C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/28/2024 | 5YR 3/20 - ANNUAL 12/23 - INPUT SHAFT DRIP PAN IS ALMOST FULL / OIL LEAKING ON MACHINE ROOM FLOOR / BUILDING PERSONNEL TO MAINTAIN WRITTEN ELEVATOR MONTHLY FIRE FIGHTERS SERVICE TESTING AND ELEVATOR QUARTERLY EMERGENCY PHONE TESTING LOGS PER STATE OF COLORADO CONVEYANCE REGULATIONS. RBD NOTE: PHONE DIALS FRONT DESK. (Receipt #2038062) | MATTM | MATTM | | H01 | C | 8008685 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/08/2023 | H02 - 5YR 03/2020 - ANNUAL 12/2022 - SCHINDLER AND SERVICE -/ PPRBD NOTE: RESTRICTION MEANS AND OIL ADDRESSED -/ MONITOR OIL COLLECTION AT TIME OF NEXT VISIT cat 1 -- 12/23, DS | MIKEM | MIKEM | | H02 | C | 7820634 |
C.S. POLICE DEPT. LOGISTIC SVC | HE16 | C | 03/09/2023 | ELEVATOR RE-INSPECTED WITH SCHINDLER ELEVATOR ON SITE. DRIVE MACHINE INPUT SHAFT IS COMPROMISED AND NEEDS TO BE REPAIRED/REPLACED --/ CAR DOOR RESTRICTION MEANS ARE MEASURING PAST THE 4 INCH MINIMUM AND NEEDS TO BE ADJUSTED FOR MULTIPLE FLOORS --/ MISSING 4TH FLOOR BRAILLE PLATE | MIKEM | MIKEM | | HE16 | C | 7683231 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/21/2023 | 5YR 03/2020 -- ANNUAL 12/2022 -- SCHINDLER AND SERVICE --/ PIT LIGHT IS OUT --/ FLOOR 4 DESIGNATION IS MISSING ON THE DOOR JAMB --/ 2023 MAINTENANCE RECORDS ARE NOT UP TO DATE --/ OIL RESERVOIR UNDER THE MAIN DRIVE SHAFT IS FULL AND SO IS THE MACHINE FRAME AND NEEDS TO BE EMPTIED --/ CAR DOOR RESTRICTION IS OUT OF ADJUSTMENT ON MULTIPLE FLOORS AND SHALL BE REMEDIED IN 30 DAYS TO AVOID AN ELEVATOR RED TAG AND POSSIBLE SERVICE INTERRUPTION PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL ITEM/S ARE ADDRESSED (Receipt #1934496) | MIKEM | MIKEM | | H01 | C | 7666018 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/25/2022 | H02 -- 5 YEAR 3/20 -- ANNUAL 9/21 -- SCHINDLER & SERVICE -- / CHECK PREVIOUS ITEMS AT H01 | DUSTINS | DUSTINS | | H02 | C | 7495136 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/28/2022 | 5YR -- 3/20 -- CAT1 -- 9/21 -- SCHINDLER. CAR DOOR VANE RESTRICTOR DOES NOT ENGAGE WITH HOISTWAY DOOR FLAGS ON 3RD FLOOR. CAR HITCH PLATE SHACKLE NUTS NEED TO BE SECURED. EMERGENCY PHONE DOES NOT WORK WHEN CAB 110V IS DISCONNECTED. DRIVE MACHINE INPUT SHAFT SEAL CATCH PAN NEEDS TO BE EMPTIED. OIL AROUND DRIVE MACHINE NEEDS TO BE CLEANED UP. ELECTRICAL CONNECTOR TO DOOR OPERATOR DRIVE MOTOR NEEDS REPAIRED. DOOR OPERATOR CHAIN NEEDS ATTENTION. MAINTENANCE VISITS ENTRIES NEED TO BE LOGGED. NEED FIRE SERVICE AND EMERGENCY PHONE TESTING LOGS ON SITE FOR 2022. (Receipt #1846711) | ROBERTV | ROBERTV | | H01 | C | 7284058 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/31/2021 | H02 -- H02 -- 5YR -- 3/20 -- CAT1 -- 9/21 -- SCHINDLER AND SERVICE | ROBERTV | ROBERTV | | H02 | C | 7091776 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/26/2021 | 5 YEAR 3/2020 -- SCHINDLER & SERVICE -- / EMERGENCY ALARM BELL, LIGHT AND PHONE NONFUNCTIONAL ON BATTERY POWER / PROVIDE EMERGENCY PHONE QUARTERLY TEST LOG / DOOR OPERATOR MOTOR CONDUIT NEEDS REPAIRED / REPLACE MISSING BRAILLE PLATE AT 4TH FLOOR (Receipt #1753184) | RANDYB | RANDYB | | H01 | C | 6882221 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/28/2020 | H02 -- WITNESSED 3/2020 -- SCHINDLER & SERVICE | RANDYB | RANDYB | | H02 | C | 6688885 |
C.S. POLICE DEPT. LOGISTIC SVC | H06 | C | 03/17/2020 | Witnessed 5 year safety test. No code issues. | RANDYB | RANDYB | | H06 | C | 6513033 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/25/2020 | 5YR 11/15--ANNUAL 1/19--SCHINDLER--ANNUAL TRACTION SAFETY TEST OVERDUE (Receipt #1664254) | CALE | CALE | | H01 | C | 6491210 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/28/2019 | H02 -- 5YR -- 11/15 -- ANNUAL 1/19 -- SCHINDLER. ITEMS HAVE BEEN ADDRESSED | ROBERTV | ROBERTV | | H02 | C | 6316504 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/14/2019 | 5YR -- 11/15 -- ANNUAL 1/19 -- SCHINDLER. SUSPENSION ROPES ARE ROUGED AND UNDERSIZED AND NEED REPLACED. CAR MOUNTED DIRECTIONAL LANTERN IS NOT WORKING. FIRE SERVICE PHASE I AND II KEY SWITCH ESCUTCHEON LETTERING IS WORN OFF. CLEAN PIT AND CAR TOP. (Receipt #1576282 from 02/14/2019) | ROBERTV | ROBERTV | | H01 | C | 6106837 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/06/2018 | 5YR -- 11/15 -- ANNUAL 12/17 -- SCHINDLER. cat 1 done 1/19 | ROBERTV | ROBERTV | | H02 | C | 5924325 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/26/2018 | 5 YEAR 11/15, ANNUAL 12/17 SCHINDLER AND LOCKBOX. THE WEIGHT AT THE BOTTOM OF THE GOVERNOR TAIL SHEAVE IS RESTING ON THE PIT FLOOR (Receipt #1484050) | ERIC | ERIC | | H01 | C | 5774292 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/28/2017 | 5YR -- 11/15 -- ANNUAL 9/16 -- SCHINDLER. EMERGENCY PHONE NOT WORKING, GOVERNOR ROPE MUST BE REPLACED BY OCTOBER 31, 2017. | ROBERTV | ROBERTV | | H02 | C | 5608619 |
C.S. POLICE DEPT. LOGISTIC SVC | HE16 | C | 07/14/2017 | VERIFIED ROUGED AND UNDERSIZED GOVERNOR ROPE WITH LED LANCOS FROM SCHINDLER ELEVATOR. GOVERNOR ROPE NEEDS REPLACED WITHIN 90 DAYS. | ROBERTV | ROBERTV | | HE16 | C | 5564065 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/15/2017 | 5YR -- 11/15 -- ANNUAL 9/16 -- SCHINDLER. GOVERNOR ROPE IS ROUGED AND UNDERSIZED AND MUST BE REPLACED, NEED PHASE I AND II SIGNAGE, NEED CODE COMPLIANT MAINTENANCE CONTROL PROGRAM ONSITE. THESE ITEMS CONTINUE TO BE NON-ADDRESSED AND MUST NOW BE REMEDIED WITHIN 90 DAYS TO AVOID SERVICE INTERRUPTION. (Receipt #1402623) | ROBERTV | ROBERTV | | H01 | C | 5415455 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/18/2016 | 5YR -- 11/15 -- SCHINDLER. CAR TOP STATION NOT WORKING AGAIN, GOVERNOR ROPE SHOWING ROUGE, NEED PHASE I AND II SIGNAGE, NEED CODE COMPLIANT MAINTENANCE CONTROL PROGRAM ONSITE. | ROBERTV | ROBERTV | | H02 | C | 5272007 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/11/2016 | THIS VISIT SKIPPED IN LIEU OF WITNESS TEST PERFORMED 11/2015 (Receipt #1312720) | ROBERTV | ROBERTV | | H01 | C | 5133059 |
C.S. POLICE DEPT. LOGISTIC SVC | H06 | C | 11/09/2015 | WITNESSED 5 YEAR SAFETY TEST. NEED FIRE FIGHTERS PHASE 1 AND 2 INSTRUCTIONAL PLACARDS (Receipt #1298182) | ERIC | ERIC | | H06 | C | 5075219 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/31/2015 | H02 -- 5 YEAR WITNESS TESTS WILL BE PERFORMED 9/2015 | ROBERTV | ROBERTV | | H02 | C | 5025378 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/24/2015 | 5YR 8-10-SCHINDLER CK TOP OF CAR OPERATING STATION--DOOR RESTRICTORS, FIRE SIGNAGE (Receipt #1247770) | TOM | TOM | | H01 | C | 4908661 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/15/2014 | 5 YR -- 8/10 -- SCHINDLER. CAR TOP INSPECTION STATION INOPERABLE, NEEDS DOOR RESTRICTORS INSTALLED, NEED FIRE FIGHTER PHASE I AND PHASE II OPERATION PLACARDS INSTALLED, EMERGENCY PHONE ACCESS DOOR IS MISSING HANDLE | ROBERTV | ROBERTV | | H02 | C | 4797585 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/04/2014 | 5YR 8-10-SCHINDLER (Receipt #1180506) | TOM | TOM | | H01 | C | 4691496 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/20/2013 | 5YR 8-10 SCHINDLER-ITEMS FROM LAST INSPECTION HAVE NOT BEEN COMPLETED | TOM | TOM | | H02 | C | 4596800 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/26/2013 | 5 YEAR 8/10 SCHINDLER. NEED DOOR RESTRICTOR INSTALLED, NEED FIRE FIGHTERS PHASE 1 AND 2 OPERATION PLACARDS INSTALLED (Receipt #1113584) | ERIC | ERIC | | H01 | C | 4478070 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/09/2012 | 5 YR 8-10--SCHINDLER | TOM | TOM | | H02 | C | 4370289 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/03/2012 | 5 YR 8-10--SCHINDLER--PHONE IN CAR NOT WORKING (Receipt #1030269) | TOM | TOM | | H01 | C | 4276802 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/18/2011 | 5YR 8-10--SCHINDLER--PHONE IN CAR WORKING NOW | TOM | TOM | | H02 | C | 4200756 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/17/2011 | 5 YR 8-10--SCHINDLER--PHONE IN CAR NOT WORKING (Receipt #961456) | TOM | TOM | | H01 | C | 4116370 |
C.S. POLICE DEPT. LOGISTIC SVC | H06 | C | 08/16/2010 | WITNESSED 5 YEAR SAFETY TEST (Receipt #926446) | ERIC | ERIC | | H06 | C | 4025275 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/11/2010 | SCHINDLER. 5 YEAR TRACTION SAFETY TEST EXPIRED, EMERGENCY PHONE NOT WORKING | ERIC | ERIC | | H02 | C | 4023161 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/22/2010 | 5 yr 6-08--schindler (Receipt #898171) | TOM | TOM | | H01 | C | 3948264 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 09/01/2009 | 5 YR 6-08 SCHINDLER | TOM | TOM | | H02 | C | 3879099 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/28/2009 | 5 YR 6-08--SCHINDLER (Receipt #848323) | TOM | TOM | | H01 | C | 3807450 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/28/2008 | per tom e. see images. 5yr 6/08 | JOHNW | JOHNW | | H02 | C | 3732813 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/29/2008 | 5YR--4--03--SCHINDLER--PHONE AND ALARM INOP | JOHNW | JOHNW | | H01 | C | 747723 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/27/2007 | 5 YR 4-03--SCHINDLER | TOM | TOM | | H02 | C | 747716 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/28/2007 | 5 YR 4-03--SCHINDLER | TOM | TOM | | H01 | C | 747708 |
C.S. POLICE DEPT. LOGISTIC SVC | H02 | C | 08/29/2006 | 5 YR 4-03--SCHINDLER | TOM | TOM | | H02 | C | 747700 |
C.S. POLICE DEPT. LOGISTIC SVC | H01 | C | 02/27/2006 | 5 YR 4-03--SCHINDLER--CK ALARM NEXT INSP | TOM | TOM | | H01 | C | 747692 |
CTY OF C/S - FACILITIES MAINT | H02 | C | 08/31/2005 | 5 YR 4-03--SCHINDLER | TOM | TOM | | H02 | C | 747640 |
COLO SPRINGS UTILITIES | H01 | C | 02/25/2005 | 5 YR 4-03--SCHINDLER | TOM | TOM | | H01 | C | 747682 |
COLO SPRINGS UTILITIES | H02 | C | 08/31/2004 | 5 YR 4-03-SCHINDLER--FOX THERIAULT MAINTENANCE SUPERVISOR 444-7973 | JOHNW | JOHNW | | H02 | C | 747675 |
COLO SPRINGS UTILITIES | H01 | C | 02/02/2004 | 5 YR 4-03--SCHINDLER | TOM | TOM | | H01 | C | 747667 |
COLO SPRINGS UTILITIES | H02 | C | 08/18/2003 | 5 YR 10-98--SCHINDLER | TOM | TOM | | H02 | C | 747660 |
COLO SPRINGS UTILITIES | H01 | C | 02/06/2003 | 5 YR 10-98--SCHINDLER | TOM | TOM | | H01 | C | 747653 |
COLO SPRINGS UTILITIES | H02 | C | 08/15/2002 | 5 YR 10-01--SCHINDLER | TOM | TOM | | H02 | C | 747645 |
CTY OF C/S - FACILITIES MAINT | H01 | C | 02/08/2002 | 5 YR 1-01--SCHINDLER | TOM | TOM | | H01 | C | 747634 |
CTY OF C/S - FACILITIES MAINT | H02 | C | 08/27/2001 | 5 YR 1-01--SCHINDLER | TOM | TOM | | H02 | C | 747628 |
CTY OF C/S - FACILITIES MAINT | H01 | C | 02/13/2001 | 5 YR--10-98--SCHINDLER (ED) | TOM | TOM | | H01 | C | 747622 |
CTY OF C/S - FACILITIES MAINT | H02 | C | 08/04/2000 | RP 10-99--SCHINDLER (ED) | TOM | TOM | | H02 | C | 747616 |
CTY OF C/S - FACILITIES MAINT | H01 | C | 02/03/2000 | SCHINDLER 5yr 10-98 | LES | LES | | H01 | C | 747509 |
CTY OF C/S - FACILITIES MAINT | H02 | C | 08/05/1999 | | RUSS | RUSS | | H02 | C | 747608 |
CTY OF C/S - FACILITIES MAINT | H01 | C | 02/08/1999 | 5YR 10-98 SEE JIM YOUNIE | RUSS | RUSS | | H01 | C | 747600 |
CTY OF C/S - FACILITIES MAINT | H02 | C | 08/04/1998 | | RUSS | RUSS | | H02 | C | 747501 |
CTY OF C/S - FACILITIES MAINT | H01 | C | 02/02/1998 | 5 yr due | DAVEL | DAVEL | | H01 | C | 747493 |
CTY OF C/S - FACILITIES MAINT | H02 | C | 08/28/1997 | | RUSS | RUSS | | H02 | C | 747592 |
CTY OF C/S - FACILITIES MAINT | H01 | P | 02/04/1997 | 5yr 2-93,phn,door torque | RUSS | RUSS | | H01 | P | 747584 |
CTY OF C/S - FACILITIES MAINT | H02 | C | 08/28/1996 | | RUSS | RUSS | | H02 | C | 747576 |
CTY OF C/S - FACILITIES MAINT | H01 | C | 02/06/1996 | | RUSS | RUSS | | H01 | C | 747568 |
CTY OF C/S - FACILITIES MAINT | H02 | C | 08/24/1995 | | RUSS | RUSS | | H02 | C | 747558 |
CTY OF C/S - FACILITIES MAINT | H01 | C | 02/06/1995 | | RUSS | RUSS | | H01 | C | 747550 |
CTY OF C/S - FACILITIES MAINT | H02 | C | 08/30/1994 | | RUSS | RUSS | | H02 | C | 747541 |
CTY OF C/S - FACILITIES MAINT | H01 | P | 02/03/1994 | PHN | RUSS | RUSS | | H01 | P | 747533 |
CTY OF C/S - FACILITIES MAINT | H02 | P | 08/25/1993 | PHN NOT WKING | RUSS | RUSS | | H02 | P | 747525 |
CTY OF C/S - FACILITIES MAINT | H01 | C | 02/01/1993 | INIT INSP, PMT ISSD, OK EXCEPT FOR PHONE | RUSS | RUSS | | H01 | C | 747518 |