MEMORIAL HOSPITAL | H02 | C | 03/06/2024 | HO2 -- ANNUAL 11/23 -- TKE & SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION LOGS AND ELEVATOR TWO-WAY COMMUNICATION. / EMERGENCY PHONE IN ELEVATOR DOESN'T HANG UP THE PHONE PROPERLY PREVENTING PHONE CHECKS FOR TWO WAY COMMUNICATION IN OTHER CARS IN THIS BANK OF ELEVATORS -- 30 DAYS TO ADDRESS (Receipt #2040669) | BENH | BENH | | H02 | C | 8016347 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2023 | ANNUAL 10/22 -- TKE & LOCKBOX -- EMERGENCY LIGHT & ALARM BELL ARE NONFUNCTIONAL WHEN CAB 110V IS DISCONNECTED (Receipt #1989666) cat 1 11/23---PM, per report emergency light and bell still non-functional. | BENH | BENH | | H01 | C | 7861026 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2023 | HO2 -- ANNUAL 10/22 -- TKE & LOCKBOX -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7701022 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2022 | 5 YEAR 8/21 -- ANNUAL 8/21 -- TKE & LOCKBOX -- ANNUAL TRACTION SAFETY TEST PAST DUE -- OIL DRIPPING ON CAR TOP CROSSHEAD FROM ABOVE IN MACHINE ROOM -- ROPES ARE OVER LUBRICATED AND NEED TO BE CLEANED TO INSPECT PROPERLY FOR WEAR AND TEAR (2ND NOTICE) -- WILL HOLD PERMIT TO OPERATE UNTIL ITEMS HAVE BEEN ADDRESSED (Receipt #1897699) cat 1 10/22 | BENH | BENH | | H01 | C | 7509741 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2022 | HO2 -- ANNUAL 8/21 -- TKE & LOCKBOX -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7321141 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2021 | 5YR -- CAT1 -- 8/21 -- TKE AND LOCKBOX. MONITOR WIRE ROPE BREAKS AND DIAMETERS (Receipt #1809937) | ROBERTV | ROBERTV | | H01 | C | 7120486 |
MEMORIAL HOSPITAL | H06 | C | 08/31/2021 | WITNESSED 5 YR SAFETY TEST-- TKE AND LOCKBOX-- ROPES ARE OVER LUBRICATED AND NEED TO BE CLEANED TO INSPECT PROPERLY FOR WEAR AND TEAR (Receipt #1803012) | BENH | BENH | | H06 | C | 7091266 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2021 | H02 -- 5YR -- 10/16 -- CAT1 -- 12/19 -- TKE AND SERVICE. 5 YEAR WITNESS TESTING SCHEDULED FOR 7/2021 (NEED TO MONITOR WIRE ROPE BREAKS AND DIAMETERS) | ROBERTV | ROBERTV | | H02 | C | 6902325 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2020 | 5YR -- 10/16 -- CAT1 -- 12/19 -- TKE AND LOCKBOX. NEED UP TO DATE FIRE SERVICE TESTING LOG. NEED QUARTERLY EMERGENCY PHONE TESTING LOG. NEED ELEVATOR EMERGENCY POWER TESTING LOG. NEED TAC32t INSPECTORS TESTING MANUAL ONSITE...... (NOTE: NEED TO MONITOR WIRE ROPE BREAKS AND DIAMETERS. (Receipt #1713644) | ROBERTV | ROBERTV | | H01 | C | 6708493 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | ANNUAL INSPECTION CONDUCTED ON 9/25/2019 FAILED TO GENERATE AN INVOICE, THIS ENTRY IS TO CORRECT THE ISSUE (Receipt #1663658) (Cat. 1 Performed 12/2019) | ERIC | ERIC | | H01 | C | 6488371 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | 5YR 10/16--ANNUAL 12/18--DOVER W/ TKE LOCKBOX--DOOR GIB'S LOOSE ON FLOOR 2 (Receipt #1566009 from 12/27/2018) | CALE | CALE | | H01 | C | 6346796 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2019 | 5 YEAR 10/16, ANNUAL 12/18 TKE AND LOCKBOX, HO2 | ERIC | ERIC | | H02 | C | 6142619 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2018 | 5YR -- 10/16 -- ANNUAL 11/17 -- DOVER W/ TKE LOCKBOX. MISSING MIDDLE SAFETY RETAINER AT BOTTOM OF FAST HOISTWAY DOOR ON LEVEL 4 (Receipt #1566009)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 5972601 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2018 | H02 | ROBERTV | ROBERTV | | H02 | C | 5783853 |
MEMORIAL HOSPITAL | H01 | C | 09/26/2017 | 5 YEAR 10/16, (Receipt #1455199) | ERIC | ERIC | | H01 | C | 5636690 |
MEMORIAL HOSPITAL | H02 | C | 03/24/2017 | H02 - MOD PERMIT STILL OPEN AND INSPECTIONS NEED TO BE PERFORMED | ROBERTV | ROBERTV | | H02 | C | 5455126 |
MEMORIAL HOSPITAL | H06 | C | 10/26/2016 | WITNESSED ACCEPTANCE TO MODERNIZATION -- SEE PERMIT #J95451 FOR ITEMS THAT NEED COMPLETED | ROBERTV | ROBERTV | | H06 | C | 5328524 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2016 | STILL UNDERGOING MOD (Receipt #1366588) | ROBERTV | ROBERTV | | H01 | C | 5306394 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2016 | UNDER GOING MOD | ERIC | ERIC | | H02 | C | 5151454 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2015 | DOVER AND LOCKBOX. 5 YEAR SAFETY TEST EXPIRED, LAST TEST 5/2010 (Receipt #1288937) | ERIC | ERIC | | H01 | C | 5042677 |
MEMORIAL HOSPITAL | H02 | C | 03/26/2015 | 5 YEAR 5/10 DOVER. STILL HAVE NOT INSTALLED LIGHT BULB GUARDS IN CARS. NOTE--5 YEAR SAFETY TEST DUE IN MAY 2015 | ERIC | ERIC | | H02 | C | 4924194 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2014 | 5 YEAR 5/10 DOVER. NEED LIGHT BULB GUARDS IN CAR AND NEED CAPACITY RATE POSTED IN CAR (Receipt #1222696) | ERIC | ERIC | | H01 | C | 4824362 |
MEMORIAL HOSPITAL | H02 | C | 03/13/2014 | H02 5 YR 5/10 DOVER | ERIC | ERIC | | H02 | C | 4701604 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2013 | 5YR 5-10-DOVER (Receipt #1156761) | TOM | TOM | | H01 | C | 4612763 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2013 | 5YR 5-10-DOVER--PHONE IN CAR NOT WORKING | TOM | TOM | | H02 | C | 4496967 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2012 | 5YR 5-10--DOVER (Receipt #1082954) | TOM | TOM | | H01 | C | 4392083 |
MEMORIAL HOSPITAL | H02 | C | 03/05/2012 | 5 YR 5-10--DOVER | TOM | TOM | | H02 | C | 4290635 |
MEMORIAL HOSPITAL | H01 | C | 09/15/2011 | 5 YR 5-10--DOVER (Receipt #1003065) | TOM | TOM | | H01 | C | 4215355 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2011 | 5 YR 5-10--DOVER--ADJUST BOTTOM HOISTWAY DOOR GUIDES (GIBBS) | TOM | TOM | | H02 | C | 4129169 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2010 | 5 YR 5-10--DOVER (Receipt #936166) | TOM | TOM | | H01 | C | 4049190 |
MEMORIAL HOSPITAL | H06 | C | 04/30/2010 | WITNESSED 5 YEAR SAFETY TEST (Receipt #907324) | ERIC | ERIC | | H06 | C | 3975057 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2010 | DOVER. OTIS SERVICE. 5 YEAR SAFETY TEST EXPIRED, LAST TEST 11/04, NEED CAPACITY RATING POSTED INSIDE CAR, NEED LIGHT BULB GUARDS IN CAR | ERIC | ERIC | | H02 | C | 3960662 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2009 | 5YR 11-04--OTIS (Receipt #878703) | TOM | TOM | | H01 | C | 3892339 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2009 | 5YR 11-04--OTIS | TOM | TOM | | H02 | C | 3818719 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2008 | 5yr--11-04--dover--otis lockbox (Receipt #828322) | TOM | TOM | | H01 | C | 3747517 |
MEMORIAL HOSPITAL | H02 | C | 03/14/2008 | 5 YR 11-04 --- OTIS LOCKBOX | LES | LES | | H02 | C | 438640 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2007 | 5 YR 11-04 --- OTIS LOCKBOX | LES | LES | | H01 | C | 438632 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2007 | 5 YR 11-04 --- OTIS LOCKBOX --- HALL LIGHT OUT ON BASEMENT AND UP ARROW | LES | LES | | H02 | C | 438624 |
MEMORIAL HOSPITAL | H01 | C | 09/11/2006 | 5 YR 11-04 --- OTIS LOCKBOX | LES | LES | | H01 | C | 438616 |
MEMORIAL HOSPITAL | H02 | C | 03/16/2006 | 5 YR 11-04 --- OTIS LOCKBOX --- NEED LIGHT BULB GUARDS IN CAR | LES | LES | | H02 | C | 438609 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2005 | 5 YR 11-04 --- DOVER - OTIS LOCKBOX | LES | LES | | H01 | C | 438601 |
MEMORIAL HOSPITAL | H02 | C | 03/28/2005 | 5 YR 11-04 --- DOVER --- OTIS LOCKBOX | LES | LES | | H02 | C | 438594 |
MEMORIAL HOSPITAL | H01 | C | 09/28/2004 | 5 YR TEST DUE --- DOVER -- OTIS LOCKBOX | LES | LES | | H01 | C | 438586 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2004 | 5 YR 6-99 --- DOVER --- NEED LIGHT BULB GUARDS | LES | LES | | H02 | C | 438578 |
MEMORIAL HOSPITAL | H01 | C | 09/26/2003 | 5 YR 6-99 | LES | LES | | H01 | C | 438570 |
MEMORIAL HOSPITAL | H02 | C | 03/20/2003 | 5 YR 6-99 | LES | LES | | H02 | C | 438561 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2002 | 5 YR 6-99 | LES | LES | | H01 | C | 438554 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2002 | 5 YR 6-99 -- BULB GUARDS -- CHECK LEVELING | LES | LES | | H02 | C | 438547 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2001 | 5 YR 6-99 | LES | LES | | H01 | C | 438539 |
MEMORIAL HOSPITAL | H02 | C | 03/30/2001 | 5 YR 6-99 | LES | LES | | H02 | C | 438530 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2000 | 5 YR 6-99--DOVER | TOM | TOM | | H01 | C | 438522 |
MEMORIAL HOSPITAL | H02 | P | 03/30/2000 | 5 YR 6-99--DOVER--PHONE INOP | TOM | TOM | | H02 | P | 438514 |
MEMORIAL HOSPITAL | H01 | C | 09/22/1999 | | RUSS | RUSS | | H01 | C | 438507 |
MEMORIAL HOSPITAL | H02 | C | 03/23/1999 | | RUSS | RUSS | | H02 | C | 438354 |
MEMORIAL HOSPITAL | H01 | C | 09/25/1998 | | RUSS | RUSS | | H01 | C | 438347 |
MEMORIAL HOSPITAL | H02 | C | 03/12/1998 | | RUSS | RUSS | | H02 | C | 438339 |
MEMORIAL HOSPITAL | H01 | C | 09/18/1997 | | RUSS | RUSS | | H01 | C | 438499 |
MEMORIAL HOSPITAL | H02 | C | 03/24/1997 | | RUSS | RUSS | | H02 | C | 438491 |
MEMORIAL HOSPITAL | H01 | C | 09/06/1996 | 5yr5-94 | RUSS | RUSS | | H01 | C | 438482 |
MEMORIAL HOSPITAL | H02 | C | 03/14/1996 | 5yr5-94 | RUSS | RUSS | | H02 | C | 438474 |
MEMORIAL HOSPITAL | H01 | C | 09/12/1995 | 5yr 5-94 | RUSS | RUSS | | H01 | C | 438467 |
MEMORIAL HOSPITAL | H02 | C | 03/09/1995 | | RUSS | RUSS | | H02 | C | 438459 |
MEMORIAL HOSPITAL | H01 | C | 09/08/1994 | 5YR-5-94 | RUSS | RUSS | | H01 | C | 438451 |
MEMORIAL HOSPITAL | H01 | C | 09/06/1993 | | RUSS | RUSS | | H01 | C | 438445 |
MEMORIAL HOSPITAL | H02 | C | 03/09/1993 | | RUSS | RUSS | | H02 | C | 438437 |
MEMORIAL HOSPITAL | H01 | C | 09/01/1992 | 5YR 4-89 | RUSS | RUSS | | H01 | C | 438428 |
MEMORIAL HOSPITAL | H02 | C | 03/19/1992 | | RUSS | RUSS | | H02 | C | 438420 |
MEMORIAL HOSPITAL | H01 | C | 09/06/1991 | | RUSS | RUSS | | H01 | C | 438412 |
MEMORIAL HOSPITAL | H02 | C | 03/19/1991 | | RUSS | RUSS | | H02 | C | 438404 |
MEMORIAL HOSPITAL | H01 | P | 09/17/1990 | SMK DET | RUSS | RUSS | | H01 | P | 438396 |
MEMORIAL HOSPITAL | H02 | R | 03/22/1990 | SMK DET | RUSS | RUSS | | H02 | R | 438388 |
MEMORIAL HOSPITAL | H01 | P | 09/19/1989 | ORDER: FIRE SVC | RUSS | RUSS | | H01 | P | 438380 |
MEMORIAL HOSPITAL | H02 | P | 03/24/1989 | ORDER: INCOMPLETE FIRE SERVICE | RUSS | RUSS | | H02 | P | 438372 |
MEMORIAL HOSPITAL | H16 | C | 09/15/1988 | INIT INSP, PERM ISS'D | RUSS | RUSS | | H16 | C | 438362 |