CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/06/2024 | 5 YEAR 8/21 -- ANNUAL 2/24 -- TKE & LOCKBOX AT P1 -- / PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040305) | DUSTINS | DUSTINS | | H02 | C | 8015312 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/19/2023 | 5 YEAR 8/21 -- ANNUAL 11/22 -- TKE & LOCKBOX AT P1 -- / BUILDING TO KEEP MONTHLY FIREFIGHTERS’ EMERGENCY OPERATION TEST LOGS UP TO DATE / COUNTERWEIGHT RUNBY IS LESS THAN 6" / 60 DAYS TO ADDRESS (Receipt #1989664) cat 1 2/24--PM, check logs at H02 | DUSTINS | DUSTINS | | H01 | C | 7861014 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/23/2023 | 5 YEAR 8/21 -- ANNUAL 11/22 -- TKE & LOCKBOX AT P2 -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7695762 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/19/2022 | 5 YEAR 8/21 -- TKE & LOCKBOX AT P2 -- / REQUIRED ANNUAL TRACTION SAFETY TESTING IS PAST DUE / BUILDING TO PROVIDE UP TO DATE MONTHLY FIREFIGHTERS' EMERGENCY OPERATION AND QUARTERLY EMERGENCY PHONE TEST LOGS / COUNTERWEIGHT RUNBY IS LESS THAN 6" / STILL NEED ALL ITEMS FROM MODERNIZATION PERMIT ADDRESSED, SEE PERMIT #M73387 FOR INSPECTION ITEMS (Receipt #1900467) cat 1 -- 11/22 | DUSTINS | DUSTINS | | H01 | C | 7522158 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/25/2022 | 5YR -- 8/21 -- TKE AND LOCKBOX AT P2. BROKEN HOISTWAY DOOR SIGHT GUARDS ON FLOORS P3, P2, P1, 3RD, 5TH, 13TH AND 14TH NEED TO BE REPLACED. NEED TO FINISH TOP OF CAR RAILING ON WIRE DUCT SIDE - (MODERNIZATION ITEM). NEED TO REINSTALL ORIGINAL STYLE ROPE GUARD ON CAR TOP SHEAVE - (MODERNIZATION ITEM). CLEAN MODERNIZATION DEBRIS FROM CAR TOP AND MACHINE ROOM. NEED 4" TOE-BOARD INSTALLED ON CAR TOP WHERE CLEARANCE TO HOISTWAY EXCEEDS 12" - (MODERNIZATION ITEM). LOBBY PANEL SELECTOR SWITCH TO SOLELY ILLUMINATE JEWEL FOR CAR IN SERVICE - (MODERNIZATION ITEM). | ROBERTV | ROBERTV | | H02 | C | 7314985 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/23/2021 | 5YR -- 8/21 -- TKE AND LOCKBOX AT P2. SEE PERMIT #M73387 FOR INSPECTION ITEMS (Receipt #1809370) | ROBERTV | ROBERTV | | H01 | C | 7118319 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 05/20/2021 | WITNESSED ACCEPTANCE TO MODERNIZATION - SEE PERMIT #M73387 FOR ITEMS THAT NEED TO BE ADDRESSED. | ROBERTV | ROBERTV | | H06 | C | 6988457 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/17/2021 | MODERNIZATION IN PROGRESS | ROBERTV | ROBERTV | | H02 | C | 6902284 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/30/2020 | MODERNIZATION IN PROGRESS - CAR IS STILL AVAILABLE FOR PUBLIC USE, AND NO CODE ISSUES ARE PRESENT. (Receipt #1717634) | ROBERTV | ROBERTV | | H01 | C | 6725410 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/02/2020 | MODERNIZATION IN PROGRESS | ROBERTV | ROBERTV | | H02 | C | 6497560 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/27/2019 | 5YR -- 7/15 -- ANNUAL 10/18 -- OTIS AND LOCKBOX AT P2. ELEVATOR OUT OF SERVICE PENDING GENERATOR REPAIR. NEED TO LOG ENTRIES IN MAINTENANCE CONTROL PROGRAM FOR ROUTINE VISITS, REPAIRS, REPLACEMENTS AS REQUIRED. (Receipt #1633353) | ROBERTV | ROBERTV | | H01 | C | 6350363 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/07/2019 | 5YR -- 7/15 -- ANNUAL 10/18 -- OTIS AND LOCKBOX. H02 | ROBERTV | ROBERTV | | H02 | C | 6126383 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2018 | 5 YEAR 7/15, ANNUAL 9/17 OTIS (Receipt #1542245) / (annual safety test performed 10-18, see images) | ERIC | ERIC | | H01 | C | 5979577 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/29/2018 | 5 YEAR 7/15, ANNUAL 9/17 OTIS, PEAK SERVICE. NEED TO REPLACE BROKEN HOISTWAY DOOR SIGHT GUARD AT LEVEL P-2 | ERIC | ERIC | | H02 | C | 5803011 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/26/2017 | 5 YEAR 7/15, ANNUAL 8/16, OTIS, PEAK SERVICE. NEED ANNUAL CAT 1 TESTING, NEED MCP ON SITE, CLEAN PIT, REPLACE BROKEN SITE GUARD AT P-2 (Receipt #1455391) | ERIC | ERIC | | H01 | C | 5637436 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/16/2017 | 5YR--6--15--ANNUAL 8--16--OTIS | JOHNW | JOHNW | | H02 | C | 5442505 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/29/2016 | 5YR -- 6/15 -- 1YR -- 8/16 -- OTIS. MISSING CATEGORY 1 TEST FORMS IN MAINTENANCE CONTROL PROGRAM, FLOOR P2 SIGHT GUARD IS BROKEN, ELEVATOR PIT NEEDS CLEANED | ROBERTV | ROBERTV | | H01 | C | 5305635 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/31/2016 | 5YR -- 6/15 -- OTIS. CLEAN DIRT AND DEBRIS FROM ELEVATOR PIT, NEED MAINTENANCE CONTROL PROGRAM ONSITE. | ROBERTV | ROBERTV | | H02 | C | 5166432 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/01/2015 | THIS INSPECTION SKIPPED IN LIEU OF WITNESS TEST PERFORMED 7/2015 (Receipt #1284453) | ROBERTV | ROBERTV | | H01 | C | 5027403 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 07/30/2015 | WITNESSED 5 YEAR TRACTION SAFETY TEST W/ OTIS -- FIRE SERVICE PHASE I AND PHASE II KEY SWITCHES MUST BE KEYED ALIKE, HOISTWAY DOOR SIGHT GUARDS ARE BROKEN AT MULTIPLE LEVELS. -- OTIS LOCKBOX AT P2 | ROBERTV | ROBERTV | | H06 | C | 5004125 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/11/2015 | 5 YEAR 6/10 OTIS | ERIC | ERIC | | H02 | C | 4916540 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/18/2014 | 5 YEAR 6/10 OTIS (Receipt #1220756) | ERIC | ERIC | | H01 | C | 4818636 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/21/2014 | 5YR 6/10 OTIS. | ERIC | ERIC | | H02 | C | 4706750 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/10/2013 | 5YR 6-10-OTIS (Receipt #1156709) | TOM | TOM | | H01 | C | 4612690 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/26/2013 | 5 YEAR 6/10 OTIS | ERIC | ERIC | | H02 | C | 4494052 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/05/2012 | 5 YR 6-10--OTIS (Receipt #1082503) | TOM | TOM | | H01 | C | 4390956 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/29/2012 | 5 YR 6-10--OTIS | TOM | TOM | | H02 | C | 4289942 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2011 | 5 YR 6-10--OTIS DOOR GIBBS ADJUSTED (Receipt #1002964) | TOM | TOM | | H01 | C | 4215093 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/02/2011 | 5YR 6-10--OTIS CHECK DOOR GIBBS NEXT INSP | TOM | TOM | | H02 | C | 4128922 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/20/2010 | 5 YR 6-10--OTIS (Receipt #936093) | TOM | TOM | | H01 | C | 4049073 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 06/29/2010 | WITNESSED 5 YEAR SAFETY TESTS (Receipt #917480) | ERIC | ERIC | | H06 | C | 4002852 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/19/2010 | OTIS. 5 YEAR SAFETY TEST EXPIRED, LAST TEST 9/04, REPAIR HOISTWAY PENETRATION AT FLOOR 2. | ERIC | ERIC | | H02 | C | 3956148 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/30/2009 | 5 YR 9-04--OTIS TEST DUE (Receipt #878666) | TOM | TOM | | H01 | C | 3892294 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/31/2009 | 5yr 9-04 | TOM | TOM | | H02 | C | 3818126 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/29/2008 | 5yr--9--04--otis #3 (Receipt #828403) | TOM | TOM | | H01 | C | 3747815 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/25/2008 | 5 YR 9-04 --- OTIS --- FIRE SERVICE TESTED YEARLEY BY INDEPENDENT CO. PER PAUL | LES | LES | | H02 | C | 439133 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/18/2007 | 5 YR 9-04 --- OTIS | LES | LES | | H01 | C | 439126 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/21/2007 | 5 YR 9-04 --- OTIS --- FIRE SERVICE TESTED YEARLY BY INDEPENDENT CO. PER PAUL IN ENGINEERING | LES | LES | | H02 | C | 439117 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2006 | 5 YR 9-04 --- OTIS | LES | LES | | H01 | C | 439108 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/27/2006 | 5 YR 9-04 --- OTIS | LES | LES | | H02 | C | 439051 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/30/2005 | 5 YR 9-04 --- OTIS | TOM | TOM | | H01 | C | 439042 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/08/2005 | 5 YR 9-04 --- OTIS | LES | LES | | H02 | C | 439035 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/29/2004 | 5 YR 9-04 --- OTIS | LES | LES | | H01 | C | 439027 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/31/2004 | 5 YR 11-99 --- OTIS | LES | LES | | H02 | C | 439019 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/10/2003 | 5 YR 11-99--OTIS | TOM | TOM | | H01 | C | 439011 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/26/2003 | 5 YR 11-99-OTIS | TOM | TOM | | H02 | C | 439007 |
PREMISYS REAL ESTATE SVCS | H01 | C | 08/30/2002 | 5 YR 11-99--OTIS | TOM | TOM | | H01 | C | 438997 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/25/2002 | 5 YR 10-99--OTIS | TOM | TOM | | H02 | C | 438990 |
PREMISYS REAL ESTATE SVCS | H01 | C | 08/31/2001 | 5 YR 10-99--OTIS | TOM | TOM | | H01 | C | 438983 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/27/2001 | 5 YR 10-99--OTIS | TOM | TOM | | H02 | C | 438974 |
PREMISYS REAL ESTATE SVCS | H01 | C | 08/11/2000 | 5 YR 10-99--OTIS | TOM | TOM | | H01 | C | 438967 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/28/2000 | 5 YR 10-99--OTIS | TOM | TOM | | H02 | C | 438959 |
PREMISYS REAL ESTATE SVCS | H01 | C | 08/19/1999 | OTIS, installed 1964 --- 5 yr 10-94 | LES | LES | | H01 | C | 438862 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/04/1999 | | RUSS | RUSS | | H02 | C | 438855 |
PREMISYS REAL ESTATE SVCS | H01 | C | 08/04/1998 | | RUSS | RUSS | | H01 | C | 438850 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/06/1998 | | DAVEL | DAVEL | | H02 | C | 438843 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/16/1997 | d.l. | RUSS | RUSS | | H01 | C | 438951 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/25/1997 | | RUSS | RUSS | | H02 | C | 438943 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/09/1996 | 5yr10-94 | RUSS | RUSS | | H01 | C | 438935 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/19/1996 | | RUSS | RUSS | | H02 | C | 438926 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/12/1995 | 5yr10-94,29aug for sep | RUSS | RUSS | | H01 | C | 438919 |
PREMISYS REAL ESTATE SVCS | H02 | P | 03/03/1995 | | RUSS | RUSS | | H02 | P | 438911 |
PREMISYS REAL ESTATE SVCS | H01 | R | 09/01/1994 | 5YR EXP.GLASS BOTTLE ROLLING AROUND ON | RUSS | RUSS | | H01 | R | 438903 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/01/1993 | | RUSS | RUSS | | H01 | C | 438895 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/02/1993 | | RUSS | RUSS | | H02 | C | 438887 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/08/1992 | 5YR 5-89 | RUSS | RUSS | | H01 | C | 438879 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/23/1992 | | RUSS | RUSS | | H02 | C | 438871 |
PERA | H01 | C | 09/12/1991 | | RUSS | RUSS | | H01 | C | 438835 |
PERA | H02 | C | 03/29/1991 | | RUSS | RUSS | | H02 | C | 438827 |
PERA | H01 | P | 09/10/1990 | SMK DET | RUSS | RUSS | | H01 | P | 438819 |
PERA | H02 | P | 03/20/1990 | SMK DET | RUSS | RUSS | | H02 | P | 438811 |
PERA | H01 | P | 09/13/1989 | ORDER: UPDATE FIRE SERVICE | RUSS | RUSS | | H01 | P | 438803 |
PERA | H02 | R | 03/13/1989 | ORDER: PROVIDE FIRE SERVICE | RUSS | RUSS | | H02 | R | 438795 |
PERA | H16 | C | 09/21/1988 | INIT INSP, PERM ISSD | RUSS | RUSS | | H16 | C | 438787 |