TOMA ALLIANCE GROUP LLC | H02 | C | 04/05/2024 | HO2 -- 5 YR 3/22 -- ANNUAL 2/24 -- TKE W/ PEAK SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2050292) | BENH | BENH | | H02 | C | 8044060 |
TOMA ALLIANCE GROUP LLC | H01 | C | 10/31/2023 | 5YR -- 3/2022 -- CAT1 -- 2/2023 -- TKE W/ PEAK SERVICE. CAR DOOR RESTRICTOR VANE NEEDS TO BE RELOCATED TO NOT ALLOW CAR DOORS TO OPEN MORE THAN 4 INCHES WHEN CAR IS IN THE RESTRICTION ZONE. NEED TO ADD HOISTWAY FASCIA RESTRICTOR FLAG BETWEEN FLOORS 1 AND 2. ELEVATOR EMERGENCY PHONE IS NON-OPERABLE WHEN MAINLINE POWER IS SHUTOFF............... 60 DAYS TO ADDRESS. (Receipt #2003910) corrections made per Russ at Peak 11/2/23 er (Cat1 -- 2/7/2024 RV) | ROBERTV | ROBERTV | | H01 | C | 7905096 |
TOMA ALLIANCE GROUP LLC | H02 | C | 04/26/2023 | HO2 -- ANNUAL 2/23 -- TKE W/ PEAK SERVICE | BENH | BENH | | H02 | C | 7727276 |
TOMA ALLIANCE GROUP LLC | H01 | C | 10/28/2022 | 5YR 03/2022 -- TKE WITH PEAK SERVICE --/ BOTTOM COUNTERWEIGHT GUIDE ROLLERS ARE WORN AND SHALL BE DIAGNOSED--/ BUILDING TO PROVIDE LOCATION OF GENERATOR TESTING LOGS INSIDE THE MACHINE ROOM (Receipt #1910517) cat 1 2/23 BH | MIKEM | MIKEM | | H01 | C | 7565604 |
TOMA ALLIANCE GROUP LLC | HE16 | C | 06/10/2022 | WITNESSED GENERATOR TESTING WITH GRIFFIS BLESSING AND PEAK ELEVATOR - (GENERATOR TESTING IS OK). FIRE COMMAND CENTER RATH PHONE WILL NOT CONNECT TO CAR. NEED TO KEEP UP WITH MONTHLY FIRE SERVICE TESTING LOGS, QUARTERLY EMERGENCY PHONE TESTING LOGS, AND ANNUAL GENERATOR TESTING LOGS. LOGS NEED TO BE ACCESSIBLE TO ELEVATOR INSPECTORS (Fire Command Center phone has been repaired by Peak, check for logs next inspection RV) | ROBERTV | ROBERTV | | HE16 | C | 7406945 |
TOMA ALLIANCE GROUP LLC | H02 | C | 04/29/2022 | H02 - ELEVATOR STILL RED TAGGED AND REMOVED FROM SERVICE PENDING WITNESS GENERATOR TESTING | ROBERTV | ROBERTV | | H02 | C | 7357988 |
TOMA ALLIANCE GROUP LLC | H05 | C | 04/18/2022 | ELEVATOR WAS RED TAGGED AND REMOVED FROM SERVICE WITH LOCK APPLIED TO DISCONNECT PENDING GENERATOR TESTING W/ ELEVATOR COMPANY AND INSPECTOR PRESENT. IF RED TAG IS REMOVED OR ELEVATOR IS TURNED BACK ON, A $1000 FINE PER ELEVATOR / PER DAY WILL BE ENFORCED. | ROBERTV | ROBERTV | | H05 | C | 7342437 |
TOMA ALLIANCE GROUP LLC | H06 | C | 03/18/2022 | WITNESSED 5 YEAR TRACTION SAFETY TESTING W/ PEAK ELEVATOR - CAR BUFFER NEEDS OIL. ELEVATOR GENERATOR TESTING NEEDS TO BE PERFORMED WITH INSPECTOR ONSITE WITHIN 30 DAYS TO PREVENT ELEVATOR FROM BEING REMOVED FROM SERVICE. (NOTE: MONITOR SUSPENSION ROPE DIAMETERS AND WIRE BREAKS) (Receipt #1851750) | ROBERTV | ROBERTV | | H06 | C | 7307667 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/18/2021 | 5YR 02/2017-- ANNUAL 04/2020-- TKE WITH PEAK SERVICE--/ ANNUAL TRACTION CATEGORY 1 SAFETY TEST IS PAST DUE--/ PROVIDE QUARTERLY EMERGENCY PHONE LOGS (note: cat1 completed 12/7/2021 mm) (Receipt #1815400) | MIKEM | MIKEM | | H01 | C | 7144317 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/30/2021 | H02 -- 5 YEAR 2/2017 - ANNUAL 4/2020 -- / SEE PREVIOUS INSPECTION COMMENTS | RANDYB | RANDYB | | H02 | C | 6953259 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/26/2020 | 5YR -- 2/17 -- CAT1 -- 4/20 -- TKE W/ PEAK SERVICE. COULD NOT FINISH HOISTWAY INSPECTION DUE TO PROBLEMS WITH CAR TOP INSPECTION OPERATION. PEAK EMERGENCY PHONE OPERATOR COULD NOT IDENTIFY BUILDING LOCATION OR ELEVATOR. NEED QUARTERLY EMERGENCY PHONE TESTING LOG ONSITE. (Receipt #1724416) | ROBERTV | ROBERTV | | H01 | C | 6754009 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/29/2020 | H02 - 5YR -- 2/17 -- CAT1 -- 4/20 -- TKE W/ PEAK SERVICE -- NO ACCESS DUE TO COVID-19 | ROBERTV | ROBERTV | | H02 | C | 6554727 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/21/2019 | 5YR -- 2/17 -- ANNUAL 4/19 -- TKE W/ PEAK SERVICE. TOP OF CAR ESCAPE HATCH NEEDS SECURED. ASCENDING CAR OVERSPEED AND UNINTENDED MOTION TESTS NEED PERFORMED NEXT VISIT. MACHINE ROOM FIRE EXTINGUISHER EXPIRED................ CAR FAULTED OUT OF SERVICE AFTER HOISTWAY INSPECTION, CONTACTED BUILDING ENGINEER AND ELEVATOR SERVICE COMPANY. (Receipt #1638802) | ROBERTV | ROBERTV | | H01 | C | 6374609 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/25/2019 | 5YR -- 2/17 -- ANNUAL 4/19 -- TKE W/ PEAK SERVICE. (ITEMS HAVE BEEN ADDRESSED) | ROBERTV | ROBERTV | | H02 | C | 6177521 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/16/2018 | 5YR -- 2/17 -- ANNUAL 4/18 -- TKE W/ PEAK SERVICE. ASCENDING CAR OVERSPEED AND UNINTENDED MOTION TESTS WERE MARKED "N/A" ON CATEGORY 1 TEST FORMS. THESE TESTS ARE REQUIRED TO BE PERFORMED ANNUALLY PER ASME A17.2 (2.43.2.1(a)(1) AND (b)(1), AND (2.43.2.1(a)(2) AND (b)(2). ALSO, CHECK CAB DOOR RESTRICTOR BAR ENGAGEMENT WITH HOISTWAY FLAGS AND PLATE. CAB DOOR RESTRICTOR BAR MOUNTING AT CAB DOOR IS LOOSE.............90 DAYS TO ADDRESS. | ROBERTV | ROBERTV | | H01 | C | 5995370 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/06/2018 | 5YR --2--17--DOVER --PEAK SERVICE --ANNUAL EXPIRED | JOHNW | JOHNW | | H02 | C | 5809842 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/18/2017 | 5YR--2--17--DOVER (Receipt #1460123) | JOHNW | JOHNW | | H01 | C | 5658943 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/03/2017 | H02 -- FINAL INSPECTION COMPLETED 2/2017 | ROBERTV | ROBERTV | | H02 | C | 5462996 |
EQUITY GROUP - EXECUTIVE TOWER | H06 | C | 12/23/2016 | WITNESSED AT MODERNIZATION ACCEPTANCE -- SEE #J77873 INSPECTION NOTES | ROBERTV | ROBERTV | | H06 | C | 5376044 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/03/2016 | STILL UNDER GOING MOD (Receipt #1367572) | ROBERTV | ROBERTV | | H01 | C | 5308446 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/11/2016 | STILL UNDERGOING MOD | ROBERTV | ROBERTV | | H02 | C | 5174424 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/26/2015 | 5 YEAR 4/11 TKE AND LOCKBOX. WAIVED REQUIREMENT FOR 5 YEAR TEST UNTIL MODS ARE COMPLETED (Receipt #1295495) | ERIC | ERIC | | H01 | C | 5065638 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/16/2015 | 5 YEAR 4/11 TKE AND LOCKBOX---HO2--MOD SCHEDULED FOR JULY 2015 | ERIC | ERIC | | H02 | C | 4936898 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/21/2014 | 5 YEAR 4/11 TKE AND LOCKBOX. (Receipt #1227587) | ERIC | ERIC | | H01 | C | 4839039 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/21/2014 | HO2 | JOHNW | JOHNW | | H02 | C | 4723479 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/16/2013 | 5YR 4-11-DOVER-PHONES FOR ALL CARS RING TO STRATMOOR HILLS FIRE DEPT / NO ANNUAL INSPECTION TAGS ON EQUIPMENT (ALL CARS)(RECEIPT #1163869) | TOM | TOM | | H01 | C | 4633833 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/18/2013 | 5YR 4-11--DOVER--PHONE IN CAR NOT WORKING | TOM | TOM | | H02 | C | 4515052 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/18/2012 | 5 YR 4-11--DOVER--POST FLOOR DESIGNATION NUMBERS AT ALL LANDINGS FOR ALL FOUR CARS--PHASE II "HOLD" FUNCTION NOT WORKING (Receipt #1090106) | TOM | TOM | | H01 | C | 4410547 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/16/2012 | 5 YR 4-11--DOVER--POST FLOOR DESIGNATION NUMBERS AT ALL LANDINGS & IN HOISTWAY | TOM | TOM | | H02 | C | 4304123 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/11/2011 | 5 YR 4-11--DOVER--PHONE IN CAR NOT WORKING / POST FLOOR DESIGNATION NUMBERS AT ALL LANDINGS AND IN HOISTWAY (Receipt #1009341) | TOM | TOM | | H01 | C | 4229054 |
EQUITY GROUP - EXECUTIVE TOWER | H06 | C | 04/22/2011 | WITNESSED 5 YEAR SAFETY TEST. NEED TO NUMBER ALL FLOORS ON DOOR JAMBS AND ALL MIRRORS MUST BE PROPERLY SECURED (Receipt #970730) | ERIC | ERIC | | H06 | C | 4139684 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/05/2011 | 5YR 1-06--DOVER--LOCKBOX--POST FLOOR DESIGNATION NUMBERS AT ALL LANDINGS / NUMBER INSIDE OF HOISTWAY DOORS | TOM | TOM | | H02 | C | 4142471 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/13/2010 | 5 YEAR 1/06 TKE AND LOCKBOX. NEED FLOOR NUMBERS ON INSIDE OF HOISTWAY DOORS (Receipt #939010) | ERIC | ERIC | | H01 | C | 4055518 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/08/2010 | 5 YR 1-06--DOVER--LOCKBOX | TOM | TOM | | H02 | C | 3968369 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/26/2009 | 5 YR 1-06 DOVER (Receipt #882547) | TOM | TOM | | H01 | C | 3903086 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/30/2009 | 5 YR 1-06--DOVER | TOM | TOM | | H02 | C | 3829765 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/07/2008 | 5YR 1-06--DOVER (Receipt #833696) | TOM | TOM | | H01 | C | 3764224 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 05/02/2008 | 5yr--1--06--dover | JOHNW | JOHNW | | H02 | C | 3669774 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/22/2007 | 5 YR 1-06 --- DOVER | LES | LES | | H01 | C | 459519 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/30/2007 | 5 YR 1-06 --- DOVER | LES | LES | | H02 | C | 459511 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/17/2006 | 5 YR 1-06 --- DOVER | LES | LES | | H01 | C | 459505 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/11/2006 | 5 YR 1-06 --- DOVER | LES | LES | | H02 | C | 459498 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/17/2005 | 5 YR TEST DUE --- DOVER --- CHECK PHONE NEXT INSP. | LES | LES | | H01 | C | 459492 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/04/2005 | 5 YR 1-00 --- DOVER LOCKBOX OUTSIDE BEHIND TRANSFORMER NORTH WEST CORNER | LES | LES | | H02 | C | 459486 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/20/2004 | 5 YR 1-00 --- DOVER | LES | LES | | H01 | C | 459481 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/12/2004 | 5 YR 1-00 --- DOVER | LES | LES | | H02 | C | 459473 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/06/2003 | 5 YR 1-00 | LES | LES | | H01 | C | 459466 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/04/2003 | 5 YR 1-00 | LES | LES | | H02 | C | 459457 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/30/2002 | 5 YR 1--00 | LES | LES | | H01 | C | 459449 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/15/2002 | 5 YR 1-00 | LES | LES | | H02 | C | 459441 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/17/2001 | 5 YR 1-00 --- DOVER LOCKBOX ON PENTHOUSE DOOR --- 10TH FLOOR REMODEL | LES | LES | | H01 | C | 459434 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/06/2001 | | LES | LES | | H02 | C | 459426 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/12/2000 | | LES | LES | | H01 | C | 459417 |
EQUITY GROUP - EXECUTIVE TOWER | H03 | C | 05/10/2000 | | LES | LES | | H03 | C | 459246 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/14/2000 | 5 YR 1-00--DOVER--LOCKBOX--LIGHT BULB GUARDING IN CAR | TOM | TOM | | H02 | C | 459410 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | R | 10/14/1999 | needs 5 yr test | LES | LES | | H01 | R | 459239 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/13/1999 | 5YR DUE THIS YR | RUSS | RUSS | | H02 | C | 459231 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/08/1998 | 5yr--4-94 | RUSS | RUSS | | H01 | C | 459223 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/21/1998 | | RUSS | RUSS | | H02 | C | 459215 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/14/1997 | | RUSS | RUSS | | H01 | C | 459401 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/28/1997 | | RUSS | RUSS | | H02 | C | 459393 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/02/1996 | | RUSS | RUSS | | H01 | C | 459386 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/19/1996 | 5yr 5-94 | RUSS | RUSS | | H02 | C | 459378 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/03/1995 | 5yr 5-94 | RUSS | RUSS | | H01 | C | 459370 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/17/1995 | 5yr 5-94 | RUSS | RUSS | | H02 | C | 459362 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/10/1994 | 5YR,5-94 | RUSS | RUSS | | H01 | C | 459354 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | R | 04/25/1994 | 5YR EXPIRED | RUSS | RUSS | | H02 | R | 459345 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/11/1993 | | RUSS | RUSS | | H01 | C | 459340 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/27/1993 | | RUSS | RUSS | | H02 | C | 459332 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/07/1992 | 5YR 11-88 | RUSS | RUSS | | H01 | C | 459324 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/20/1992 | | RUSS | RUSS | | H02 | C | 459316 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/01/1991 | | RUSS | RUSS | | H01 | C | 459308 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/10/1991 | | RUSS | RUSS | | H02 | C | 459301 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/01/1990 | | RUSS | RUSS | | H01 | C | 459293 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 04/02/1990 | | RUSS | RUSS | | H02 | C | 459285 |
EQUITY GROUP - EXECUTIVE TOWER | H01 | C | 10/09/1989 | | RUSS | RUSS | | H01 | C | 459277 |
EQUITY GROUP - EXECUTIVE TOWER | H02 | C | 03/07/1989 | | RUSS | RUSS | | H02 | C | 459269 |
EQUITY GROUP - EXECUTIVE TOWER | H16 | C | 12/29/1988 | DEFICIENCIES CORRECTED | RUSS | RUSS | | H16 | C | 459263 |
EQUITY GROUP - EXECUTIVE TOWER | H16 | C | 10/10/1988 | INIT INSP,PERM ISSD,ORDER:OUTDATED TAGS/5 YR DUE | RUSS | RUSS | | H16 | C | 459255 |