COLORADO STRUCTURES INC | B= | C | 09/03/1996 | RECEIVED ENGINEERING FROM TERRACON REGARDING DOCK WALL REPAIR | BLAKE | BLAKE | | B= | C | 1053067 |
COLORADO STRUCTURES INC | B= | P | 08/19/1996 | TCO OK 30 DAYS/NEED ONE HANDRAIL AT NE EXTERIOR STAIRS | BLAKE | BLAKE | | B= | P | 1053051 |
COLORADO STRUCTURES INC | BFR | C | 08/19/1996 | | MIKE | MIKE | | BFR | C | 1053059 |
COLORADO STRUCTURES INC | BFR | P | 08/16/1996 | SEAL 1HR WALL @ TBO SERVICE AREA NOT COMPLETE | MIKE | MIKE | | BFR | P | 1053040 |
COLORADO STRUCTURES INC | BFR | P | 08/12/1996 | SEAL FIREWALL @ TBO SERVICE AREA | MIKE | MIKE | | BFR | P | 1053030 |
COLORADO STRUCTURES INC | BFR | R | 08/07/1996 | SEAL CORRIDOR FIREWALLS STILL NOT CORRECTED | MIKE | MIKE | | BFR | R | 1053022 |
COLORADO STRUCTURES INC | BFR | R | 07/18/1996 | CORRIDOR PROBLEMS NOT CORRECTED | MIKE | MIKE | | BFR | R | 1053014 |
COLORADO STRUCTURES INC | BFR | P | 07/11/1996 | COMPLETE CORRIDOR FIREWALL | MIKE | MIKE | | BFR | P | 1053007 |
COLORADO STRUCTURES INC | BFR | P | 07/03/1996 | STILL NEED STRUCTURAL ANGLES @ CORRIDOR WALLS,COMPLETE SHEETROCK @ CORRIDORS THRU INTERIOR WALLS | MIKE | MIKE | | BFR | P | 1052999 |
COLORADO STRUCTURES INC | BFR | T | 06/26/1996 | PAID (REC#: 240639)PROBLEMS NOT CORRECTED | MIKE | MIKE | | BFR | T | 1052991 |
COLORADO STRUCTURES INC | BFR | P | 06/21/1996 | COMPLETE SEALING CORRIDOR WALL PENETRATIONS,RATED WALL CONSTRUCTION STILL NOT PER DESIGN | MIKE | MIKE | | BFR | P | 1052984 |
COLORADO STRUCTURES INC | BFR | P | 06/18/1996 | REVIEWED FIRE CAULK PRODUCT DATA SHEET & INSTALLATION PROCEEDURE | MIKE | MIKE | | BFR | P | 1052978 |
COLORADO STRUCTURES INC | BFR | R | 06/13/1996 | TUBE STEEL NOT INSTALLED IN CORRIDOR WALLS AS SHOWN IN DETAIL 11/A6,SEAL ALL PENETRATIONS IN CORRIDOR WALLS | MIKE | MIKE | | BFR | R | 1052971 |
COLORADO STRUCTURES INC | BFR | R | 06/05/1996 | NOT READY | MIKE | MIKE | | BFR | R | 1052963 |
COLORADO STRUCTURES INC | BFR | P | 06/04/1996 | TBO AREA - SEAL FIREWALL PENETRATIONS,FRT OFFICE AREA - SEAL CORRIDOR WALL PENETRATIONS | MIKE | MIKE | | BFR | P | 1052955 |
COLORADO STRUCTURES INC | BFR | P | 05/17/1996 | Front entry, Offices, & Retrooms after Plbg & Elect rgh insp | JOHNP | JOHNP | | BFR | P | 1052947 |
COLORADO STRUCTURES INC | BFR | P | 05/09/1996 | CORRIDOR #144 - INSTALL TUBE STEEL ABOVE SLIP TRACK PER DETAIL 11/A6 | MIKE | MIKE | | BFR | P | 1052936 |
COLORADO STRUCTURES INC | BFR | P | 04/26/1996 | SEE SHEET A-1/FRONT FASCIA OK TO ROCK PEND ANY ELEC OR MECH | BLAKE | BLAKE | | BFR | P | 1052930 |
COLORADO STRUCTURES INC | BFR | P | 04/22/1996 | EAST MAIN CELL WALL,EAST AND NORTH CORRIDORS,EAST OFFICES,WEST AND NORTH FACIAS INCOMPLT,HANG WALL LOADS TO LID,PTO REQD | RICH | RICH | | BFR | P | 1052924 |
COLORADO STRUCTURES INC | BFN | C | 04/22/1996 | RECIEVED ENGINEERS LETTER DATED 4/17/96,TERRACON CONSULTANTS,STAMPED BY SCOTT NEELY,APPRVL PER ROLF PHILLIPSEN | RICH | RICH | | BFN | C | 1052915 |
COLORADO STRUCTURES INC | BFR | R | 04/17/1996 | Need clear BFT & BFN | JOHNP | JOHNP | | BFR | R | 1052908 |
COLORADO STRUCTURES INC | BFR | R | 04/09/1996 | NEED CLEAR FTG & FDTN INSPECTION | MIKE | MIKE | | BFR | R | 1052900 |
COLORADO STRUCTURES INC | BFT | P | 12/05/1995 | | JOE | JOE | | BFT | P | 1052892 |
L. G. ELECTRIC | E= | C | 08/19/1996 | | TERRY | TERRY | | E= | C | 1053515 |
L. G. ELECTRIC | E= | R | 08/15/1996 | conduit to support properly, GFI backwards, need to support amin sub feed conduits and main distribution center | TERRY | TERRY | | E= | R | 1053507 |
L. G. ELECTRIC | ER | P | 07/19/1996 | still need several ceilings looked at | TERRY | TERRY | | ER | P | 1053500 |
L. G. ELECTRIC | E= | P | 07/19/1996 | ok to move in merchandise | TERRY | TERRY | | E= | P | 1053492 |
L. G. ELECTRIC | ER | P | 06/26/1996 | ceilings in several area's east side and west side | TERRY | TERRY | | ER | P | 1053482 |
L. G. ELECTRIC | ER | P | 06/12/1996 | pharmacy walls | TERRY | TERRY | | ER | P | 1053474 |
L. G. ELECTRIC | ER | P | 06/03/1996 | south and sw walls | TERRY | TERRY | | ER | P | 1053466 |
L. G. ELECTRIC | ER | P | 05/29/1996 | conduits are Able to float | TERRY | TERRY | | ER | P | 1053458 |
L. G. ELECTRIC | ER | P | 05/23/1996 | photo lab partial on the east side walls, hair care walls | TERRY | TERRY | | ER | P | 1053442 |
L. G. ELECTRIC | ES | C | 05/23/1996 | 400a 4w/ug R G Electric, called in ok to energize | TERRY | TERRY | | ES | C | 1053450 |
L. G. ELECTRIC | ES | R | 05/21/1996 | need information on the GFI protection and testing for the 2000A mains | TERRY | TERRY | | ES | R | 1053434 |
L. G. ELECTRIC | ER | P | 05/21/1996 | north west walls ok | TERRY | TERRY | | ER | P | 1053425 |
L. G. ELECTRIC | ER | P | 05/09/1996 | refrigeration units partial and back east walls | TERRY | TERRY | | ER | P | 1053417 |
L. G. ELECTRIC | ER | P | 05/06/1996 | nw walls | TERRY | TERRY | | ER | P | 1053409 |
L. G. ELECTRIC | ER | P | 04/25/1996 | strapping ok on east side walls | TERRY | TERRY | | ER | P | 1053401 |
L. G. ELECTRIC | ER | P | 04/24/1996 | layaway, deli, bakery, talked to electrician Lee that more strapping is needed and will be rejected next time | TERRY | TERRY | | ER | P | 1053393 |
L. G. ELECTRIC | ER | P | 04/05/1996 | McD's, deli, office walls, watch strapping and ko closures in boxes | TERRY | TERRY | | ER | P | 1053386 |
L. G. ELECTRIC | EUG | P | 03/22/1996 | | HAROLD | HAROLD | | EUG | P | 1053377 |
L. G. ELECTRIC | ER | P | 01/10/1996 | underground connetions between electrical rooms | TERRY | TERRY | | ER | P | 1053370 |
L. G. ELECTRIC | ER | P | 12/05/1995 | upher ground connections | TERRY | TERRY | | ER | P | 1053363 |
FRONTIER MECHANICAL INC. | H= | C | 08/19/1996 | | JOHNW | JOHNW | | H= | C | 1053356 |
BOCHNAK MECHANICAL, INC. | H= | C | 08/19/1996 | | JOHNW | JOHNW | | H= | C | 1053102 |
FRONTIER MECHANICAL INC. | H= | P | 08/06/1996 | finish equipment in bakery area/need more support on gas line in tire storage area | JOHNW | JOHNW | | H= | P | 1053328 |
FRONTIER MECHANICAL INC. | HV | C | 08/06/1996 | | JOHNW | JOHNW | | HV | C | 1053350 |
FRONTIER MECHANICAL INC. | HD | C | 08/06/1996 | | JOHNW | JOHNW | | HD | C | 1053334 |
FRONTIER MECHANICAL INC. | HI | C | 08/06/1996 | | JOHNW | JOHNW | | HI | C | 1053341 |
FRONTIER MECHANICAL INC. | HD | P | 07/02/1996 | INTERIOR GREASE DUCT SHAFTS (DELI, BAKERY AND MICKY D'S)... | BOBM | BOBM | | HD | P | 1053319 |
BOCHNAK MECHANICAL, INC. | HI | P | 07/02/1996 | all but the loading dock on the east side of the building ok,,welder stamp is | BILL | BILL | | HI | P | 1053091 |
FRONTIER MECHANICAL INC. | HD | P | 06/21/1996 | grease duct ok will check shafts later/duct in hard lid areas ok/radiant heaters in garage area complete/bvent must extend thru ceiling on unit heaters | JOHNW | JOHNW | | HD | P | 1053315 |
FRONTIER MECHANICAL INC. | HD | P | 06/18/1996 | rough duct on McDonalds grease duct | JOHNW | JOHNW | | HD | P | 1053308 |
FRONTIER MECHANICAL INC. | HD | P | 06/10/1996 | duct in N/W entry and restrooms in back ok | JOHNW | JOHNW | | HD | P | 1053302 |
FRONTIER MECHANICAL INC. | HD | P | 05/31/1996 | all tenent spaces in west end of except for bank and restrooms | JOHNW | JOHNW | | HD | P | 1053289 |
FRONTIER MECHANICAL INC. | HV | P | 05/31/1996 | rough vent thru roof / bvent must extend thru drop ceiling for waterheater the space is unconditioned | JOHNW | JOHNW | | HV | P | 1053296 |
BOCHNAK MECHANICAL, INC. | HI | P | 05/29/1996 | tbo, loading dock, Mc donald's, entry, are not completed yet and need recalled | BILL | BILL | | HI | P | 1053083 |
BOCHNAK MECHANICAL, INC. | HI | R | 05/24/1996 | TEST DOWN | JOHNW | JOHNW | | HI | R | 1053075 |
FRONTIER MECHANICAL INC. | HD | P | 05/24/1996 | OFFICE AERA ROUGH COMPLETE | JOHNW | JOHNW | | HD | P | 1053281 |
FRONTIER MECHANICAL INC. | HD | P | 04/25/1996 | trunkline above coolers ok except for drops in wall that have combustibles in return air plenum | JOHNW | JOHNW | | HD | P | 1053275 |
FRONTIER MECHANICAL INC. | HD | P | 04/08/1996 | fire dampers in stud walls complete | JOHNW | JOHNW | | HD | P | 1053269 |
BOCHNAK MECHANICAL, INC. | P= | C | 08/20/1996 | ok for plbg co | MARTY | MARTY | | P= | C | 1053262 |
BOCHNAK MECHANICAL, INC. | P= | T | 08/16/1996 | PAID (REC#: 244557)no b/flo preventer on 3 comp sink, no p trap on l/tub inoil pit, no gate valves on sumps, seal off sump holes, sink in hair care not done,secure l/tub in hair care | MARTY | MARTY | | P= | T | 1053255 |
BOCHNAK MECHANICAL, INC. | P= | P | 08/14/1996 | 3 compartment sink in McDonalds needs back flow prevention, Haircare was not finished, fixtures in oil change pit need P-traps, check water dispenser in front of rest rooms | KYE | KYE | | P= | P | 1053249 |
BOCHNAK MECHANICAL, INC. | P= | P | 07/26/1996 | all the store is ok but the bacement of the TBO and McDonalds//ok to stock the shelves if the building inspector says ok | BILL | BILL | | P= | P | 1053241 |
BOCHNAK MECHANICAL, INC. | P= | P | 07/18/1996 | front bathrooms only! need to look over the entire building again,,to many items to list | BILL | BILL | | P= | P | 1053233 |
BOCHNAK MECHANICAL, INC. | PB | P | 05/28/1996 | tbo ok | BILL | BILL | | PB | P | 1053226 |
BOCHNAK MECHANICAL, INC. | PTO | P | 05/20/1996 | large bathrooms on the west wall ok | BILL | BILL | | PTO | P | 1053217 |
BOCHNAK MECHANICAL, INC. | PTO | P | 05/15/1996 | big baths on the east side only//construction trailor locked at 1215 hours and could not sign the card | BILL | BILL | | PTO | P | 1053210 |
BOCHNAK MECHANICAL, INC. | PB | P | 05/06/1996 | tbo area ok but need to see the interior piping of the sand trap when ready,,ok to cover tie in and up to the trap,, recall when ready | BILL | BILL | | PB | P | 1053204 |
BOCHNAK MECHANICAL, INC. | PTO | P | 04/22/1996 | east wall ok//north wall up to the northwest corner ok | BILL | BILL | | PTO | P | 1053197 |
BOCHNAK MECHANICAL, INC. | PB | P | 04/18/1996 | need city approval before you bury | BILL | BILL | | PB | P | 1053191 |
BOCHNAK MECHANICAL, INC. | PB | R | 03/05/1996 | 0# test at 930 hours//small base in the shipping area | BILL | BILL | | PB | R | 1053183 |
BOCHNAK MECHANICAL, INC. | PB | P | 02/22/1996 | all but the 4" trap arm going to the recieving area on the east grease lines ok to cover | BILL | BILL | | PB | P | 1053175 |
BOCHNAK MECHANICAL, INC. | PB | P | 01/30/1996 | inside grease lines on the east side complete and finishes the grease lines on the inside of the building but no outside yet or sand oil yet | BILL | BILL | | PB | P | 1053169 |
BOCHNAK MECHANICAL, INC. | PB | R | 01/29/1996 | not ready,,,pipe not bedded in/ low test 3 1/2# | BILL | BILL | | PB | R | 1053162 |
BOCHNAK MECHANICAL, INC. | PB | P | 01/23/1996 | the grease lines from the stub out to the east grease trap to the west end and all the branches ok to cover but no lines to the east of the same stub yet | BILL | BILL | | PB | P | 1053155 |
BOCHNAK MECHANICAL, INC. | PB | P | 01/16/1996 | tbo ok ,, all the floor drains from e line to west wall ok//big bathrooms on the east side and the janitor room ok to cover | BILL | BILL | | PB | P | 1053149 |
BOCHNAK MECHANICAL, INC. | PB | P | 01/12/1996 | deep trunks from the tbo combo to grid line h-7 ok to cover | BILL | BILL | | PB | P | 1053143 |
BOCHNAK MECHANICAL, INC. | PB | P | 01/11/1996 | GREASE LINE TO THE WEST END OF THE FRONT OF THE STORE BUT NONE OF THE VENT LINES OR OUTSIDE GREASE LINES ON THE WEST GREASE SYSTEM, ALSO THE PREP AREA OF THE GROCERY DEPARTMENT IN THE NORTH WEST AREA ON THE SANITARY OK// | BILL | BILL | | PB | P | 1053137 |
BOCHNAK MECHANICAL, INC. | PB | P | 01/09/1996 | VISION CARE,HAIR CARE AND FRONT BATHROOMS OK ALL FROM THE END OF LINE C/O AT THE SOUTH TO THE STUB AT THE NORTH END, EXCEPT THE FLOOR DRAIN IN FRONT OF THE VISION CARE CENTER NOT RUN OUT BECAUSE OF CONCRETE ALREADY POURED, NEEDS SAW CUT AND RECALLED | BILL | BILL | | PB | P | 1053132 |
BOCHNAK MECHANICAL, INC. | PB | P | 12/29/1995 | deep trunks on the north end of store,sanitary, from the west footer to the (f)coloum with all the combos but no runouts,,,and the tbo bathroom on the south end from the deep trunk to the south footer and under but no sand oil or trough drains yet | BILL | BILL | | PB | P | 1053125 |
BOCHNAK MECHANICAL, INC. | PB | R | 12/22/1995 | not done no test | MARTY | MARTY | | PB | R | 1053109 |
BOCHNAK MECHANICAL, INC. | PB | P | 12/22/1995 | DEEP TRUNKS FROM THE EXIT AT THE SOUTH WEST CORNER OF THE BUILDING TO THE TIE IN OF THE AUTO TRUNK LINE OK | BILL | BILL | | PB | P | 1053117 |