COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/20/2024 | 5 YEAR 9/23 -- ANNUAL 9/23 -- TKE & LOCKBOX AT MACHINE ROOM 5 -- / BUILDING TO KEEP MONTHLY FIREFIGHTERS’ EMERGENCY OPERATION AND QUARTERLY EMERGENCY PHONE TEST LOGS UP TO DATE / NEED HARD COPY TAC32T INSPECTORS GUIDE ON SITE FOR TESTING / EMERGENCY ALARM BELL NOT WORKING WITH CAB 110V DISCONNECTED (Receipt #2044659) | DUSTINS | DUSTINS | | H01 | C | 8028006 |
COLORADO SPRINGS HOTEL OWNER, LLC | H05 | C | 09/11/2023 | RED TAG SHUT DOWN: ELEVATOR WAS SHUT DOWN AFTER TESTING DUE TO ALL ROPES NEEDING REPLACED SINCE 3/2023 / BUILDING OWNER AND CONTRACTOR TO CONTACT PPRBD AFTER REPAIRS MADE BEFORE RETURNING ELEVATOR BACK TO NORMAL SERVICE | DUSTINS | DUSTINS | | H05 | C | 7851848 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/11/2023 | WITNESSED AT H02 (Receipt #1986691) | DUSTINS | DUSTINS | | H02 | C | 7851836 |
COLORADO SPRINGS HOTEL OWNER, LLC | H06 | C | 09/11/2023 | WITNESSED TRACTION SAFETY TESTING WITH TKE -- 5 YEAR 9/23 -- TKE & LOCKBOX AT MACHINE ROOM 5 -- / ELEVATOR WAS SHUT DOWN AFTER TESTING DUE TO ALL ROPES NEEDING REPLACED SINCE 3/2023 / BUILDING TO KEEP MONTHLY FIREFIGHTERS’ EMERGENCY OPERATION AND QUARTERLY EMERGENCY PHONE TEST LOGS UP TO DATE / BUILDING TO KEEP ANNUAL GENERATOR TESTING LOG UP TO DATE / EMERGENCY LIGHT AND ALARM BELL NON FUNCTIONAL WITH CAB 110V DISCONNECTED / NEED TAC32T INSPECTORS GUIDE ON SITE FOR TESTING / EMERGENCY POWER JEWEL AT CALL STATION NOT ILLUMINATING / 60 DAYS TO ADDRESS (Receipt #1986686) | DUSTINS | DUSTINS | | H06 | C | 7851813 |
COLORADO SPRINGS HOTEL OWNER, LLC | HE16 | C | 05/09/2023 | PERFORMED FOLLOW UP INSPECTION TO PREVIOUS ITEMS LISTED. NO ITEMS HAVE BEEN ADDRESSED. THE FOLLOWING ITEMS NEED ADDRESSED BY 7/31/23 TO AVOID SHUT DOWN, ROPES ON COUNTERWEIGHT SIDE ARE ROUGED AT FLOORS 7 & 8, ROPES ARE ALSO UNDERSIZED PER A17.6 AS MEASUREMENTS TAKEN ARE SMALLER THAN 9.688MM IN SEVERAL LOCATIONS, ALL ROPES NEED REPLACED. EMERGENCY ALARM BELL IS STILL NON FUNCTIONAL / RBD NOTE: 5 YEAR WITNESS TESTING DUE 8/2023 | DUSTINS | DUSTINS | | HE16 | C | 7739050 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/06/2023 | 5 YEAR 7/18 -- ANNUAL 4/22 -- TKE & LOCKBOX AT MACHINE ROOM 5 -- / BUILDING TO KEEP MONTHLY FIREFIGHTERS’ EMERGENCY OPERATION AND QUARTERLY EMERGENCY PHONE TEST LOGS UP TO DATE / NEED ANNUAL ELEVATOR EMERGENCY POWER TEST LOGS WITHIN THE MCP / EMERGENCY ALARM BELL IS NON FUNCTIONAL / ROPES ON COUNTERWEIGHT SIDE WHERE ROUGING OCCURS AT FLOORS 7 & 8 MEASURES 9.56MM AT SMALLEST MEASUREMENT TAKEN, MINIMUM DIAMETER PER A17.6 IS 9.688MM / RBD NOTE: 5 YEAR WITNESS TESTING DUE 8/2023 (Receipt #1937578) | DUSTINS | DUSTINS | | H01 | C | 7678157 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/28/2022 | HO2 -- ANNUAL 4/22 -- TKE & LOCKBOX | BENH | BENH | | H02 | C | 7532356 |
COLORADO SPRINGS HOTEL OWNER, LLC | H05 | C | 04/14/2022 | ELEVATOR HAS BEEN RED TAGGED DUE TO ANNUAL TRACTION SAFETY TEST PAST DUE -- ELEVATOR WILL BE REMOVED FROM SERVICE ON 4/28/2022 IF TEST ISN'T COMPLETED cat 1 4/2022 | BENH | BENH | | H05 | C | 7339210 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/14/2022 | ANNUAL 12/2020 -- TKE W/ INNOVATION KEYS & TKE LOCKBOX -- ANNUAL TRACTION SAFETY TEST IS PAST DUE -- NEED FIREFIGHTERS LOG AND QUARTERLY PHONE LOG FOR 2022 -- NEED ANNUAL ELEVATOR EMERGENCY POWER TEST LOGS IN ELEVATOR MAINTENANCE CONTROL PROGRAM( 2ND NOTICE) -- NEED TO CLEAN PIT -- MACHINE ROOM FIRE EXTINGUISHER HAS EXPIRED --ELEVATOR WILL BE REMOVED FROM SERVICE IN 30 DAYS UNLESS ANNUAL TRACTION SAFETY TEST IS PERFORMED (Receipt #1850370) | BENH | BENH | | H01 | C | 7300713 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/28/2021 | HO2 -- ANNUAL 12/2020 -- TKE W/ INNOVATION KEYS & TKE LOCKBOX -- SEE PREVIOUS NOTES FROM HO1 | BENH | BENH | | H02 | C | 7123057 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/16/2021 | 5 YEAR 7/2018 - ANNUAL 12/2020 -- TKE W/ INNOV KEYS & TKE LOCKBOX -- / NEED ANNUAL ELEVATOR EMERGENCY POWER TEST LOGS IN ELEVATOR MAINTENANCE CONTROL PROGRAM / EMERGENCY PHONE OPERATOR UNABLE TO ID ELEVATOR/BUILDING LOCATION (Receipt #1757226) | RANDYB | RANDYB | | H01 | C | 6900497 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/30/2020 | H02 -- ANNUAL 9/2019 -- TKE W/ INNOV KEYS & TKE LOCKBOX -- SEE PREVIOUS INSPECTION NOTES cat 1 12/20 | RANDYB | RANDYB | | H02 | C | 6724737 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/19/2020 | 5YR -- 7/18 -- ANNUAL 9/19 -- TKE W/ INNOV KEYS AND TKE LOCKBOX. LARGE HOLES IN SHEETROCK SHAFT LINER FOR INSTALLATION OF HALL FIXTURES AT TIME OF MODERNIZATION NEED TO BE PATCHED TO MAINTAIN THE ORIGINAL FIRE RATING - (HOLES ARE AT LOBBY AND 8TH FLOOR ENTRANCE HEADERS). NEED ANNUAL ELEVATOR EMERGENCY POWER TEST LOGS IN ELEVATOR MAINTENANCE CONTROL PROGRAM. (Receipt #1669165) | ROBERTV | ROBERTV | | H01 | C | 6515572 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/27/2019 | H02 -- 5YR - 7/18 -- ANNUAL 9/19 -- TKE W/ INNOVATION KEYS AND LOCKBOX. ITEMS HAVE BEEN ADDRESSED. | ROBERTV | ROBERTV | | H02 | C | 6350228 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/12/2019 | 5YR -- 7/18 -- MONTGOMERY - W/ TKE LOCKBOX. GOVERNOR TAIL SHEAVE WEIGHT IS SITTING ON PIT FLOOR - (GOVERNOR ROPE NEEDS TO BE SHORTENED). EMERGENCY PHONE VOLUME TOO LOW | ROBERTV | ROBERTV | | H01 | C | 6131141 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/20/2018 | ANNUAL AND 5 YEAR 7/18, TKE MOD. HO2 | ERIC | ERIC | | H02 | C | 5971273 |
COLORADO SPRINGS HOTEL OWNER, LLC | H06 | C | 07/10/2018 | PERFORMED ACCEPTANCE TO MOD -- SEE #L27683 FOR INSPECTION NOTES | ROBERTV | ROBERTV | | H06 | C | 5897784 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/12/2018 | UNDERGOING MOD (Receipt #1486750) | ERIC | ERIC | | H01 | C | 5786416 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/19/2017 | 5 YEAR 11/16 KONE, TKE SERVICE. MOD SCHEDULED | ERIC | ERIC | | H02 | C | 5630545 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/09/2017 | 5 YEAR 11/16 KONE. OTIS SERVICE. MOD TO BE PROPOSED SOON (Receipt #1408314) | ERIC | ERIC | | H01 | C | 5436653 |
COLORADO SPRINGS HOTEL OWNER, LLC | H06 | C | 11/03/2016 | WITNESSED 5 YEAR SAFETY TEST. GOVERNOR ROPE IS IN POOR CONDITION, WILL MONITOR (Receipt #1378871) | ERIC | ERIC | | H06 | C | 5335532 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/21/2016 | UNDERGOING REPAIRS AND TESTING | ERIC | ERIC | | H02 | C | 5299374 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/09/2016 | 5 YEAR 6/11 KONE. NEED CODE COMPLIANT MAINTENANCE CONTROL PROGRAMS FOR ALL ELEVATORS. (Receipt #1317175) | ERIC | ERIC | | H01 | C | 5151101 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/18/2015 | 5 YEAR 6/11 KONE HO2 | ERIC | ERIC | | H02 | C | 5039489 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/19/2015 | 5 YEAR 6/11 MKE. ELEVATOR MACHINE ROOM DOOR ON ROOF MUST BE REPLACED AND SECURED (Receipt #1251528) | ERIC | ERIC | | H01 | C | 4920458 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/23/2014 | 5YR--6--11--MKE--GUIDE ROLLERS NEED REPLACED --ROPES NEED CLEANED AND CHECK ALL FLOORS FOR FIRE SIGNS --SAME PROBLEMS AS LAST INSPECTION | JOHNW | JOHNW | | H02 | C | 4821081 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/24/2014 | 5 YR 6/11 MKE. GUIDE ROLLER AT TOP OF CAR DAMAGED, NEED CAR TOP LIGHT AND ROPES STILL NEED TO BE CLEANED TO ALLOW FOR PROPER INSPECTION. NEED CALL STATION FIRE SIGNS AT ALL FLOORS (Receipt #1185472) | ERIC | ERIC | | H01 | C | 4707747 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/16/2013 | 5YR 6-11-MONTGOMERY--TOP OF CAR LIGHT BULB MISSSING--ROPES ON ALL CARS STILL NEED TO BE CLEANED FOR INSPECTION | TOM | TOM | | H02 | C | 4612718 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/21/2013 | 5 YEAR 6/11 MKE. BOTTOM GUIDE ROLLER DAMAGED, ROPES NEED TO BE CLEANED (Receipt #1118378) | ERIC | ERIC | | H01 | C | 4491291 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/28/2012 | 5 YR 6-11--MONTGOMERY HALL CALL STATION LOOSE IN WALL AT MAIN LANDING / SEQUENCE NUMBER INSIDE CAR (#1) | TOM | TOM | | H02 | C | 4392014 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/06/2012 | 5 YR 6-11--MONTGOMERY--SEQUENCE NUMBER CAR INSIDE---CAR #1 (Receipt #1036396) | TOM | TOM | | H01 | C | 4290337 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/08/2011 | 5 YR 6-11--MONTGOMERY- | TOM | TOM | | H02 | C | 4215363 |
COLORADO SPRINGS HOTEL OWNER, LLC | H06 | C | 06/08/2011 | WITNESSED 5 YEAR SAFETY TEST (Receipt #979170) | ERIC | ERIC | | H06 | C | 4160936 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/24/2011 | 5 YR SAFETY TEST EXPIRED--LAST TEST 3-05--KONE (Receipt #966525) | TOM | TOM | | H01 | C | 4129259 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/17/2010 | 5 YEAR SAFETY TEST EXPIRED. ELEVATOR OUT OF SERVICE AT TIME OF INSPECTION | ERIC | ERIC | | H02 | C | 4041502 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/15/2010 | 5 yr 3-05--montgomery (Receipt #901683) | TOM | TOM | | H01 | C | 3958199 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/30/2009 | KONE 5 YR 3/05. ELECTRIC EYE DOOR SAFETIES INOPERABLE, CHECK DOOR FORCE ON ALL 3 LOBBY ELEVATORS | ERIC | ERIC | | H02 | C | 3891811 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/31/2009 | 5YR 3-05--MONTGOMERY (Receipt #852318) | TOM | TOM | | H01 | C | 3818725 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/26/2008 | 5yr--3--05--kone---replace broken stop switch in pit | TOM | TOM | | H02 | C | 3746756 |
COLORADO SPRINGS HOTEL OWNER, LLC | H01 | C | 03/31/2008 | 5YR--3--05--MONTGOMERY | JOHNW | JOHNW | | H01 | C | 475292 |
COLORADO SPRINGS HOTEL OWNER, LLC | H02 | C | 09/03/2007 | 5YR--3--05--MONTGOMERY | JOHNW | JOHNW | | H02 | C | 475285 |
WYNDHAM HOTEL | H01 | C | 02/21/2007 | 5 YR 3-05 --- MONTGOMERY --- REPAIR SHEETROCK IN MACHINE ROOM --- FIRE SERVICE STUCK IN PHASE ONE MODE, TOLD KYLE IN MAINTENANCE | LES | LES | | H01 | C | 475278 |
WYNDHAM HOTEL | H02 | C | 08/29/2006 | 5YR--3--05--MONTGOMERY | JOHNW | JOHNW | | H02 | C | 475270 |
WYNDHAM HOTEL | H01 | C | 02/14/2006 | 5 YR 3-05 --- KONE --- REPAIR SHEETROCK IN MACHINE ROOM | LES | LES | | H01 | C | 475261 |
WYNDHAM HOTEL | H02 | C | 08/24/2005 | 5 YR 3-05 --- KONE | LES | LES | | H02 | C | 475254 |
MARRIOTT HOTEL | H01 | C | 02/23/2005 | 5 YR TEST OVERDUE [2ND NOTICE] | LES | LES | | H01 | C | 475245 |
MARRIOTT HOTEL | H02 | C | 08/17/2004 | 5 YR TEST DUE --- PHONE INOP. | LES | LES | | H02 | C | 475238 |
MARRIOTT HOTEL | H01 | C | 02/24/2004 | 5 YR 2-99 --- MONTGOMERY | LES | LES | | H01 | C | 475231 |
MARRIOTT HOTEL | H02 | C | 08/19/2003 | 5 YR 2-99 --- CLEAN PIT --- REPAIR SHEETROCK IN MACHINE ROOM | LES | LES | | H02 | C | 475223 |
MARRIOTT HOTEL | H01 | C | 02/25/2003 | 5 YR 2-99 --- CLEAN PIT | LES | LES | | H01 | C | 475214 |
MARRIOTT HOTEL | H02 | C | 08/06/2002 | 5 YR 2-99 | LES | LES | | H02 | C | 475206 |
MARRIOTT HOTEL | H01 | C | 02/27/2002 | 5 YR 2-99--MONTGOMERY | TOM | TOM | | H01 | C | 475198 |
MARRIOTT HOTEL | H02 | C | 08/27/2001 | RP 5 YR 2-99 | LES | LES | | H02 | C | 475191 |
MARRIOTT HOTEL | H01 | C | 02/26/2001 | 5 YR 2-99 | LES | LES | | H01 | C | 475185 |
MARRIOTT HOTEL | H02 | C | 08/29/2000 | 5 YR 2-99--MONTGOMERY | TOM | TOM | | H02 | C | 475176 |
MARRIOTT HOTEL | H01 | P | 02/11/2000 | 5-YR-2-99--MONTGOMERY --PHONE INOP | TOM | TOM | | H01 | P | 475170 |
MARRIOTT HOTEL | H02 | P | 08/03/1999 | Montgomery installed 12- 1988, 5yr. 2-99 --- phone inoperable | LES | LES | | H02 | P | 475014 |
MARRIOTT HOTEL | H01 | C | 02/12/1999 | | RUSS | RUSS | | H01 | C | 475006 |
MARRIOTT HOTEL | H02 | P | 08/25/1998 | phone inop no directions | DAVEL | DAVEL | | H02 | P | 474999 |
MARRIOTT HOTEL | H01 | C | 02/05/1998 | 5yr 10-94 | RUSS | RUSS | | H01 | C | 474991 |
MARRIOTT HOTEL | H02 | C | 08/26/1997 | | RUSS | RUSS | | H02 | C | 475162 |
MARRIOTT HOTEL | H01 | C | 02/04/1997 | 5yr 10-94 | RUSS | RUSS | | H01 | C | 475156 |
MARRIOTT HOTEL | H02 | C | 08/29/1996 | | RUSS | RUSS | | H02 | C | 475148 |
MARRIOTT HOTEL | H01 | C | 02/02/1996 | | RUSS | RUSS | | H01 | C | 475140 |
MARRIOTT HOTEL | H02 | C | 08/21/1995 | | RUSS | RUSS | | H02 | C | 475129 |
MARRIOTT HOTEL | H01 | C | 02/01/1995 | | RUSS | RUSS | | H01 | C | 475120 |
MARRIOTT HOTEL | H02 | C | 08/23/1994 | | RUSS | RUSS | | H02 | C | 475112 |
MARRIOTT HOTEL | H01 | C | 02/01/1994 | | RUSS | RUSS | | H01 | C | 475105 |
MARRIOTT HOTEL | H02 | C | 08/24/1993 | | RUSS | RUSS | | H02 | C | 475094 |
MARRIOTT HOTEL | H01 | C | 02/02/1993 | | RUSS | RUSS | | H01 | C | 475085 |
MARRIOTT HOTEL | H02 | C | 08/19/1992 | | RUSS | RUSS | | H02 | C | 475078 |
MARRIOTT HOTEL | H01 | C | 02/03/1992 | 3-89 5YR | RUSS | RUSS | | H01 | C | 475070 |
MARRIOTT HOTEL | H02 | C | 08/26/1991 | | RUSS | RUSS | | H02 | C | 475063 |
MARRIOTT HOTEL | H01 | C | 02/01/1991 | | RUSS | RUSS | | H01 | C | 475054 |
MARRIOTT HOTEL | H02 | C | 08/27/1990 | | RUSS | RUSS | | H02 | C | 475046 |
MARRIOTT HOTEL | H01 | P | 02/01/1990 | TAG | RUSS | RUSS | | H01 | P | 475038 |
MARRIOTT HOTEL | H02 | P | 08/02/1989 | NEED FIVE YEAR TEST TAG | RUSS | RUSS | | H02 | P | 475030 |
MARRIOTT HOTEL | H16 | C | 02/22/1989 | INIT INSP,PERM ISSD | RUSS | RUSS | | H16 | C | 475023 |