PENROSE HOSPITAL FACILITIES | H02 | C | 03/25/2024 | HO2 -- 5 YR 10/21 -- ANNUAL 10/23 -- OTIS & SERVICE -- MECHANIC TO DIAGNOSE ROUGH CAR RIDE -- BUILDING TO REMOVE NON-ELEVATOR RELATED ITEMS FROM MACHINE ROOM -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2046202) | BENH | BENH | | H02 | C | 8032585 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/21/2023 | 5YR 10/2021 -- ANNUAL 2/23 -- OTIS & SERVICE -- MACHINE ROOM CLEANLINESS NEEDS SOME ATTENTION (Receipt #1990467) cat 1 10/23 BH | BENH | BENH | | H01 | C | 7863296 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/03/2023 | H02 -- 5 YEAR 10/21 -- ANNUAL 2/23 -- OTIS & SERVICE -- / CHECK PREVIOUS ITEMS AT H01 INSPECTION | DUSTINS | DUSTINS | | H02 | C | 7676841 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/23/2022 | ANNUAL 10/21 -- OTIS & SERVICE -- NON ELEVATOR RELATED ITEMS NEED TO BE REMOVED FROM MACHINE ROOM -- VICTAULIC FITTINGS IN MACHINE ROOM ARE LEAKING OIL -- MONITOR ROUGE ROPES ON FLOOR STRIKE SIDE (Receipt #1901655) | BENH | BENH | | H01 | C | 7527538 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/2022 | HO2 -- WITNESSED ON 10/21 -- OTIS & SERVICE -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7319608 |
PENROSE HOSPITAL FACILITIES | H06 | C | 10/12/2021 | WITNESSED ROPED HYDRO SAFETY TESTING W/ OTIS - DIRECTIONAL INDICATOR AUDIBLE SIGNAL NOT WORKING. "1" FLOOR MISSING HOISTWAY DOOR SAFETY RETAINER. LOW OIL PROTECTION NOT WORKING. (Receipt #1813951) | ROBERTV | ROBERTV | | H06 | C | 7138043 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2021 | 5YR -- 10/16 -- CAT1 -- 1/20 -- OTIS AND SERVICE. "LL" HOISTWAY DOOR MISSING UPPER AND LOWER DOOR RESTRICTOR FLAGS. DIRECTIONAL INDICATOR AUDIBLE SIGNAL NOT WORKING. "1" FLOOR MISSING HOISTWAY DOOR SAFETY RETAINER........... ITEMS NEED TO BE COMPLETED BY 5 YEAR FULL LOAD TEST DUE BY 10/31/2021 (Receipt #1808133) | ROBERTV | ROBERTV | | H01 | C | 7112830 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/12/2021 | H02 -- 5YR -- 10/16 -- CAT1 -- 1/20 -- OTIS AND SERVICE. CHECK PREVIOUS LISTED ITEMS AT H01 | ROBERTV | ROBERTV | | H02 | C | 6898825 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2020 | 5YR -- 10/16 -- OTIS AND SERVICE. COULD NOT LOCATE CURRENT CATEGORY TESTING FORM, LAST RECORDED 10/2018. LEFT PIT ROPE FASTENING SWITCH MISSING COTTER PIN. (Receipt #1717609) (Cat 1 performed 10/2020) | ROBERTV | ROBERTV | | H01 | C | 6725287 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/20/2020 | H02 -- FOLLOW UP SCHEDULED WITH TKE FOR 60 DAYS FOR ITEMS LISTED IN PREVIOUS INSPECTION REPORT | ROBERTV | ROBERTV | | H02 | C | 6517056 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/23/2019 | RP 10/18--OTIS W/ TKE SERVICE--LOCKBOX ON MECH ROOM #10 (Receipt #1632032) | CALE | CALE | | H01 | C | 6344433 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/27/2019 | RP 10/18 OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 6146426 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2018 | RP--10--17--OTIS --TKE SERVICE (Receipt #1539370) | JOHNW | JOHNW | | H01 | C | 5971063 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/29/2018 | RP--11--17--OTIS --TKE SERIVCE --LOCKBOX ON #14 ELEVATOR MECH RM | JOHNW | JOHNW | | H02 | C | 5802175 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/22/2017 | RP -- 10/16 -- OTIS W/ TKE SERVICE. ANNUAL CATEGORY 1 DUE BY 10/31/2017, EMERGENCY LIGHT NOT WORKING. (Receipt #1454600) | ROBERTV | ROBERTV | | H01 | C | 5633657 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/23/2017 | H02 -- WITNESSED 10/2016 | ROBERTV | ROBERTV | | H02 | C | 5453381 |
PENROSE HOSPITAL FACILITIES | H06 | C | 10/24/2016 | WITNESSED 5 YEAR (Receipt #1374928) | ERIC | ERIC | | H06 | C | 5325560 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/27/2016 | 5YR -- 10/11 -- 1YR -- 2/16 -- OTIS. EMERGENCY LIGHT AND BELL NOT WORKING, MISSING FIRE SERVICE TEST LOG, 5 YEAR ROPED HYDRAULIC TEST DUE NEXT MONTH. (Receipt #1365822) | ROBERTV | ROBERTV | | H01 | C | 5303248 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/2016 | RP--2--16--OTIS--NEED MCP IN MACHINE ROOM | ERIC | ERIC | | H02 | C | 5160469 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2015 | RP -- 9/14 -- OTIS. CONTROLLER HARD FAULTS AFTER HOISTWAY INSPECTION, (Receipt #1290397) | ROBERTV | ROBERTV | | H01 | C | 5047613 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2015 | RP--9--14--OTIS | JOHNW | JOHNW | | H02 | C | 4926392 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/2014 | RP--8--13--OTIS--EMERGENCY LIGHTS IN CAB (Receipt #1222654) | JOHNW | JOHNW | | H01 | C | 4824274 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/25/2014 | RP 8/13 H02 | ERIC | ERIC | | H02 | C | 4708015 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/06/2013 | RP 8-13-OTIS (Receipt #1156728) | TOM | TOM | | H01 | C | 4612713 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/2013 | RP--4--12--OTIS | JOHNW | JOHNW | | H02 | C | 4492046 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/20/2012 | RP 4-12--OTIS (Receipt #1091688) | TOM | TOM | | H01 | C | 4392053 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/27/2012 | ROPED-HYDRO--5 YR TEST & PRESSURE TEST NOV--11 | TOM | TOM | | H02 | C | 4290610 |
PENROSE HOSPITAL FACILITIES | H06 | C | 11/04/2011 | WITNESSED 5 YEAR SAFETY TEST AND PRESSURE RELIEF TEST FOR ROPED HYDRO (Receipt #1010490) | ERIC | ERIC | | H06 | C | 4231549 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/21/2011 | RP 5-11-OTIS (Receipt #1003044) | TOM | TOM | | H01 | C | 4215311 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/10/2011 | RP 5-10--OTIS | TOM | TOM | | H02 | C | 4129129 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/15/2010 | RP 5-10--OTIS (Receipt #936153) | TOM | TOM | | H01 | C | 4049160 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/25/2010 | rp 2-09--otis | TOM | TOM | | H02 | C | 3960098 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/30/2009 | RP 2-09 OTIS (Receipt #878679) | TOM | TOM | | H01 | C | 3892310 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2009 | RP 3-08--OTIS | TOM | TOM | | H02 | C | 3818694 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/26/2008 | rp--3--08--otis (Receipt #828105) | TOM | TOM | | H01 | C | 3746713 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/21/2008 | RP--2--08--OTIS | JOHNW | JOHNW | | H02 | C | 435625 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/24/2007 | RP--11--06--OTIS | JOHNW | JOHNW | | H01 | C | 435617 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/2007 | OLD ELEVATOR NOT IN SERVICE / 10# IS NOW THE NEW ELEVATOR ACROSS THE HALL | JOHNW | JOHNW | | H02 | C | 435609 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/28/2006 | RP--8--06--OTIS | JOHNW | JOHNW | | H01 | C | 435601 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2006 | RP--8--05--OTIS
| JOHNW | JOHNW | | H02 | C | 435594 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/2005 | RP--8--05--OTIS | JOHNW | JOHNW | | H01 | C | 435586 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2005 | RP 10-04--OTIS--WILL REMOVE THIS CAR AT NEXT PHASE OF CONST. | TOM | TOM | | H02 | C | 435577 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/2004 | RP10-03--OTIS--NO PHONE | JOHNW | JOHNW | | H01 | C | 435569 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/31/2004 | RP 10-03--OTIS--NO PHONE | TOM | TOM | | H02 | C | 435561 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/27/2002 | OTIS--NEED PHONE | TOM | TOM | | H01 | C | 435553 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/29/2002 | RP 7-01--OTIS | TOM | TOM | | H02 | C | 435545 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/28/2001 | RP 7-01--OTIS--NO PHONE IN CAR--LIGHT BULB GUARDING | TOM | TOM | | H01 | P | 435537 |
PENROSE HOSPITAL FACILITIES | H02 | P | 03/30/2001 | RP 7-00--OTIS--NO PHON IN CAR--LIGHT BULB GUARDING | TOM | TOM | | H02 | P | 435529 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/27/2000 | RP 7-00--OTIS | TOM | TOM | | H01 | C | 435521 |
PENROSE HOSPITAL FACILITIES | H01 | C | 12/17/1999 | | TOM | TOM | | H01 | C | 435513 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/03/1998 | | RUSS | RUSS | | H01 | C | 435348 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/1998 | | RUSS | RUSS | | H02 | C | 435340 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/29/1997 | | RUSS | RUSS | | H01 | C | 435505 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/21/1997 | | RUSS | RUSS | | H02 | C | 435497 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/10/1996 | | RUSS | RUSS | | H01 | C | 435490 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/29/1996 | rp6-95 | RUSS | RUSS | | H02 | C | 435482 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/13/1995 | | RUSS | RUSS | | H01 | C | 435474 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/29/1995 | | RUSS | RUSS | | H02 | C | 435466 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/07/1994 | | RUSS | RUSS | | H01 | C | 435458 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/30/1994 | | RUSS | RUSS | | H02 | C | 435450 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/15/1993 | | RUSS | RUSS | | H01 | C | 435442 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/15/1993 | | RUSS | RUSS | | H02 | C | 435434 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/14/1992 | RP8-92 | RUSS | RUSS | | H01 | C | 435426 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/24/1992 | | RUSS | RUSS | | H02 | C | 435419 |
PENROSE HOSPITAL FACILITIES | H01 | C | 09/16/1991 | | RUSS | RUSS | | H01 | C | 435412 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/22/1991 | PHN NOT NEC | RUSS | RUSS | | H02 | C | 435402 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/13/1990 | PHN | RUSS | RUSS | | H01 | P | 435394 |
PENROSE HOSPITAL FACILITIES | H02 | C | 03/14/1990 | | RUSS | RUSS | | H02 | C | 435386 |
PENROSE HOSPITAL FACILITIES | H01 | P | 09/21/1989 | ORDER: NEEDS PIT LADDER | RUSS | RUSS | | H01 | P | 435378 |
PENROSE HOSPITAL FACILITIES | H02 | R | 03/16/1989 | ORDER: NEED PT LDR, WIRED ALM TO ST SW | RUSS | RUSS | | H02 | R | 435370 |
PENROSE HOSPITAL FACILITIES | H16 | R | 12/27/1988 | NOTHING DONE | RUSS | RUSS | | H16 | R | 435363 |
PENROSE HOSPITAL FACILITIES | H16 | C | 09/09/1988 | INIT INSP, PERM ISS'D, ORDER: NO PIT LDR | RUSS | RUSS | | H16 | C | 435355 |