ALTA SPRINGS OFF I-25 OWNER, LLC | H05 | C | 01/16/2024 | RED TAG SHUTDOWN: MADE SITE VISIT TO VERIFY ELEVATOR HAS BEEN REMOVED FROM SERVICE PER REQUIREMENTS OF STATE OF COLORADO CONVEYANCE REGULATIONS (Receipt #2024875) | DUSTINS | DUSTINS | | H05 | C | 7968799 |
ALTA SPRINGS OFF I-25 OWNER, LLC | H03 | C | 10/19/2023 | ANNUAL 5/23 -- OTIS W/ PEAK SERVICE -- / SMALL OIL LEAKS AT VICTAULIC FITTINGS IN ROOM BEHIND MACHINE ROOM / FLOOR B HOISTWAY FAST DOOR MISSING GIB / BUILDING TO ADDRESS MACHINE ROOM CEILING FALLING APART AND BUSTED CONCRETE ON FLOOR IN MACHINE ROOM (Receipt #2000278) | DUSTINS | DUSTINS | | H03 | C | 7893826 |
ALTA SPRINGS OFF I-25 OWNER, LLC | H01 | C | 09/15/2023 | ANNUAL 5/23 -- OTIS & LOCK BOX AT MACHINE ROOM 5 W/ PEAK SERVICE -- / SMALL OIL LEAKS AT VICTAULIC FITTINGS IN ROOM BEHIND MACHINE ROOM / ELEVATOR DOWN FOR REPAIRS AT TIME OF INSPECTION / (Receipt #1988527) | DUSTINS | DUSTINS | | H01 | C | 7857547 |
ALTA SPRINGS OFF I-25 OWNER, LLC | HE16 | C | 06/05/2023 | ANNUAL 5/23 -- OTIS & LOCKBOX AT MACHINE ROOM 5 -- / PERFORMED FOLLOW UP INSPECTIONS -- / SMALL OIL LEAKS AT VICTAULIC FITTINGS IN ROOM BEHIND MACHINE ROOM / BUILDING TO KEEP MONTHLY FIREFIGHTERS’ EMERGENCY OPERATION AND QUARTERLY EMERGENCY PHONE TEST LOGS UP TO DATE / FLOOR B HOISTWAY FAST DOOR MISSING GIBB / STORAGE AT FLOORS 3 AND 4 BLOCKING ENTRANCES NEEDS TO BE REMOVED | DUSTINS | DUSTINS | | HE16 | C | 7762173 |
ALTA SPRINGS OFF I-25 OWNER, LLC | HE16 | C | 04/19/2023 | ISOLATED STATIC TEST ON JACK HAS BEEN VERIFIED BY PPRBD. CAR MOVED 2.5 INCHES OVER A 24 HOUR PERIOD. MOVEMENT DUE TO HYDRAULIC FLUID COOL DOWN, NO UNACCOUTABLE OIL LOSS.....(NOTE: JACK HAS BEEN REPLACED AT SOME POINT IN THE ELEVATORS LIFE AND IS NOT REQUIRED TO BE VERIFIED FOR SINGLE BOTTOM) (cat 1 -- 5/23, DS) | ROBERTV | ROBERTV | | HE16 | C | 7720930 |
ALTA SPRINGS OFF I-25 OWNER, LLC | HE16 | C | 04/13/2023 | ANNUAL 2/22 -- OTIS & LOCKBOX -- / PERFORMED FOLLOW UP INSPECTION ON ELEVATOR AFTER REPAIRS MADE / REQUIRED ANNUAL HYDRAULIC CATEGORY 1 TESTING IS PAST DUE / CLEAN OIL SOAKED PADS AND DEBRIS FROM PIT / OIL BEING STORED IN MACHINE ROOM NEEDS TO BE STORED IN NON FLAMMABLE CONTAINERS OR STORED ELSEWHERE / FLOOR "B" FAST DOOR MISSING GIBB / FLOOR "B" HOISTWAY DOOR SEPARATING FROM CAR DOOR WHEN CLOSING IN NORMAL OPERATION / CAR DOOR CLUTCH SCRAPING PICK UP ROLLERS ON FLOOR 1 / ALL ITEMS NEED TO BE ADDRESSED WITHIN 60 DAYS TO AVOID RED TAG AND POSSIBLE SERVICE INTERRUPTION / CONTINUE TO HOLD PERMIT TO OPERATE UNTIL ALL ITEMS ARE ADDRESSED | DUSTINS | DUSTINS | | HE16 | C | 7715288 |
ALTA SPRINGS OFF I-25 OWNER, LLC | H02 | C | 03/09/2023 | ANNUAL 2/22 -- OTIS & LOCKBOX -- / ELEVATOR WAS SHUT DOWN AT TIME OF INSPECTION DUE TO THE REPAIRS MADE WERE DONE BY AN UNLICENSED CONTRACTOR IN PPRBD JURISDICTION AND REPAIRS WERE NOT LOGGED IN THE MCP / MCP DOCUMENTS NEED TO BE SEPARATED FOR EACH ELEVATOR | DUSTINS | DUSTINS | | H02 | C | 7682292 |
ALTA SPRINGS OFF I-25 OWNER, LLC | H01 | C | 09/09/2022 | ANNUAL 2/22 -- OTIS & LOCKBOX -- / ELEVATOR DOWN FOR REPAIRS AT TIME OF INSPECTION / (Receipt #1898198) | DUSTINS | DUSTINS | | H01 | C | 7512404 |
ALTA SPRINGS OFF I-25 OWNER, LLC | H02 | C | 03/03/2022 | H02 -- CAT 1 -- 2/2022 -- OTIS & LOCKBOX | DUSTINS | DUSTINS | | H02 | C | 7289774 |
513 HOTEL OPERATING. LLC | H01 | C | 09/14/2021 | ANNUAL 2/2021 -- OTIS & LOCKBOX -- / MISSING DOOR GIBS AT 4TH FLOOR / MISSING FIRE TABS AT 1ST FLOOR (Receipt #1806521) | RANDYB | RANDYB | | H01 | C | 7105650 |
513 HOTEL OPERATING. LLC | H02 | C | 03/11/2021 | HO2--ANNUAL 02/2021--OTIS & LOCKBOX | MIKEM | MIKEM | | H02 | C | 6896781 |
513 HOTEL OPERATING. LLC | H01 | C | 09/09/2020 | ANNUAL 2/2020 -- OTIS & LOCKBOX -- / ELEVATOR OUT OF SERVICE AT TIME OF INSPECTION (Receipt #1711225) | RANDYB | RANDYB | | H01 | C | 6699809 |
513 HOTEL OPERATING. LLC | H02 | C | 03/10/2020 | 5YR 02/2020--OTIS & LOCKBOX--HO2 | CALE | CALE | | H02 | C | 6505338 |
513 HOTEL OPERATING. LLC | H06 | C | 02/10/2020 | WITNESSED 5YR HYDRO CATEGORY 1 TEST W/ OTIS--OTIS & LOCKBOX--MISSING DOOR RETAINERS TOP & BOTTOM FLOORS (REPAIRS MADE PER OTIS MECHANIC) | CALE | CALE | | H06 | C | 6478037 |
513 HOTEL OPERATING. LLC | H01 | C | 09/30/2019 | RP--5--19--OTIS--AND LOCKBOX--TOP FLOOR RETAINERS MISSING BOTTOM OF THE DOOR --PHONE DIALS NO ANSWER (Receipt #1633636) | JOHNW | JOHNW | | H01 | C | 6351893 |
513 HOTEL OPERATING. LLC | H02 | C | 03/19/2019 | H02 -- RP 5/18--(annual 5/19) | ROBERTV | ROBERTV | | H02 | C | 6137360 |
513 HOTEL OPERATING. LLC | H01 | C | 09/19/2018 | RP -- 5/18 -- OTIS AND LOCKBOX. (NO CODE ISSUES) | ROBERTV | ROBERTV | | H01 | C | 5969389 |
513 HOTEL OPERATING. LLC | H02 | C | 03/07/2018 | H02 | ROBERTV | ROBERTV | | H02 | C | 5781993 |
513 HOTEL OPERATING. LLC | H01 | C | 09/20/2017 | RP -- 4/17 -- OTIS AND LOCKBOX. CLEAN ELEVATOR PIT | ROBERTV | ROBERTV | | H01 | C | 5631024 |
513 HOTEL OPERATING. LLC | H02 | C | 03/21/2017 | RP--3--16--OTIS AND LOCKBOX--WATER LEAKING FROM PLUMBING PIPES ONTO MACHINE ROOM FLOOR --MISSING DOOR RESTRICTOR ALL FLOORS | JOHNW | JOHNW | | H02 | C | 5446421 |
513 HOTEL OPERATING. LLC | H01 | C | 09/14/2016 | RP--3--16--OTIS AND LOCKBOX. MISSING DOOR RESTRICTORS (FINAL NOTICE -- REPAIRS NEED BE COMPLETED BY COMPLIANCE DATE TO AVOID SERVICE INTERRUPTION -- PERMIT TO OPERATE HELD RV) (Receipt #1360810) | ROBERTV | ROBERTV | | H01 | C | 5293496 |
513 HOTEL OPERATING. LLC | H02 | C | 03/17/2016 | OTIS AND LOCKBOX -- REQUIRED ANNUAL PRESSURE RELIEF TEST EXPIRED, LAST PERFORMED 2/2015. DOOR RESTRICTORS NEED TO BE INSTALLED (3RD NOTICE). NEED VERIFICATION OF REPAIR REGARDING OIL LEAK - (REPAIR LOG DOES NOT INDICATE ANY REPAIRS HAVE BEEN MADE). NEED CATEGORY 1 TEST FORMS ALONG WITH COMPLETE MAINTENANCE CONTROL PROGRAM ONSITE. THESE ITEMS MUST BE ADDRESSED BY NEXT INSPECTION TO AVOID INTERRUPTION IN SERVICE. | ROBERTV | ROBERTV | | H02 | C | 5157189 |
513 HOTEL OPERATING. LLC | H01 | C | 09/30/2015 | RP 2-15 OTIS--ALL ITEMS FROM LAST INSPECTION HAVE NOT BEEN ADDRESSED / LETTERING IS WORN OFF OF SEVERAL KEY SWITCHES IN CAR / CALL STATION AT LANDING 4 IS UNSECURED FROM WALL BRACKET (Receipt #1290548) | TOM | TOM | | H01 | C | 5048138 |
513 HOTEL OPERATING. LLC | H02 | C | 03/02/2015 | H02 -- 5YR -- 2/15 | ROBERTV | ROBERTV | | H02 | C | 4910022 |
513 HOTEL OPERATING. LLC | H06 | C | 02/10/2015 | WITNESSED 5 YEAR HYDRO SAFETY TEST W/ OTIS AND LOCKBOX -- MACHINE ROOM FIRE EXTINGUISHER IS EXPIRED, BASEMENT HOISTWAY DOOR TOE GUARD NEEDS REINSTALLED. PIT IS FILTHY AND NEEDS CLEANED, REAR DOORS AND "HOLD" FUNCTION DO NOT WORK IN PHASE II, DOOR RESTRICTORS NEED INSTALLED, DOOR GUIDES NEED ATTENTION ON MULTIPLE LANDINGS, RUN /STOP SWITCH NEEDS TO OPERATE WITH KNOWN KEY. | ROBERTV | ROBERTV | | H06 | C | 4900661 |
513 HOTEL OPERATING. LLC | H01 | C | 09/16/2014 | RP 11-13 OTIS--POST FLOOR DESIGNATION NUMBERS AT ALL LANDINGS / ELECTRICAL CORDS LAYING ON PIT FLOOR / CLEAN TRASH, DEBRIS & OIL FROM PIT FLOOR (Receipt #1222954) | TOM | TOM | | H01 | C | 4825098 |
513 HOTEL OPERATING. LLC | H02 | C | 03/10/2014 | HO2 | JOHNW | JOHNW | | H02 | C | 4699278 |
HARRELL COLORADO OPERATING COM | H01 | C | 09/24/2013 | RP--5--12--OTIS AND LOCKBOX--PRESSURE RELIEF TEST EXPIRED (Receipt #1155638) | JOHNW | JOHNW | | H01 | C | 4609388 |
HARRELL COLORADO OPERATING COM | H02 | C | 03/18/2013 | RP--5--12--OTIS --KONE LOCKBOX--MISSING BUTTON FOR PHONE IN CAB | JOHNW | JOHNW | | H02 | C | 4488654 |
HARRELL COLORADO OPERATING COM | H01 | C | 09/25/2012 | RP--5--12--OTIS AND LOCKBOX (Receipt #1081498) | JOHNW | JOHNW | | H01 | C | 4388243 |
HARRELL COLORADO OPERATING COM | H02 | C | 03/27/2012 | RP--5--11--OTIS --AND LOCKBOX | JOHNW | JOHNW | | H02 | C | 4288084 |
HARRELL COLORADO OPERATING COM | H01 | C | 09/16/2011 | RP--5--11--OTIS--FLUID ON PIT FLOOR (Receipt #1000069) | JOHNW | JOHNW | | H01 | C | 4208209 |
HARRELL COLORADO OPERATING COM | H02 | C | 03/10/2011 | RP--6--10--OTIS --FLUID ON PIT FLOOR | JOHNW | JOHNW | | H02 | C | 4120482 |
HARRELL COLORADO OPERATING COM | H01 | C | 09/16/2010 | RP 6/10 OTIS. EMERGENCY PHONE NOT WORKING (Receipt #932900) | ERIC | ERIC | | H01 | C | 4040782 |
HARRELL COLORADO OPERATING COM | H02 | C | 03/11/2010 | rp 6-09--otis | TOM | TOM | | H02 | C | 3958191 |
HARRELL COLORADO OPERATING COM | H01 | C | 09/15/2009 | RP--6--09--OTIS--CLEAN PIT (Receipt #876024) | JOHNW | JOHNW | | H01 | C | 3884614 |
HARRELL COLORADO OPERATING COM | H02 | C | 03/26/2009 | OTIS AND LOCKBOX, RP 6/08. CLEAN PIT | ERIC | ERIC | | H02 | C | 3817399 |
HARRELL COLORADO OPERATING COM | H01 | C | 09/10/2008 | RP 6-08 [ 301-360 ] --- OTIS ELEVATOR (Receipt #825540) | LES | LES | | H01 | C | 3738717 |
HARRELL COLORADO OPERATING COM | H02 | C | 03/03/2008 | RP 3-07 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 430794 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/04/2007 | RP 3-07 --- OTIS --- LIGHT OUT IN PIT --- CLEAN PIT [ OIL ON PIT FLOOR ] | LES | LES | | H01 | C | 430785 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/02/2007 | RP 4-06 --- OTIS | LES | LES | | H02 | C | 430778 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/15/2006 | RP 4-06 --- OTIS | LES | LES | | H01 | C | 430768 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/01/2006 | RP 5-05 --- OTIS | LES | LES | | H02 | C | 430761 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/07/2005 | RP 5-05 --- OTIS --- NO CHANGE --- 3RD AND FINAL NOTICE - ELEVATOR WILL BE SHUT DOWN IF NOT CORRECTED BY 10-7-05 | LES | LES | | H01 | C | 430752 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/14/2005 | RP 4-04 --- OTIS --- [ SEE NOTES FOR ELEVATOR #3 ] | LES | LES | | H02 | C | 430745 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/13/2004 | RP 4-04 --- OTIS REMODEL --- NEED CAR TOP EMERGENCY EXIT AND CAR VENTELATION FOR ELEVATORS 1,2,3,4 --- PAN PLUMBING IN MACHINE ROOM | LES | LES | | H01 | C | 430736 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/03/2004 | RP 4-03 --- U.S. ELEVATOR --- OTIS REMODEL | LES | LES | | H02 | C | 430729 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/08/2003 | RP 4-03 --- NEED EMERGENCY EXIT IN TOP OF CAR | LES | LES | | H01 | C | 430720 |
SHERATON HOTEL - ACCTS PAYABLE | H03 | C | 04/16/2003 | RP 4-03 | LES | LES | | H03 | C | 430712 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/07/2003 | RP TEST OVERDUE [ LAST TEST 9-01 ] --- EXCESSIVE OIL ON PIT FLOOR | LES | LES | | H02 | C | 430703 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | R | 09/23/2002 | RP 9-01 --- REQUESTED SCH. FOR REPAIRS OR ELEVATOR WILL BE SHUT DOWN | LES | LES | | H01 | R | 430696 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/27/2002 | RP 9-01 --- OIL LEAK IN PIT AND MACHINE ROOM [2ND NOTICE] --- NEED 2 WAY COMMUNICATION IN CAR | LES | LES | | H02 | C | 430690 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | R | 09/06/2001 | RP TEST OVER DUE --- OIL LEAK IN PIT [FIRE HAZARD] --- OIL ON FLOOR OF MACHINE ROOM [ SAFETY HAZARD] --- REPLACE ELECTRICAL COVERS ON TOP OF CAR | LES | LES | | H01 | R | 430682 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/06/2001 | RP 5-00 --- SAFETY EDGE NOT WORKING PROPERLY | LES | LES | | H02 | C | 430674 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/06/2000 | RP 5-00 CLEAN PIT | ELEVATORS | ELEVATORS | | H01 | C | 430666 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | R | 03/21/2000 | rp test expired | LES | LES | | H02 | R | 430501 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/07/1999 | RP 12-98--US ELEV--NO IN DATE | TOM | TOM | | H01 | C | 430659 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/10/1999 | | RUSS | RUSS | | H02 | C | 430493 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | R | 09/14/1998 | light bulb guarding all elevators,rp 1-97 | DAVEL | DAVEL | | H01 | R | 430485 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/11/1998 | | RUSS | RUSS | | H02 | C | 430477 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/16/1997 | d.l. | RUSS | RUSS | | H01 | C | 430651 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/13/1997 | | RUSS | RUSS | | H02 | C | 430643 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/04/1996 | | RUSS | RUSS | | H01 | C | 430634 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/11/1996 | | RUSS | RUSS | | H02 | C | 430626 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 08/31/1995 | | RUSS | RUSS | | H01 | C | 430618 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/08/1995 | | RUSS | RUSS | | H02 | C | 430610 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/09/1994 | RP2-94 | RUSS | RUSS | | H01 | C | 430602 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/08/1993 | | RUSS | RUSS | | H01 | C | 430595 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/08/1993 | | RUSS | RUSS | | H02 | C | 430585 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/02/1992 | | RUSS | RUSS | | H01 | C | 430578 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/19/1992 | | RUSS | RUSS | | H02 | C | 430571 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/05/1991 | | RUSS | RUSS | | H01 | C | 430563 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/12/1991 | | RUSS | RUSS | | H02 | C | 430555 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | C | 09/06/1990 | | RUSS | RUSS | | H01 | C | 430547 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | P | 03/05/1990 | RP TST | RUSS | RUSS | | H02 | P | 430542 |
SHERATON HOTEL - ACCTS PAYABLE | H01 | P | 09/11/1989 | ORDER: STILL LEAKING OIL | RUSS | RUSS | | H01 | P | 430536 |
SHERATON HOTEL - ACCTS PAYABLE | H02 | C | 03/10/1989 | | RUSS | RUSS | | H02 | C | 430523 |
SHERATON HOTEL - ACCTS PAYABLE | H16 | P | 11/15/1988 | PARTIALLY COMPLETED | RUSS | RUSS | | H16 | P | 430517 |
SHERATON HOTEL - ACCTS PAYABLE | H16 | C | 09/26/1988 | INIT INSP,PERM ISSD,ORDER:OIL LK,PIT LDR,LIGHT | RUSS | RUSS | | H16 | C | 430509 |