BIJOU CONDOS LLC | H01 | C | 04/04/2024 | ANNUAL 12/23 -- DOVER W/ TKE SERVICE -- NO VISIBLE CODE ISSUES. (Receipt #2049747) | PAULM | PAULM | | H01 | C | 8042406 |
BIJOU CONDOS LLC | H02 | C | 10/11/2023 | HO2 -- ANNUAL 12/22 -- DOVER W/ TKE SERVICE -- WAS ON-SITE TO CHECK PREVIOUS INSPECTION WRITE UPS AND CHECK LOGS, & TEST EMERGENCY PHONE IN ELEVATOR -- CAR DOES STILL TAKES "GHOST" CALLS TO THE 3RD FLOOR, MECHANIC TO DIAGNOSE (Receipt #1997183) | BENH | BENH | | H02 | C | 7884187 |
BIJOU CONDOS LLC | H01 | C | 04/11/2023 | ANNUAL 12/22 -- DOVER W/ TKE SERVICE -- CAR DOOR CLUTCH SCRAPING FASCIA -- MECHANIC TO DIAGNOSE: WHEN I WAS CHECKING STOP SWITCH IN THE PIT, AFTER I PUT CAR BACK IN SERVICE THE PUMP RAN APPROXIMATELY FOR 5 MINUTES THAN TOOK A "GHOST"CALL TO THE 3RD FLOOR THEN CAME BACK DOWN TO THE 1ST FLOOR -- BUILDING OWNER TO MAINTAIN QUARTERLY EMERGENCY PHONE LOGS FOR 2023 -- 2ND FLOOR "UP" HALL CALL BUTTON DOESN'T ILLUMINATE (Receipt #1945929) | BENH | BENH | | H01 | C | 7712321 |
BIJOU CONDOS LLC | H02 | C | 10/26/2022 | HO2 -- ANNUAL 12/21 -- DOVER W/ TKE SERVICE -- SEE PEVIOUS NOTES cat 1 -- 12/22 DS
| BENH | BENH | | H02 | C | 7563661 |
BIJOU CONDOS LLC | HE16 | C | 05/27/2022 | PERFORMED FOLLOW UP INSPECTION AND NOTICED WHEN I PUSH HALL CALL BUTTON ON 1ST FLOOR ELEVATOR TAKES "GHOST" CALLS AND GOES UP TO 3RD FLOOR THEN COMES DOWN TO 1ST FLOOR (DID THAT MULTIPLE TIMES) -- DOOR ON 1ST FLOOR DOESN'T OPEN ALL THE WAY -- MECHANIC TO LOG ALL MAINTENANCE BEING PERFORMED ON ELEVATOR IN MCP & NEED FIREFIGHTER LOGS & QUARTERLY EMERGENCY PHONE LOGS UP TO DATE FOR 2022 -- WILL NOT COME BACK OUT UNTIL ELEVATOR HAS BEEN FIXED AND ELEVATOR COMPANY CONTACTS PPRBD FOR RE-INSPECTION | BENH | BENH | | HE16 | C | 7391610 |
BIJOU CONDOS LLC | H01 | C | 04/07/2022 | ANNUAL 12/21 -- DOVER W/ TKE SERVICE -- ELEVATOR WAS OUT OF SERVICE AT TIME OF INSPECTION -- HOLD PERMIT TO OPERATE -- WILL FOLLOW UP IN 30 DAYS (Receipt #1856753) | BENH | BENH | | H01 | C | 7329478 |
BIJOU CONDOS LLC | H02 | C | 10/12/2021 | H02 -- CAT1 -- 12/20 -- DOVER W/ TKE SERVICE cat1 12/21 | ROBERTV | ROBERTV | | H02 | C | 7139220 |
BIJOU CONDOS LLC | H01 | C | 04/20/2021 | CAT1 -- 12/20 -- DOVER W/ TKE SERVICE. PIT LADDER STILL NOT INSTALLED. EMERGENCY LIGHT STILL NON-OPERABLE. CAR DOOR SEPARATES FROM HOISTWAY DOOR AT 1ST FLOOR WHEN TESTING DOOR FORCE. (DO NOT ISSUE PERMIT TO OPERATE) (Receipt #1766048) (Items have been addressed per TKE) | ROBERTV | ROBERTV | | H01 | C | 6939733 |
BIJOU CONDOS LLC | H06 | C | 12/03/2020 | WITNESSED SAFETY TESTING W/ TKE -- DOVER W/ TKE SERVICE -- / PROVIDE MACHINE ROOM FIRE EXTINGUISHER / PROVIDE PIT LADDER / 2ND LANDING HALL CALL UP BUTTON LIGHT IS OUT / EMERGENCY LIGHT IS NONFUNCTIONAL / -- 60 DAYS PROVIDED TO ADDRESS CODE ISSUES TO AVOID SERVICE INTERRUPTION | RANDYB | RANDYB | | H06 | C | 6796068 |
BIJOU CONDOS LLC | H02 | C | 10/27/2020 | No inspection made due to presence of Covid 19 | ERIC | ERIC | | H02 | C | 6755051 |
BIJOU CONDOS LLC | H01 | C | 04/15/2020 | CAT 1 -- 3/18 -- DOVER W/ TKE SERVICE. ELEVATOR OUT OF SERVICE AT TIME OF INSPECTION. CATEGORY 1 TESTING NEEDS TO BE UP TO DATE IF ELEVATORS ARE GOING TO STAY IN SERVICE DURING REMODEL..... HOLD PERMIT TO OPERATE. (Receipt #1674014) | ROBERTV | ROBERTV | | H01 | C | 6541755 |
BIJOU CONDOS LLC | H02 | C | 10/31/2019 | RP 3/18--TKE--HO2 | CALE | CALE | | H02 | C | 6384223 |
BIJOU CONDOS LLC | H01 | C | 04/25/2019 | BUILDING IS VACANT PENDING REMODEL, NO CORRESPONDENCE FROM BUILDING REPRESENTATIVE AFTER MULTIPLE ATTEMPTS. HOLD PERMIT TO OPERATE (SEE IMAGES FOR LETTER SENT TO OWNER) (Receipt #1593306) | ROBERTV | ROBERTV | | H01 | C | 6177578 |
BEST WESTERN-LE BARON | H02 | C | 10/22/2018 | RP 3/18 TKE, HO2 | ERIC | ERIC | | H02 | C | 6001184 |
BEST WESTERN-LE BARON | H01 | C | 04/12/2018 | RP--3--18--DOVER (Receipt #1493344) | JOHNW | JOHNW | | H01 | C | 5814714 |
BEST WESTERN-LE BARON | H02 | C | 10/25/2017 | RP -- 2/17 -- DOVER W/ TKE SERVICE. EMERGENCY LIGHT STILL NOT WORKING | ROBERTV | ROBERTV | | H02 | C | 5666208 |
BEST WESTERN-LE BARON | H01 | C | 04/07/2017 | RP--2--17--DOVER --POST CAPACITY TAG INSIDE CAB --EMERGENCY LIGHT NOT WORKING (Receipt #1415245) | JOHNW | JOHNW | | H01 | C | 5467249 |
BEST WESTERN-LE BARON | H02 | C | 10/12/2016 | RP--2--16--TKE | JOHNW | JOHNW | | H02 | C | 5316311 |
BEST WESTERN-LE BARON | H01 | C | 04/01/2016 | THIS VISIT SKIPPED IN LIEU OF WITNESS TEST PERFORMED 2/2016 (Receipt #1321366) | ROBERTV | ROBERTV | | H01 | C | 5167516 |
BEST WESTERN-LE BARON | H06 | C | 02/10/2016 | WITNESSED 5 YEAR SAFETY TEST. NEED CAPACITY RATE POSTED INSIDE CAR, NEED WORKING EMERGENCY LIGHT | ERIC | ERIC | | H06 | C | 5133262 |
BEST WESTERN-LE BARON | H02 | C | 10/20/2015 | RP--1--15--DOVER --TKE SERVICE --CATCH CAN OVERFLOWING--MISSING CAPACITY TAG IN CABSTATE REQUIRED WITNESSED TEST REQUIRED TEST DUE NOW | JOHNW | JOHNW | | H02 | C | 5061116 |
BEST WESTERN-LE BARON | H01 | C | 04/20/2015 | RP--7--14--DOVER --WITNESSED TEST AT THE NEXT ANNUAL (Receipt #1259298) | TOM | TOM | | H01 | C | 4946159 |
BEST WESTERN-LE BARON | H02 | C | 10/31/2014 | RP -- 7/14 -- MCE/DOVER/TKE. DOOR OPERATOR CREEPS TOWARD CLOSING AFTER OPENING MECHANICALLY, BULBS ARE BURNT OUT. 5 YEAR WITNESS TEST DUE BY NEXT ANNUAL PRESSURE INSPECTION. NOTE: CAR WAS RELEVELING AT TIME OF INSPECTION, NO FLUID PRESENT. | ROBERTV | ROBERTV | | H02 | C | 4845871 |
BEST WESTERN-LE BARON | H01 | C | 04/28/2014 | RP--5--13--TKE (Receipt #1191678) | JOHNW | JOHNW | | H01 | C | 4728500 |
BEST WESTERN-LE BARON | H02 | C | 10/07/2013 | HO2 | JOHNW | JOHNW | | H02 | C | 4617504 |
BEST WESTERN-LE BARON | H01 | C | 04/08/2013 | RP--5--12--TKE (Receipt #1121847) | JOHNW | JOHNW | | H01 | C | 4501541 |
BEST WESTERN-LE BARON | H02 | C | 10/08/2012 | RP--5--12--DOVER --MISSING FIRE SIGNS ALL FLOORS | JOHNW | JOHNW | | H02 | C | 4396596 |
BEST WESTERN-LE BARON | H01 | C | 04/04/2012 | RP--5--11--DOVER -. (Receipt #1037111) | JOHNW | JOHNW | | H01 | C | 4291778 |
BEST WESTERN-LE BARON | H02 | C | 10/10/2011 | RP--5--11--DOVER ---------------------------1973 VINTAGE---------------jack has been verified
| JOHNW | JOHNW | | H02 | C | 4219238 |
BEST WESTERN-LE BARON | H01 | C | 04/27/2011 | RP--4--10--DOVER--POST FIRE SIGNS--CAPACITY TAG (Receipt #971376) | JOHNW | JOHNW | | H01 | C | 4141131 |
BEST WESTERN-LE BARON | H02 | C | 10/25/2010 | RP 4-10--DOVER--POST CAPACITY IN CAR / PHONE INOP / MACH RM DOOR KNOB MISSING / POST FIRE SIGNS AT ALL LANDINGS | TOM | TOM | | H02 | C | 4064393 |
BEST WESTERN-LE BARON | H01 | C | 04/19/2010 | RP 4/10 DOVER. NEED CAPACITY RATING POSTED IN CAR, EMERGENCY PHONE NOT WORKING (Receipt #905266) | ERIC | ERIC | | H01 | C | 3969074 |
BEST WESTERN-LE BARON | H02 | C | 10/26/2009 | RP 10-08--DOVER | TOM | TOM | | H02 | C | 3903039 |
BEST WESTERN-LE BARON | H01 | C | 04/21/2009 | DOVER RP 10/08. NEED CALL STATION FIRE SIGNS AT 2ND AND 3RD LANDING AND NEED CAPACITY RATING IN CAR (Receipt #854979) | ERIC | ERIC | | H01 | C | 3825987 |
BEST WESTERN-LE BARON | H02 | C | 10/20/2008 | DOVER RP 10/07. DOOR SAFETY EDGE BROKEN*****3RD AND FINAL NOTICE | ERIC | ERIC | | H02 | C | 3758313 |
BEST WESTERN-LE BARON | H01 | C | 04/01/2008 | RP 10-07 --- DOVER --- SAFETY EDGE BROKEN AT BOTTOM --- DOOR NOT OPENING FULLY AND SLAMING SHUT | LES | LES | | H01 | C | 497150 |
BEST WESTERN-LE BARON | H02 | C | 10/08/2007 | RP TEST DUE --- DOVER --- CLEAN PIT --- CHECK DOOR GIBBS --- CONTROL PANEL IN CAR FALLING OFF WALL --- SINAGE MISSING ONJ 2ND AND 3 RD FLOORS [ 2ND NOTICE ] | LES | LES | | H02 | C | 497143 |
BEST WESTERN-LE BARON | H01 | C | 04/10/2007 | RP 4-06 --- DOVER --- SAFETY EDGE BROKEN OFF AT BOTTOM CONNECTION, I SHUT DOWN ELEVATOR FOR SAFETY REASONS --- SINAGE MISSING 2ND AND 3RD FLOORS | LES | LES | | H01 | C | 497135 |
BEST WESTERN-LE BARON | H02 | C | 10/06/2006 | RP TEST DUE --- SINAGE MISSING 2ND AND 3RD FLOOR | LES | LES | | H02 | C | 497126 |
BEST WESTERN-LE BARON | H01 | C | 04/05/2006 | RP 4-05 --- DOVER | LES | LES | | H01 | C | 497118 |
BEST WESTERN-LE BARON | H02 | C | 10/11/2005 | RP 4-05 --- DOVER --- CLEAN PIT | LES | LES | | H02 | C | 497111 |
BEST WESTERN-LE BARON | H01 | C | 04/12/2005 | RP 4-04 --- DOVER | LES | LES | | H01 | C | 497103 |
BEST WESTERN-LE BARON | H02 | C | 10/07/2004 | RP 4-04 --- OIL LEAKING IN PIT, CLEAN UP OIL ON FLOOR, 2ND AND FINAL NOTICE [ FIRE AND SAFETY HAZARD ] | LES | LES | | H02 | C | 497096 |
BEST WESTERN-LE BARON | H01 | C | 04/20/2004 | RP 4-03 --- DOVER --- 2ND NOTICE - EXCESSIVE OIL LEAK IN PIT, MAY NEED NEW SEAL | LES | LES | | H01 | C | 497089 |
BEST WESTERN-LE BARON | H02 | C | 10/29/2003 | RP 4-03--DOVER | TOM | TOM | | H02 | C | 497085 |
BEST WESTERN-LE BARON | H01 | C | 04/10/2003 | RP 4-02 --- EXCESSIVE OIL LEAK IN PIT, MAY NEED A NEW SEAL | LES | LES | | H01 | C | 497080 |
BEST WESTERN-LE BARON | H02 | C | 10/30/2002 | RP 4-02--DOVER | TOM | TOM | | H02 | C | 497067 |
BEST WESTERN-LE BARON | H03 | C | 10/30/2002 | | TOM | TOM | | H03 | C | 497073 |
BEST WESTERN-LE BARON | H01 | R | 04/04/2002 | RP TEST OVERDUE --- NEED SIGNS --- STOP SWITCH BROKEN --- CLEAN PIT | LES | LES | | H01 | R | 497059 |
BEST WESTERN-LE BARON | H02 | C | 10/02/2001 | RP 11-00 --- NEED SINAGE | LES | LES | | H02 | C | 497052 |
BEST WESTERN-LE BARON | H01 | C | 04/05/2001 | STOP SWITCH IN CAR IS BROKEN | LES | LES | | H01 | C | 497044 |
BEST WESTERN-LE BARON | H02 | C | 10/02/2000 | SCH. TO CHANGE SEAL NEXT WEEK | LES | LES | | H02 | C | 497036 |
BEST WESTERN-LE BARON | H01 | C | 04/24/2000 | rp 10-99 | LES | LES | | H01 | C | 496887 |
BEST WESTERN-LE BARON | H02 | P | 10/14/1999 | DOVER installed 1983 --- rp test due | LES | LES | | H02 | P | 496880 |
BEST WESTERN-LE BARON | H01 | C | 04/13/1999 | RP8-98 | RUSS | RUSS | | H01 | C | 496873 |
BEST WESTERN-LE BARON | H02 | C | 10/20/1998 | rp 8-98 | DAVEL | DAVEL | | H02 | C | 496866 |
BEST WESTERN-LE BARON | H01 | C | 04/03/1998 | rp5-97 | RUSS | RUSS | | H01 | C | 496859 |
BEST WESTERN-LE BARON | H02 | C | 10/29/1997 | | ELDON | ELDON | | H02 | C | 497027 |
BEST WESTERN-LE BARON | H01 | P | 04/02/1997 | door torque,d.london | RUSS | RUSS | | H01 | P | 497019 |
BEST WESTERN-LE BARON | H02 | P | 10/16/1996 | m.r.cleaned while present | RUSS | RUSS | | H02 | P | 497011 |
BEST WESTERN-LE BARON | H01 | R | 04/08/1996 | keep m.r.clean for the umpteenth time | RUSS | RUSS | | H01 | R | 497004 |
BEST WESTERN-LE BARON | H02 | C | 10/24/1995 | | RUSS | RUSS | | H02 | C | 496997 |
BEST WESTERN-LE BARON | H01 | C | 04/06/1995 | rp4-94 | RUSS | RUSS | | H01 | C | 496989 |
BEST WESTERN-LE BARON | H02 | C | 10/21/1994 | | RUSS | RUSS | | H02 | C | 496980 |
BEST WESTERN-LE BARON | H01 | C | 04/08/1994 | RP4-93 | RUSS | RUSS | | H01 | C | 496971 |
BEST WESTERN-LE BARON | H02 | C | 10/26/1993 | | RUSS | RUSS | | H02 | C | 496963 |
BEST WESTERN-LE BARON | H01 | P | 04/07/1993 | RP11-91 EXP. | RUSS | RUSS | | H01 | P | 496955 |
BEST WESTERN-LE BARON | H02 | C | 10/23/1992 | M.R. CLEAN | RUSS | RUSS | | H02 | C | 496947 |
BEST WESTERN-LE BARON | H01 | R | 04/01/1992 | CLEAN M.R. | RUSS | RUSS | | H01 | R | 496939 |
BEST WESTERN-LE BARON | H02 | P | 10/16/1991 | CLN MR,R.P. TEST | RUSS | RUSS | | H02 | P | 496931 |
BEST WESTERN-LE BARON | H01 | L | 04/08/1991 | UNDER CONST | RUSS | RUSS | | H01 | L | 496924 |
BEST WESTERN-LE BARON | H02 | R | 10/09/1990 | NOT DONE | RUSS | RUSS | | H02 | R | 496917 |
BEST WESTERN-LE BARON | H01 | R | 04/02/1990 | NOT DONE | RUSS | RUSS | | H01 | R | 496910 |
BEST WESTERN-LE BARON | H02 | R | 10/18/1989 | MR ST,RPT,PTLD,AL SS,PN | RUSS | RUSS | | H02 | R | 496903 |
BEST WESTERN-LE BARON | H16 | C | 04/25/1989 | INIT INSP,PERM ISSD,ORDER:MR ST,RPT,PTLD,ALSS,PN | RUSS | RUSS | | H16 | C | 496896 |