CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/06/2024 | 5 YEAR 8/21 -- ANNUAL 2/24 -- TKE & LOCKBOX AT P1 -- / PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040308) | DUSTINS | DUSTINS | | H02 | C | 8015315 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/19/2023 | 5 YEAR 8/21 -- ANNUAL 11/22 -- TKE & LOCKBOX AT P1 -- / BUILDING TO KEEP MONTHLY FIREFIGHTERS’ EMERGENCY OPERATION TEST LOGS UP TO DATE / COUNTERWEIGHT RUNBY IS LESS THAN 6" / LEFT SIDE BOTTOM OF COUNTERWEIGHT WOOD GUIDE NEEDS ATTENTION DUE TO EXCESSIVE WEAR / 60 DAYS TO ADDRESS (Receipt #1989671) cat 1 2/24--PM, check logs at H02 | DUSTINS | DUSTINS | | H01 | C | 7861040 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/23/2023 | 5 YEAR 8/21-- ANNUAL 11/22 -- TKE & LOCKBOX AT P2 -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7695764 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/19/2022 | 5 YEAR 8/21 -- TKE & LOCKBOX AT P2 -- / REQUIRED ANNUAL TRACTION SAFETY TESTING IS PAST DUE / BUILDING TO PROVIDE UP TO DATE MONTHLY FIREFIGHTERS' EMERGENCY OPERATION AND QUARTERLY EMERGENCY PHONE TEST LOGS / COUNTERWEIGHT RUNBY IS LESS THAN 6" / STILL NEED ALL ITEMS FROM MODERNIZATION PERMIT ADDRESSED, SEE PERMIT #M73387 FOR INSPECTION ITEMS (Receipt #1900469) cat 1 -- 11/22 | DUSTINS | DUSTINS | | H01 | C | 7522160 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/25/2022 | 5YR -- 8/21 -- TKE AND LOCKBOX AT P2. BROKEN HOISTWAY DOOR SIGHT GUARDS ON FLOORS AT 1ST, 2ND AND14TH NEED TO BE REPLACED. NEED TO FINISH TOP OF CAR RAILING ON WIRE DUCT SIDE - (MODERNIZATION ITEM). CLEAN MODERNIZATION DEBRIS FROM CAR TOP AND MACHINE ROOM. NEED 4" TOE-BOARD INSTALLED ON CAR TOP WHERE CLEARANCE TO HOISTWAY EXCEEDS 12" - (MODERNIZATION ITEM). LOBBY PANEL SELECTOR SWITCH TO SOLELY ILLUMINATE JEWEL FOR CAR IN SERVICE - (MODERNIZATION ITEM). | ROBERTV | ROBERTV | | H02 | C | 7315009 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/23/2021 | 5YR -- 8/21 -- TKE AND LOCKBOX AT P2. SEE PERMIT #M73387 FOR INSPECTION ITEMS (Receipt #1809363) | ROBERTV | ROBERTV | | H01 | C | 7118302 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/17/2021 | H02 -- ACCEPTANCE TO MODERNIZATION PERFORMED 2/2021 - SEE #M73387 FOR INSPECTION ITEMS | ROBERTV | ROBERTV | | H02 | C | 6902300 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 02/12/2021 | ACCEPTANCE TO MODERNIZATION PERFORMED - SEE #M73387 FOR INSPECTION ITEMS | ROBERTV | ROBERTV | | H06 | C | 6902296 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/30/2020 | MODERNIZATION IN PROGRESS (Receipt #1717628) | ROBERTV | ROBERTV | | H01 | C | 6725393 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/02/2020 | MODERNIZATION IN PROGRESS | ROBERTV | ROBERTV | | H02 | C | 6497567 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/27/2019 | 5YR -- 7/15 -- ANNUAL 10/18 -- OTIS AND LOCKBOX AT P2. NEED OPERABLE CAR TOP LIGHT. NEED TO LOG ENTRIES IN MAINTENANCE CONTROL PROGRAM FOR ROUTINE VISITS, REPAIRS, REPLACEMENTS AS REQUIRED. (Receipt #1633355 from 09/27/2019) | ROBERTV | ROBERTV | | H01 | C | 6350381 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/07/2019 | 5YR -- 7/15 -- ANNUAL 10/18 -- OTIS AND LOCKBOX. ELEVATOR OUT OF SERVICE PENDING SHEAVE REPLACEMENT AND SUSPENSION ROPE SHORTENING. | ROBERTV | ROBERTV | | H02 | C | 6126404 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2018 | 5 YEAR 7/15, ANNUAL 9/17 OTIS. COUNTERWEIGHT BUFFER COMPRESSED WITH CAR AT TOP LANDING, ROPES NEED TO BE SHORTENED (Receipt #1542248) / (annual safety test performed 10-18, see images) | ERIC | ERIC | | H01 | C | 5979591 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/29/2018 | 5 YEAR 7/15, ANNUAL 9/17 OTIS, PEAK SERVICE.***** ELEVATOR MACHINE ROOM LIGHTS MUST BE REPAIRED WITHIN 30 DAYS | ERIC | ERIC | | H02 | C | 5803017 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/26/2017 | 5 YEAR 7/15, ANNUAL 8/16, OTIS, PEAK SERVICE. NEED ANNUAL CAT 1 TESTING, NEED MCP ON SITE (Receipt #1455393) | ERIC | ERIC | | H01 | C | 5637439 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/16/2017 | 5YR--6--15--ANNUAL --8--16--OTIS--ROPES HAVE BEEN CHANGED | JOHNW | JOHNW | | H02 | C | 5442512 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/29/2016 | 5YR -- 6/15 -- 1YR -- 8/16 -- OTIS. MISSING CATEGORY 1 TEST FORMS IN MAINTENANCE CONTROL PROGRAM, ELEVATOR PIT NEEDS CLEANED. | ROBERTV | ROBERTV | | H01 | C | 5305637 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/31/2016 | 5YR -- 6/15 -- OTIS. CAR TOP EMERGENCY EXIT HATCH IS BEING OPENED TO TRANSPORT MATERIALS WITHIN THE BUILDING, THIS EMERGENCY EXIT HATCH MUST BE RETURNED TO THE CLOSED AND SECURED POSITION AFTER MATERIAL TRANSPORT AND NOT LEFT OPEN WHEN ELEVATOR IS AVAILABLE FOR PUBLIC USE. AT ANY TIME THIS EMERGENCY EXIT HATCH IS FOUND OPEN WHEN THE ELEVATOR IS OPERABLE TO THE PUBLIC, THE ELEVATOR WILL BE REMOVED FROM SERVICE. | ROBERTV | ROBERTV | | H02 | C | 5166433 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/01/2015 | THIS INSPECTION SKIPPED IN LIEU OF WITNESS TEST PERFORMED 7/2015 (Receipt #1284454) | ROBERTV | ROBERTV | | H01 | C | 5027404 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 07/30/2015 | WITNESSED 5 YEAR TRACTION SAFETY TEST W/ OTIS -- FIRE SERVICE PHASE I AND PHASE II KEY SWITCHES MUST BE KEYED ALIKE, HOISTWAY DOOR SIGHT GUARDS ARE BROKEN AT MULTIPLE LEVELS. (NOTE: SUSPENSION ROPES HAVE BEEN REPLACED) -- OTIS LOCKBOX AT P2 | ROBERTV | ROBERTV | | H06 | C | 5004119 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/11/2015 | 5 YEAR 6/10 OTIS. SUSPENSION ROPES ARE UNDERSIZED AND MUST BE REPLACED PRIOR TO 5 YEAR SAFETY INSPECTION OR ELEVATOR WILL BE PUT OUT OF SERVICE. ALSO SIGHT GUARD IS BROKEN AT P-3 | ERIC | ERIC | | H02 | C | 4916576 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/18/2014 | 5 YEAR 6/10 OTIS. SUSPENSION ROPES DIAMETER LESS THAN ALLOWED BY CODE, CAN BE MEASURED AT 12TH FLOOR, SUSPENSION ROPES MUST BE REPLACED. (Receipt #1220759) | ERIC | ERIC | | H01 | C | 4818653 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/21/2014 | 5 YR 6/10 OTIS | ERIC | ERIC | | H02 | C | 4706749 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/10/2013 | 5YR 6-10-OTIS--MONITOR ROUGE ON SUSPENSION ROPES (Receipt #1156710) | TOM | TOM | | H01 | C | 4612691 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/26/2013 | 5 YEAR 6/10 OTIS. SUSPENSION ROPES ARE ROUGED | ERIC | ERIC | | H02 | C | 4494062 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/05/2012 | 5 YR 6-10--OTIS / CAR IS SITTING AT P2 LEVEL, NOT RESPONDING TO CALLS (Receipt #1082504) | TOM | TOM | | H01 | C | 4390958 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/29/2012 | 5 YR 6-10--OTIS | TOM | TOM | | H02 | C | 4289943 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2011 | 5 YR 6-10--OTIS (Receipt #1002966) | TOM | TOM | | H01 | C | 4215097 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/02/2011 | 5YR 6-10--OTIS | TOM | TOM | | H02 | C | 4128927 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/20/2010 | 5YR 6-10--OTIS (Receipt #936094) | TOM | TOM | | H01 | C | 4049076 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 06/29/2010 | WITNESSED 5 YEAR SAFETY TESTS. ROPES ROUGED (Receipt #917479) | ERIC | ERIC | | H06 | C | 4002850 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/19/2010 | OTIS. 5 YEAR SAFETY TEST EXPIRED, LAST TEST 9/04. SECURE EMERGENCY HATCH, CHECK ROUGING OF SUSPENSION ROPES. | ERIC | ERIC | | H02 | C | 3956149 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/30/2009 | 5 YR 9-04--OTIS TEST DUE BARRY HAS ON SCHEDULE FOR COMPLETION (Receipt #878667) | TOM | TOM | | H01 | C | 3892295 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/31/2009 | 5yr 9-04 | TOM | TOM | | H02 | C | 3818127 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/29/2008 | 5yr--9--04--otis #4 (Receipt #828404) | TOM | TOM | | H01 | C | 3747819 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/25/2008 | 5 YR 9-04 --- OTIS | LES | LES | | H02 | C | 439453 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/18/2007 | 5 YR 9-04 --- OTIS --- NEED SINAGE ON FLOORS 13,12,11,9 | LES | LES | | H01 | C | 439445 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/21/2007 | 5 YR 9-04 --- OTIS --- NEED SINAGE ON FLOORS 13,12,11,9, | LES | LES | | H02 | C | 439437 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2006 | 5 YR 9-04 --- OTIS | LES | LES | | H01 | C | 439428 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2006 | 5 YR 9-04 --- OTIS | LES | LES | | H01 | C | 439422 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/27/2006 | 5 YR 9-04 --- OTIS | LES | LES | | H02 | C | 439411 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/30/2005 | 5 YR 9-04--OTIS--GOVENOR NOISE--BEARING OR GEAR?--BARRY CALLED WILL CHECK OUT ASAP | TOM | TOM | | H01 | C | 439403 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/08/2005 | 5 YR 9-04 --- OTIS | LES | LES | | H02 | C | 439393 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/29/2004 | 5 YR 9-04 --- OTIS | LES | LES | | H01 | C | 439385 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/30/2004 | 5 YR 11-99 --- OTIS | LES | LES | | H02 | C | 439376 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/10/2003 | 5 YR 11-99--OTIS | TOM | TOM | | H01 | C | 439369 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/26/2003 | 5 YR 11-99--OTIS | TOM | TOM | | H02 | C | 439361 |
PREMISYS REAL ESTATE SVCS | H01 | C | 08/30/2002 | 5 YR 11-99--OTIS | TOM | TOM | | H01 | C | 439353 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/25/2002 | 5 YR 10-99--OTIS | TOM | TOM | | H02 | C | 439345 |
PREMISYS REAL ESTATE SVCS | H01 | C | 08/31/2001 | 5 YR 10-99--OTIS | TOM | TOM | | H01 | C | 439337 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/27/2001 | 5 YR 10-99--OTIS | TOM | TOM | | H02 | C | 439329 |
PREMISYS REAL ESTATE SVCS | H01 | P | 08/11/2000 | 5 YR 10-99--OTIS--CONTROL PANEL IN CAR LOOSE | TOM | TOM | | H01 | P | 439322 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/28/2000 | 5-YR 10-99--OTIS--(FACILITIES MANAGER--DAN MEYER--630-2690) | TOM | TOM | | H02 | C | 439316 |
PREMISYS REAL ESTATE SVCS | H01 | C | 08/19/1999 | OTIS, installed 1964 --- 5 yr 10-94 | LES | LES | | H01 | C | 439226 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/04/1999 | | RUSS | RUSS | | H02 | C | 439219 |
PREMISYS REAL ESTATE SVCS | H01 | C | 08/04/1998 | | RUSS | RUSS | | H01 | C | 439208 |
PREMISYS REAL ESTATE SVCS | H02 | C | 02/06/1998 | | DAVEL | DAVEL | | H02 | C | 439196 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/16/1997 | d.l. | RUSS | RUSS | | H01 | C | 439309 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/25/1997 | | RUSS | RUSS | | H02 | C | 439303 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/09/1996 | 5yr10-94 | RUSS | RUSS | | H01 | C | 439295 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/19/1996 | | RUSS | RUSS | | H02 | C | 439288 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/12/1995 | 5yr10-94, 29 aug for sep | RUSS | RUSS | | H01 | C | 439279 |
PREMISYS REAL ESTATE SVCS | H02 | P | 03/03/1995 | | RUSS | RUSS | | H02 | P | 439273 |
PREMISYS REAL ESTATE SVCS | H01 | R | 09/01/1994 | 5YR EXP. | RUSS | RUSS | | H01 | R | 439266 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/01/1993 | | RUSS | RUSS | | H01 | C | 439258 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/02/1993 | | RUSS | RUSS | | H02 | C | 439250 |
PREMISYS REAL ESTATE SVCS | H01 | C | 09/08/1992 | 5YR 5-89 | RUSS | RUSS | | H01 | C | 439243 |
PREMISYS REAL ESTATE SVCS | H02 | C | 03/23/1992 | | RUSS | RUSS | | H02 | C | 439235 |
PERA | H01 | C | 09/12/1991 | | RUSS | RUSS | | H01 | C | 439188 |
PERA | H02 | C | 03/29/1991 | | RUSS | RUSS | | H02 | C | 439179 |
PERA | H01 | P | 09/10/1990 | SMK DET | RUSS | RUSS | | H01 | P | 439171 |
PERA | H02 | P | 03/20/1990 | SMK DET | RUSS | RUSS | | H02 | P | 439163 |
PERA | H01 | P | 09/13/1989 | ORDER: UPDATE FIRE SERVICE, ESCAPE HATCH UNLOCKED | RUSS | RUSS | | H01 | P | 439154 |
PERA | H02 | R | 03/13/1989 | FIVE YR INSP COMP:DEC 84 / ORDER: PROVIDE FIRE SVC | RUSS | RUSS | | H02 | R | 439147 |
PERA | H16 | C | 09/21/1988 | INIT INSP, PERM ISSD | RUSS | RUSS | | H16 | C | 439140 |