MEMORIAL HOSPITAL | H02 | C | 03/06/2024 | HO2 -- ANNUAL 2/24 -- TKE & LOCKBOX -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040676) | BENH | BENH | | H02 | C | 8016367 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2023 | ANNUAL 10/22 -- TKE & LOCKBOX -- EMERGENCY LIGHT & ALARM BELL ARE NONFUNCTIONAL -- NEED TO CLEAN CARTOP -- NEED TO CLEAN PIT (Receipt #1989675) | BENH | BENH | | H01 | C | 7861048 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2023 | ANNUAL 10/22 -- TKE & LOCKBOX -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7701043 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2022 | 5 YEAR 8/21 -- ANNUAL 8/21 -- TKE & LOCKBOX -- ANNUAL TRACTION SAFETY TEST PAST DUE -- OIL LEAKING FROM DRIVE MACHINE AND ON TO MACHINE ROOM FLOOR -- EMERGENCY LIGHT & ALARM BELL NONFUNCTIONAL WHEN CAB 110V IS DISCONNECTED -- WILL HOLD PERMIT TO OPERATE UNTIL ITEMS HAVE BEEN ADDRESSED (Receipt #1897716) cat 1 10/22 | BENH | BENH | | H01 | C | 7509806 |
MEMORIAL HOSPITAL | H02 | C | 03/23/2022 | HO2 -- ANNUAL 8/21 -- TKE & LOCKBOX -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7312300 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2021 | 5YR -- CAT1 -- 8/21 -- TKE AND LOCKBOX. FOLLOW-UP SCHEDULED FOR SAFETY RETAINER INSTALLATION ON 1ST AND 2ND FLOOR HOISTWAY DOORS AND OIL LEAKAGE FROM DRIVE MACHINE. MONITOR WIRE ROPE BREAKS AND DIAMETERS (Receipt #1809941) | ROBERTV | ROBERTV | | H01 | C | 7120499 |
MEMORIAL HOSPITAL | H06 | C | 08/31/2021 | WITNESSED 5 YR SAFETY TEST-- TKE AND LOCKBOX-- MISSING SAFETY RETAINERS ON 1ST AND 2ND FLOOR, OIL IN MACHINE ROOM FLOOR (Receipt #1803021) | BENH | BENH | | H06 | C | 7091290 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2021 | H02 -- 5YR -- 8/16 -- CAT1 -- 4/20 -- TKE AND SERVICE. 5 YEAR WITNESS TESTING SCHEDULED FOR 7/2021 (NEED TO MONITOR WIRE ROPE BREAKS AND DIAMETERS) | ROBERTV | ROBERTV | | H02 | C | 6902326 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2020 | 5YR -- 8/16 -- CAT1 -- 4/20 -- TKE AND LOCKBOX. DIRECTIONAL INDICATOR NOT SOUNDING WHEN CAR ARRIVES AT FLOOR. NEED FIRE SERVICE TESTING LOG. NEED QUARTERLY EMERGENCY PHONE TESTING LOG........... (NOTE: NEED TO MONITOR WIRE ROPE BREAKS AND DIAMETERS) (Receipt #1713652) | ROBERTV | ROBERTV | | H01 | C | 6708506 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2019 | ANNUAL INSPECTION CONDUCTED ON 9/27/2019 FAILED TO GENERATE AN INVOICE, THIS ENTRY IS TO CORRECT THE ISSUE (Receipt #1663659) cat 1 4/20 | ERIC | ERIC | | H01 | C | 6488372 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2019 | 5YR 8/16--ANNUAL 11/17--DOVER W/ TKE SERVICE--ANNUAL TRACTION SAFETY TEST PAST DUE--FLUID ON PIT FLOOR--CHECK LOWER DOOR GIBS--DRIVE SHEAVE IS WEARING RAPIDLY, SUSPENSION ROPE DIAMETERS ARE GETTING SMALLER AND WILL BE MONITORED UNTIL REPLACEMENT IS NEEDED PER ASME A17.6 (Receipt #1566011 from 12/27/2018) | CALE | CALE | | H01 | C | 6349975 |
MEMORIAL HOSPITAL | H02 | C | 03/27/2019 | 5 YEAR 8/16, TKE, HO2 | ERIC | ERIC | | H02 | C | 6146473 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2018 | 5YR -- 8/16 -- ANNUAL 11/17 -- DOVER W/ TKE SERVICE. DRIVE SHEAVE IS WEARING RAPIDLY, SUSPENSION ROPE DIAMETERS ARE GETTING SMALLER AND WILL BE MONITORED UNTIL REPLACEMENT IS NEEDED PER ASME A17.6 (Receipt #1566011) | ROBERTV | ROBERTV | | H01 | C | 5972605 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2018 | H02 | ROBERTV | ROBERTV | | H02 | C | 5783854 |
MEMORIAL HOSPITAL | H01 | C | 09/26/2017 | 5 YEAR 8/16 TKE. SUSPENSION ROPE DIAMETERS ARE THIN, NEED ANNUAL CAT 1 TESTING (Receipt #1455402) | ERIC | ERIC | | H01 | C | 5637480 |
MEMORIAL HOSPITAL | H02 | C | 03/27/2017 | 5YR -- 8/16 -- DOVER W/ TKE SERVICE. SUSPENSION ROPES THIN AND WILL BE MONITORED UNTIL DEEMED REPLACEMENT REQUIRED PER ASME 17.6 | ROBERTV | ROBERTV | | H02 | C | 5456414 |
MEMORIAL HOSPITAL | H01 | C | 09/13/2016 | THIS VISIT SKIPPED IN LIEU OF WITNESS TEST PERFORMED 8/2016 (Receipt #1360018) | ROBERTV | ROBERTV | | H01 | C | 5291565 |
MEMORIAL HOSPITAL | HE16 | C | 08/31/2016 | EMERGENCY LIGHT DOES NOT EXIST ON THIS ELEVATOR | ROBERTV | ROBERTV | | HE16 | C | 5282614 |
MEMORIAL HOSPITAL | H06 | C | 08/23/2016 | WITNESSED TRACTION SAFETY TEST W/ TKE -- SECURE TOP OF CAR ESCAPE HATCH, EMERGENCY LIGHT NOT WORKING, SUSPENSION ROPES NOT EQUALLY TENSIONED AND SHOWING PREMATURE DIAMETER WEAR - (WILL MONITOR ROPES UNTIL DEEMED REPLACEMENT NEEDED PER ASME A17.6) | ROBERTV | ROBERTV | | H06 | C | 5276234 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2016 | DOVER W/ TKE SERVICE -- 5 YEAR WITNESS TEST WAY PAST DUE. | ROBERTV | ROBERTV | | H02 | C | 5164375 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2015 | DOVER AND LOCKBOX. 5 YEAR SAFETY TEST EXPIRED, LAST TEST 6/2010 (Receipt #1288941) | ERIC | ERIC | | H01 | C | 5042687 |
MEMORIAL HOSPITAL | H02 | C | 03/26/2015 | 5 YEAR 6/10 DOVER. ROPES HAVE BEEN REPLACED | ERIC | ERIC | | H02 | C | 4924200 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2014 | 5 YEAR 6/10 DOVER. SUSPENSION ROPES STRETCHED PAST ALLOWABLE TOLERANCES AND MUST BE REPLACED (Receipt #1222703) | ERIC | ERIC | | H01 | C | 4824377 |
MEMORIAL HOSPITAL | H02 | C | 03/13/2014 | H02 5 YR 6/10 DOVER | ERIC | ERIC | | H02 | C | 4701607 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2013 | 5YR 6-10-CLOSELY MONITOR ROUGE ON ROPES (Receipt #1156762) | TOM | TOM | | H01 | C | 4612764 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2013 | 5YR 6-10-DOVER--ROUGE ON ROPES-MONITOR CLOSELY | TOM | TOM | | H02 | C | 4496971 |
MEMORIAL HOSPITAL | H01 | C | 09/24/2012 | 5YR 6-10--DOVER (Receipt #1082946) | TOM | TOM | | H01 | C | 4392074 |
MEMORIAL HOSPITAL | H02 | C | 03/05/2012 | 5 YR 6-10--DOVER | TOM | TOM | | H02 | C | 4290636 |
MEMORIAL HOSPITAL | H01 | C | 09/15/2011 | 5 YR 6-10--DOVER (Receipt #1003067) | TOM | TOM | | H01 | C | 4215356 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2011 | 5 YR 6-10--DOVER--MACHINE ROOM LIGHT BULBS BURNED OUT | TOM | TOM | | H02 | C | 4129176 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2010 | 5 YR 6-10--DOVER--REMOVE NON-ELEVATOR STORAGE FROM MACHINE ROOM (Receipt #936169) | TOM | TOM | | H01 | C | 4049198 |
MEMORIAL HOSPITAL | H06 | C | 06/23/2010 | WITNESSED 5 YEAR SAFETY TEST (Receipt #916348) | ERIC | ERIC | | H06 | C | 3999615 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2010 | DOVER. OTIS SERVICE. 5 YEAR SAFETY TEST EXPIRED, LAST TEST 12/04, TRIM OFF BOLTS USED TO SUSPEND NEW CAR CEILING TO PREVENT TRIP HAZARD, CHECK ROUGING OF HOIST ROPES | ERIC | ERIC | | H02 | C | 3960671 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2009 | 5YR 12-04 OTIS (Receipt #878704) | TOM | TOM | | H01 | C | 3892340 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2009 | 5YR 12-04--OTIS | TOM | TOM | | H02 | C | 3818720 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2008 | 5yr--12--04--otis and lockbox (Receipt #828329) | TOM | TOM | | H01 | C | 3747538 |
MEMORIAL HOSPITAL | H02 | C | 03/13/2008 | 5 YR 12-04 --- OTIS LOCKBOX | LES | LES | | H02 | C | 438957 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2007 | 5 YR 12-04 --- OTIS LOCKBOX | LES | LES | | H01 | C | 438950 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2007 | 5 YR 12-04 --- OTIS LOCKBOX | LES | LES | | H02 | C | 438942 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2006 | 5 YR 12-04 --- OTIS LOCKBOX | LES | LES | | H01 | C | 438934 |
MEMORIAL HOSPITAL | H02 | C | 03/16/2006 | 5 YR 12-04 --- OTIS LOCKBOX | LES | LES | | H02 | C | 438927 |
MEMORIAL HOSPITAL | H01 | C | 09/28/2005 | 5 YR 12-04 --- OTIS LOCKBOX --- CHECK GOV. CABLE NEXT INSP. | LES | LES | | H01 | C | 438918 |
MEMORIAL HOSPITAL | H02 | C | 03/23/2005 | 5 YR 12-04 --- OTIS LOCKBOX --- CHECK GOV. CABLE FOR ROUGING NEXT INSP. | LES | LES | | H02 | C | 438910 |
MEMORIAL HOSPITAL | H01 | C | 09/24/2004 | 5 YR TEST DUE --- OTIS LOCKBOX | LES | LES | | H01 | C | 438902 |
MEMORIAL HOSPITAL | H02 | C | 03/20/2003 | 5 YR 7-99 | LES | LES | | H02 | C | 438893 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2002 | 5 YR 7-99 | LES | LES | | H01 | C | 438885 |
MEMORIAL HOSPITAL | H02 | C | 03/21/2002 | 5 YR 7-99 | LES | LES | | H02 | C | 438878 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2001 | 5 YR 7-99 --- SINAGE MISSING BASEMENT AND 2ND FLOOR | LES | LES | | H01 | C | 438870 |
MEMORIAL HOSPITAL | H02 | R | 03/30/2001 | 5 YR 6-99 --- ROPE FATIGUE ON COUNTERWEIGHT,ROPE NEEDS TO BE REPLACED | LES | LES | | H02 | R | 438842 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2000 | | LES | LES | | H01 | C | 438832 |
MEMORIAL HOSPITAL | H02 | P | 03/30/2000 | 5 YR 7-99--DOVER--ALARM INOP | TOM | TOM | | H02 | P | 438824 |
MEMORIAL HOSPITAL | H01 | C | 09/22/1999 | | RUSS | RUSS | | H01 | C | 438816 |
MEMORIAL HOSPITAL | H02 | C | 03/23/1999 | | RUSS | RUSS | | H02 | C | 438664 |
MEMORIAL HOSPITAL | H01 | C | 09/28/1998 | | RUSS | RUSS | | H01 | C | 438656 |
MEMORIAL HOSPITAL | H02 | C | 03/12/1998 | | RUSS | RUSS | | H02 | C | 438648 |
MEMORIAL HOSPITAL | H01 | C | 09/18/1997 | | RUSS | RUSS | | H01 | C | 438808 |
MEMORIAL HOSPITAL | H02 | C | 03/24/1997 | | RUSS | RUSS | | H02 | C | 438800 |
MEMORIAL HOSPITAL | H01 | C | 09/06/1996 | 5yr5-94 | RUSS | RUSS | | H01 | C | 438792 |
MEMORIAL HOSPITAL | H02 | C | 03/18/1996 | | RUSS | RUSS | | H02 | C | 438784 |
MEMORIAL HOSPITAL | H01 | C | 09/12/1995 | 5yr 4-94 | RUSS | RUSS | | H01 | C | 438776 |
MEMORIAL HOSPITAL | H02 | C | 03/09/1995 | | RUSS | RUSS | | H02 | C | 438768 |
MEMORIAL HOSPITAL | H01 | C | 09/08/1994 | 5YR-4-94 | RUSS | RUSS | | H01 | C | 438760 |
MEMORIAL HOSPITAL | H01 | C | 09/06/1993 | | RUSS | RUSS | | H01 | C | 438752 |
MEMORIAL HOSPITAL | H02 | C | 03/09/1993 | | RUSS | RUSS | | H02 | C | 438744 |
MEMORIAL HOSPITAL | H01 | C | 09/01/1992 | 5YR 4-89 | RUSS | RUSS | | H01 | C | 438736 |
MEMORIAL HOSPITAL | H02 | C | 03/19/1992 | | RUSS | RUSS | | H02 | C | 438728 |
MEMORIAL HOSPITAL | H01 | C | 09/06/1991 | | RUSS | RUSS | | H01 | C | 438720 |
MEMORIAL HOSPITAL | H02 | C | 03/15/1991 | | RUSS | RUSS | | H02 | C | 438712 |
MEMORIAL HOSPITAL | H01 | C | 09/17/1990 | | RUSS | RUSS | | H01 | C | 438704 |
MEMORIAL HOSPITAL | H02 | C | 03/21/1990 | | RUSS | RUSS | | H02 | C | 438696 |
MEMORIAL HOSPITAL | H01 | C | 09/19/1989 | | RUSS | RUSS | | H01 | C | 438688 |
MEMORIAL HOSPITAL | H02 | P | 03/24/1989 | ALARM INOPERATIVE AND NOT WIRED TO STOP SWITCH | RUSS | RUSS | | H02 | P | 438680 |
MEMORIAL HOSPITAL | H16 | C | 09/15/1988 | INIT INSP, PERM ISS'D | RUSS | RUSS | | H16 | C | 438672 |