR NOT WORKING / POST FLOOR DESIGNATION NUMBERS AT ALL LANDINGS / GOVENOR NOT TAGGED | TOM | TOM | | H02 | C | 4392044 |
PENROSE HOSPITAL FACILITIES | H01 | C | 03/26/2012 | 5 YR 7-08 OTIS--ALARM IN CAR NOT WORKING (Receipt #1036478) | TOM | TOM | | H01 | C | 4290599 |
PENROSE HOSPITAL FACILITIES | H02 | C | 09/21/2011 | 5 YR 7-08--OTIS--HANDRAIL LOOSE IN CAR | TOM | TOM | | H02 | C | 4215275 |
PENROSE HOSPITAL FACILITIES | H01 | C | 03/09/2011 | 5 YR 7-08--OTIS--ALSRM & STOP SWITCH BELLS NOT WORKING IN CAR (Receipt #966468) | TOM | TOM | | H01 | C | 4129094 |
PENROSE HOSPITAL FACILITIES | H02 | C | 09/13/2010 | 5 YR 7-08--OTIS | TOM | TOM | | H02 | C | 4049118 |
PENROSE HOSPITAL FACILITIES | H01 | C | 03/25/2010 | 5 yr 7-08--otis (Receipt #902377) | TOM | TOM | | H01 | C | 3960071 |
PENROSE HOSPITAL FACILITIES | H02 | C | 09/30/2009 | 5 YR 7-08 OTIS | TOM | TOM | | H02 | C | 3892299 |
PENROSE HOSPITAL FACILITIES | H01 | C | 03/31/2009 | 5YR 7-08 OTIS (Receipt #852305) | TOM | TOM | | H01 | C | 3818675 |
PENROSE HOSPITAL FACILITIES | H02 | C | 09/25/2008 | 5yr--7--08--otis | TOM | TOM | | H02 | C | 3746638 |
PENROSE HOSPITAL FACILITIES | H01 | C | 03/21/2008 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H01 | C | 430970 |
PENROSE HOSPITAL FACILITIES | H02 | C | 09/15/2007 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H02 | C | 430962 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/2007 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H02 | C | 430954 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/2006 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H01 | C | 430946 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2006 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H02 | C | 430939 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2005 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H01 | C | 430930 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2005 | 5 YR 5-03--OTIS | TOM | TOM | | H02 | C | 430923 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2004 | 5YR--5--03--OTIS | JOHNW | JOHNW | | H01 | C | 430915 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2004 | 5 YR 5-03--OTIS--NO PHONE | TOM | TOM | | H02 | C | 430903 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/27/2002 | OTIS--NEED PHONE | TOM | TOM | | H01 | C | 430894 |
PENROSE HOSPITAL FACILITIES | H02 | P | 03/29/2002 | 5 YR 6-98--OTIS--PHONE MISSING FROM CAR | TOM | TOM | | H02 | P | 430886 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/28/2001 | 5 YR 6-98--PHONE MISSING FROM CAR | TOM | TOM | | H01 | P | 430880 |
PENROSE HOSPITAL FACILITIES | H02 | P | 03/30/2001 | 5 YR 6-98--OTIS--PHONE STILL MISSING FROM CAR | TOM | TOM | | H02 | P | 430869 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/28/2000 | PHONE MISSING | LES | LES | | H01 | P | 430850 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/16/1999 | 5 YR 6-98 | TOM | TOM | | H01 | C | 430840 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/15/1999 | | RUSS | RUSS | | H02 | C | 430673 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/03/1998 | | RUSS | RUSS | | H01 | C | 430667 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/1998 | | RUSS | RUSS | | H02 | C | 430658 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/1997 | | RUSS | RUSS | | H01 | C | 430832 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/18/1997 | | RUSS | RUSS | | H02 | C | 430824 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/10/1996 | | RUSS | RUSS | | H01 | C | 430814 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/29/1996 | | RUSS | RUSS | | H02 | C | 430803 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/13/1995 | | RUSS | RUSS | | H01 | C | 430795 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/1995 | | RUSS | RUSS | | H02 | C | 430784 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/06/1994 | | RUSS | RUSS | | H01 | C | 430776 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/28/1994 | | RUSS | RUSS | | H02 | C | 430769 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/15/1993 | 5YR4-93 | RUSS | RUSS | | H01 | C | 430760 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/15/1993 | | RUSS | RUSS | | H02 | C | 430753 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/14/1992 | 5YR8-88 | RUSS | RUSS | | H01 | C | 430744 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/24/1992 | | RUSS | RUSS | | H02 | C | 430738 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/16/1991 | | RUSS | RUSS | | H01 | C | 430728 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/1991 | PHN NOT NEC | RUSS | RUSS | | H02 | C | 430721 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/13/1990 | PHN | RUSS | RUSS | | H01 | P | 430713 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/13/1990 | | RUSS | RUSS | | H02 | C | 430704 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/21/1989 | ORDER: NEEDS PIT LADDER | RUSS | RUSS | | H01 | P | 430697 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/16/1989 | ORDER: NEED PT LDR | RUSS | RUSS | | H02 | R | 430689 |
PENROSE HOSPITAL FACILITIES | H16 | C | 09/07/1988 | INIT INSP, PERM ISS'D | RUSS | RUSS | | H16 | C | 430681 |