SAUNDERS CONSTRUCTION, INC. | B= | C | 12/20/1995 | OK FOR C.O. | BILLC | BILLC | | B= | C | 1031819 |
SAUNDERS CONSTRUCTION, INC. | B= | R | 12/19/1995 | CANCELED BY RBD | JOE | JOE | | B= | R | 1031811 |
SAUNDERS CONSTRUCTION, INC. | B= | R | 12/15/1995 | canceled by bld | JOE | JOE | | B= | R | 1031805 |
SAUNDERS CONSTRUCTION, INC. | B= | P | 11/08/1995 | REAR CORRIDOR FIRE WALL AND CEILING, TENT ALL LIGHTS IN RATED CEILING, HOLES IN LIGHT TENTS, HOLES IN BAKERY CEILING, SPRINKLER ESCUSIONS IN BAKERY-PHARMACY,ELECT RM-MNY RM-AIR HNDLR RM, GATE ACROSS MEZ DOOR, LOW HEADRM SOGN AT MEZ STAIRS, ENCLOSE COND. LINE, FIT TILE IN PHARMACY, BUILD DROP AROUND SPRINKLER HEADS, FINISH CEILING IN VARIETY OF AREAS, SEAL HOLE ABOVE DOOR AT MNY RM, SEAL HOLE UNDER PANEL IN MNY RM, SMK SEALS AIR HNDLR RM, FULL ROOF INSP, SEAL WIRE HOLE IN TUNN | BILLC | BILLC | | B= | P | 1031798 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 11/07/1995 | rear cooler walls ok to rock--meat area walls and vent shafts ok--did walk thru for general list for final | BILLC | BILLC | | BFR | P | 1031791 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 11/06/1995 | walls around meat dept cooler ok--need to return today to check chases and beam protection | BILLC | BILLC | | BFR | P | 1031783 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 11/05/1995 | SPENT 14 HOURS--11 HOURS THEN RETURNED FOR 3 MORE AT NIGHT--INTERIOR PARTITION WALLS AND CURTAIN WALLS OK TO ROCK EXCEPT MEAT DEPT AREA--NEED TO SEE THESE 1ST STOP MONDAY AM--DISCUSSED ROOF PROBLEMS WITH BUILDER--CHECK STAIRS, SIGNS, RAILS, ETC AT FINAL | BILLC | BILLC | | BFR | P | 1031775 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 10/30/1995 | Drops in line L-M, & At line 7 | JOHNP | JOHNP | | BFR | P | 1031768 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 10/24/1995 | drops in existing store | BILLC | BILLC | | BFR | P | 1031760 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 10/06/1995 | GREASE DUCT SHAFT ENCLOSURE | BILLC | BILLC | | BFR | P | 1031752 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 10/04/1995 | | JOE | JOE | | BFR | P | 1031744 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 09/27/1995 | SHOULD HAVE BEEN A B16 | JOE | JOE | | BFR | P | 1031736 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 09/20/1995 | | JOE | JOE | | BFR | P | 1031727 |
HOMEOWNER | BFN | C | 09/20/1995 | DRILL LOG ON FILE | JOE | JOE | | BFN | C | 1031657 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 09/12/1995 | see initials on plan--interior wall framing | BILLC | BILLC | | BFR | P | 1031720 |
SAUNDERS CONSTRUCTION, INC. | BFR | P | 08/31/1995 | west-front wall only-OK | BILLC | BILLC | | BFR | P | 1031712 |
SAUNDERS CONSTRUCTION, INC. | BBB | P | 08/29/1995 | B7 TO B4 AND B1-2-3-4 | BILLC | BILLC | | BBB | P | 1031704 |
SAUNDERS CONSTRUCTION, INC. | BBB | P | 08/25/1995 | east wall south half top bbb | JOE | JOE | | BBB | P | 1031696 |
SAUNDERS CONSTRUCTION, INC. | BBB | P | 08/17/1995 | 4 LN B.7-D.7 & BLN 3-2,INSTALL REBAR & EMBEDS AS SHOWN ON STRUCTURAL PLNS | MIKE | MIKE | | BBB | P | 1031689 |
SAUNDERS CONSTRUCTION, INC. | BBB | P | 08/11/1995 | NORTH WALL & SOUTH HALF OF EAST WALL | JOE | JOE | | BBB | P | 1031681 |
SAUNDERS CONSTRUCTION, INC. | BFN | P | 07/25/1995 | FRONT & NORTH WALLS----NEED ENG LETTER ON CASSIONS | JOE | JOE | | BFN | P | 1031673 |
SAUNDERS CONSTRUCTION, INC. | BFN | P | 07/21/1995 | BACK WALL | JOE | JOE | | BFN | P | 1031666 |
WAYNE'S ELECTRIC INC | E= | C | 12/15/1995 | need a separate permit for the ouside sign | TERRY | TERRY | | E= | C | 1032245 |
WAYNE'S ELECTRIC INC | E= | R | 12/14/1995 | need to close up j-boxes in ceiling in several places, need to transfer services in other two units to perminant meters | TERRY | TERRY | | E= | R | 1032238 |
WAYNE'S ELECTRIC INC | E= | P | 11/08/1995 | TCO OK, NEED TO INSPECT WHOLE BUILDING | TERRY | TERRY | | E= | P | 1032230 |
WAYNE'S ELECTRIC INC | ER | P | 11/07/1995 | EARLY A.M. INSPECTION REQUREST FOR CEILING | TERRY | TERRY | | ER | P | 1032222 |
WAYNE'S ELECTRIC INC | ER | P | 11/06/1995 | some ceiling in pharmacy | TERRY | TERRY | | ER | P | 1032208 |
WAYNE'S ELECTRIC INC | ER | R | 11/06/1995 | ceiling still has too much temp wiring in it | TERRY | TERRY | | ER | R | 1032215 |
WAYNE'S ELECTRIC INC | ER | P | 11/05/1995 | STAYED FROM 2:00 A.M. TO 1:00 P.M. AND CAME BACK FRO AN ADDITIONAL INSPECTION AT 7:00P.M. ON UNDER FLOOR AND VARIOUS WALLS IN THE OLD REMODLED SECTION | TERRY | TERRY | | ER | P | 1032202 |
WAYNE'S ELECTRIC INC | ER | P | 10/31/1995 | consultation for weekend inspection | TERRY | TERRY | | ER | P | 1032195 |
WAYNE'S ELECTRIC INC | ER | P | 10/24/1995 | new ceiling, deli in old area, bottle room | TERRY | TERRY | | ER | P | 1032188 |
WAYNE'S ELECTRIC INC | ES | C | 10/18/1995 | called in to Whayne Olson, ok to energize, 1200a 4w/ug, ct metered Whaynes Electric,1750A (1750B, 1768, 1772 ARE DIRECTMETERED) | TERRY | TERRY | | ES | C | 1032180 |
WAYNE'S ELECTRIC INC | ES | R | 10/16/1995 | don't like the way the CT'S ARE INSTALLED | TERRY | TERRY | | ES | R | 1032173 |
WAYNE'S ELECTRIC INC | ES | R | 10/13/1995 | not done yet | TERRY | TERRY | | ES | R | 1032166 |
WAYNE'S ELECTRIC INC | ES | R | 10/12/1995 | | TERRY | TERRY | | ES | R | 1032157 |
WAYNE'S ELECTRIC INC | ER | P | 10/03/1995 | demo part of existing ceiling | TERRY | TERRY | | ER | P | 1032151 |
WAYNE'S ELECTRIC INC | EUG | P | 09/27/1995 | 1 HOUR OT FOR UNDERGROUND INSPECTION | TERRY | TERRY | | EUG | P | 1032140 |
WAYNE'S ELECTRIC INC | ER | P | 09/26/1995 | 10TH INSPECTION AT 1 HOUR CHARGE | TERRY | TERRY | | ER | P | 1032136 |
WAYNE'S ELECTRIC INC | EUG | P | 09/25/1995 | 9TH INSPECTION AT 1 HOUR OT | TERRY | TERRY | | EUG | P | 1032124 |
WAYNE'S ELECTRIC INC | ER | P | 09/22/1995 | PRODUCE WALLS OK | TERRY | TERRY | | ER | P | 1032116 |
WAYNE'S ELECTRIC INC | EUG | P | 09/21/1995 | 7TH INSPECTION PER AGREEMENT OF 1 HOUR PAY OT | TERRY | TERRY | | EUG | P | 1032109 |
WAYNE'S ELECTRIC INC | EUG | P | 09/20/1995 | 6TH INSPECTION AT 1 HOUR, DONE AT 6:00 | TERRY | TERRY | | EUG | P | 1032102 |
WAYNE'S ELECTRIC INC | EUG | P | 09/19/1995 | 4TH INSPECTION AT 1 HOUR CHARGE | TERRY | TERRY | | EUG | P | 1032095 |
WAYNE'S ELECTRIC INC | EUG | P | 09/18/1995 | 4TH INSPECTION AT 1 HOUR CHARGE | TERRY | TERRY | | EUG | P | 1032088 |
WAYNE'S ELECTRIC INC | EUG | P | 09/15/1995 | 3RD INSPECTION AT 1HOUR OT | TERRY | TERRY | | EUG | P | 1032080 |
WAYNE'S ELECTRIC INC | EUG | P | 09/14/1995 | 2ND INSPECTION, 1 HOUR OT | TERRY | TERRY | | EUG | P | 1032073 |
WAYNE'S ELECTRIC INC | EUG | P | 09/13/1995 | this is the first A.M. inspection, agreed to pay 1 hour ot for each inspection | TERRY | TERRY | | EUG | P | 1032065 |
WAYNE'S ELECTRIC INC | ER | P | 09/12/1995 | meat department and deli walls | TERRY | TERRY | | ER | P | 1032057 |
WAYNE'S ELECTRIC INC | ER | P | 09/11/1995 | stub walls, bathrooms, floral and video walls | TERRY | TERRY | | ER | P | 1032049 |
WAYNE'S ELECTRIC INC | ESL | P | 08/15/1995 | east side slab | TERRY | TERRY | | ESL | P | 1032041 |
WAYNE'S ELECTRIC INC | ESL | P | 08/11/1995 | west side lower slab | TERRY | TERRY | | ESL | P | 1032033 |
WAYNE'S ELECTRIC INC | EUG | P | 07/28/1995 | under ground from transformer to service was over 4' deep, told that it was not ny inspection | TERRY | TERRY | | EUG | P | 1032027 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 12/13/1995 | | JOHNW | JOHNW | | H= | C | 1031931 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 11/21/1995 | need to check on tube heaters and their venting req. | JOHNW | JOHNW | | H= | P | 1031917 |
HEATING & PLUMBING ENGINEERS, INC | HD | C | 11/21/1995 | | JOHNW | JOHNW | | HD | C | 1031925 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 11/08/1995 | | JOHNW | JOHNW | | H= | P | 1031895 |
HEATING & PLUMBING ENGINEERS, INC | HI | C | 11/08/1995 | | JOHNW | JOHNW | | HI | C | 1031901 |
HEATING & PLUMBING ENGINEERS, INC | HV | C | 11/08/1995 | | JOHNW | JOHNW | | HV | C | 1031910 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 11/06/1995 | under ground and bagle hood ok | JOHNW | JOHNW | | HD | P | 1031887 |
HEATING & PLUMBING ENGINEERS, INC | HV | P | 11/01/1995 | fire dampers over cash registers ok | JOHNW | JOHNW | | HV | P | 1031881 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 10/25/1995 | RADIANT DAMPERS IN NEW AREA OK / FIRE DAMPERS IN AREA ABOVE CASH REGISTERS NOT INSTALLED PROPERLY/GREASE DUCT AND SHAFTS OK | JOHNW | JOHNW | | HD | P | 1031873 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 10/03/1995 | | JOHNW | JOHNW | | HD | P | 1031865 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 10/02/1995 | 80% ON H.V.A.C. AND GREASE DUCT ABOVE CEILING | JOHNW | JOHNW | | HD | P | 1031857 |
HEATING & PLUMBING ENGINEERS, INC | HI | P | 09/19/1995 | saw test, and roof section, need final when tied in | MARTY | MARTY | | HI | P | 1031849 |
HEATING & PLUMBING ENGINEERS, INC | HI | P | 09/18/1995 | for 4 new R.T.U.'S NOT ON KING SOOPERS. | JOHNW | JOHNW | | HI | P | 1031842 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 09/18/1995 | gas lines for 4 new R.T.U'S/ not on KING SOOPERS | JOHNW | JOHNW | | H= | P | 1031834 |
HEATING & PLUMBING ENGINEERS, INC | HI | P | 07/28/1995 | 4 new lines on north side of complex to R.T.U.'S | JOHNW | JOHNW | | HI | P | 1031826 |
HEATING & PLUMBING ENGINEERS, INC | P= | C | 12/14/1995 | | PAT | PAT | | P= | C | 1032005 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 09/19/1995 | | MARTY | MARTY | | PTO | P | 1031998 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 09/11/1995 | bathrooms, dwv and water, north wall dwv sheet rock walls and do water test north side | MARTY | MARTY | | PTO | P | 1031991 |
HEATING & PLUMBING ENGINEERS, INC | PGI | C | 09/04/1995 | already ok'ed by the city inspector also | BILL | BILL | | PGI | C | 1031984 |
HEATING & PLUMBING ENGINEERS, INC | PB | P | 08/16/1995 | H20, UNDERGROUND IN THE ADDITION COMPLETE EXCEPT FOR IN THE TUNNEL AND UNDERGROUND IN THE EXISTING BUILDING, SEE THE PLUMBING DRAWINGS. | ALAN | ALAN | | PB | P | 1031976 |
HEATING & PLUMBING ENGINEERS, INC | PB | P | 08/11/1995 | N-E corner, D.7 thru colum 2 sanitary & grease | JIMV | JIMV | | PB | P | 1031968 |
HEATING & PLUMBING ENGINEERS, INC | PB | P | 08/08/1995 | SEE THE PLUMBERS PLANS | BILL | BILL | | PB | P | 1031960 |
HEATING & PLUMBING ENGINEERS, INC | PB | P | 08/07/1995 | floor drains from D.7 to colum line 1////see plans | BILL | BILL | | PB | P | 1031952 |
HEATING & PLUMBING ENGINEERS, INC | PB | P | 08/04/1995 | sanitary on the west wall from the 2" riser to the existing wall of king soopers approximately 30 feet out from the west wall all ok | BILL | BILL | | PB | P | 1031946 |
HEATING & PLUMBING ENGINEERS, INC | PB | P | 07/28/1995 | N. side sewer & grease ok | JIMV | JIMV | | PB | P | 1031938 |