M. A. MORTENSON COMPANY | B= | C | 12/01/1997 | | JOHNP | JOHNP | | B= | C | 1212011 |
M. A. MORTENSON COMPANY | BFN | C | 12/01/1997 | | JOHNP | JOHNP | | BFN | C | 1212019 |
M. A. MORTENSON COMPANY | BFR | C | 12/01/1997 | | JOHNP | JOHNP | | BFR | C | 1212028 |
M. A. MORTENSON COMPANY | BSP | P | 11/13/1997 | SPOKE WITH PROJECT MANAGER ABOUT WHAT IS LEFT FOR B= | JOHNP | JOHNP | | BSP | P | 1212003 |
M. A. MORTENSON COMPANY | BSP | P | 09/17/1997 | Mag locks at entry & West side work properly, East side needs shorter delay, Clean room door not activated | JOHNP | JOHNP | | BSP | P | 1211996 |
M. A. MORTENSON COMPANY | BFN | R | 09/17/1997 | RBD doesn't inspect aprons at street intersections | JOHNP | JOHNP | | BFN | R | 1211990 |
M. A. MORTENSON COMPANY | BSP | P | 09/10/1997 | Entry frame & doors | JOHNP | JOHNP | | BSP | P | 1211982 |
M. A. MORTENSON COMPANY | BSP | R | 09/05/1997 | Smoke seals not installed on req doors, many blocked open due to wet paint | JOHNP | JOHNP | | BSP | R | 1211974 |
M. A. MORTENSON COMPANY | B= | P | 08/15/1997 | Office #230, clean room & corridors to same OK after fire & plbg OK | JOHNP | JOHNP | | B= | P | 1211967 |
M. A. MORTENSON COMPANY | BSP | P | 08/14/1997 | | JOHNP | JOHNP | | BSP | P | 1211960 |
M. A. MORTENSON COMPANY | BFR | P | 08/11/1997 | Firecaulking of penetrations in rated walls OK | JOHNP | JOHNP | | BFR | P | 1211953 |
M. A. MORTENSON COMPANY | BSP | P | 08/06/1997 | OK to stock chem rooms per fire dept limitations listed on their inspections | JOHNP | JOHNP | | BSP | P | 1211948 |
M. A. MORTENSON COMPANY | BSP | P | 08/05/1997 | Chem storage area only - need cut sheets on F&T rated firecaulk applications & fire dept approval before chemicals can be brought in | JOHNP | JOHNP | | BSP | P | 1211940 |
M. A. MORTENSON COMPANY | B= | R | 08/01/1997 | Haz mat area - doors OK, F&T rated assemblies on through penitrations incomplete | JOHNP | JOHNP | | B= | R | 1211932 |
M. A. MORTENSON COMPANY | BSP | P | 07/31/1997 | | JOHNP | JOHNP | | BSP | P | 1211925 |
M. A. MORTENSON COMPANY | BSP | P | 07/29/1997 | Firecaulking incomplete | JOHNP | JOHNP | | BSP | P | 1211916 |
M. A. MORTENSON COMPANY | BFR | P | 07/23/1997 | | JOHNP | JOHNP | | BFR | P | 1211909 |
M. A. MORTENSON COMPANY | BFR | P | 06/30/1997 | MISC.WALLS | DAVE JONES | DAVE JONES | | BFR | P | 1211901 |
M. A. MORTENSON COMPANY | BFR | P | 06/12/1997 | Elevator #2 shaft walls OK, see plans for other framing | JOHNP | JOHNP | | BFR | P | 1211893 |
M. A. MORTENSON COMPANY | BFR | P | 05/29/1997 | See plans | JOHNP | JOHNP | | BFR | P | 1211885 |
M. A. MORTENSON COMPANY | BFR | P | 05/15/1997 | See plans | JOHNP | JOHNP | | BFR | P | 1211877 |
M. A. MORTENSON COMPANY | BFR | P | 05/05/1997 | See plans | JOHNP | JOHNP | | BFR | P | 1211869 |
M. A. MORTENSON COMPANY | BFR | P | 04/29/1997 | See plans | JOHNP | JOHNP | | BFR | P | 1211862 |
M. A. MORTENSON COMPANY | B= | R | 04/22/1997 | VAR APP'D TO DELETE THE SPRAY APPLIED FIRE PROOFING FOR PROTECTION OF STRUCTURAL MEMBERS WITH THE STIPULATION THE JOB IS DONE AS MR. DONOHUE OF THE COLO SPR FIRE DEPT SPECIFIED - BC 4/97 | JAN | JAN | | B= | R | 1211855 |
M. A. MORTENSON COMPANY | BFR | P | 04/21/1997 | SEE PLANS | JOHNP | JOHNP | | BFR | P | 1211848 |
M. A. MORTENSON COMPANY | BFR | P | 04/17/1997 | See A2.1 & A2.2 | JOHNP | JOHNP | | BFR | P | 1211840 |
M. A. MORTENSON COMPANY | BFR | P | 04/14/1997 | See plans | JOHNP | JOHNP | | BFR | P | 1211833 |
M. A. MORTENSON COMPANY | BFR | P | 04/08/1997 | 1st & 2nd floor - partial on walls | JOHNP | JOHNP | | BFR | P | 1211826 |
M. A. MORTENSON COMPANY | BFR | P | 04/01/1997 | 2nd floor clean room corridor walls & wall on roof at grade separation | JOHNP | JOHNP | | BFR | P | 1211821 |
M. A. MORTENSON COMPANY | BFR | P | 03/26/1997 | 2ND FL.CORR.WALLS CLEAN ROOM SIDE-NORTH AND EAST | DAVE JONES | DAVE JONES | | BFR | P | 1211816 |
M. A. MORTENSON COMPANY | BFN | P | 02/24/1997 | | JOHNP | JOHNP | | BFN | P | 1211811 |
M. A. MORTENSON COMPANY | BFN | R | 02/19/1997 | Not ready | JOHNP | JOHNP | | BFN | R | 1211801 |
M. A. MORTENSON COMPANY | BFN | P | 02/18/1997 | | JOHNP | JOHNP | | BFN | P | 1211794 |
M. A. MORTENSON COMPANY | BFN | P | 02/14/1997 | Only 2 bars coming out of pad on cold joint at NE corner | JOHNP | JOHNP | | BFN | P | 1211786 |
M. A. MORTENSON COMPANY | BFN | P | 02/13/1997 | | JOHNP | JOHNP | | BFN | P | 1211778 |
M. A. MORTENSON COMPANY | BFN | R | 02/11/1997 | Canceled by contractor | JOHNP | JOHNP | | BFN | R | 1211770 |
M. A. MORTENSON COMPANY | BFN | P | 02/10/1997 | | JOHNP | JOHNP | | BFN | P | 1211762 |
M. A. MORTENSON COMPANY | BFN | P | 02/07/1997 | | JOHNP | JOHNP | | BFN | P | 1211754 |
M. A. MORTENSON COMPANY | BFN | P | 02/06/1997 | | JOHNP | JOHNP | | BFN | P | 1211746 |
M. A. MORTENSON COMPANY | BFN | P | 02/05/1997 | | JOHNP | JOHNP | | BFN | P | 1211737 |
M. A. MORTENSON COMPANY | BFN | P | 02/03/1997 | | JOHNP | JOHNP | | BFN | P | 1211730 |
M. A. MORTENSON COMPANY | BFN | P | 01/31/1997 | | JOHNP | JOHNP | | BFN | P | 1211722 |
M. A. MORTENSON COMPANY | BFN | P | 01/28/1997 | Repour of bad pad | JOHNP | JOHNP | | BFN | P | 1211713 |
M. A. MORTENSON COMPANY | BFN | P | 01/27/1997 | | JOHNP | JOHNP | | BFN | P | 1211705 |
M. A. MORTENSON COMPANY | BFN | R | 01/23/1997 | Grade beam 1 steel not running into pad to the East | JOHNP | JOHNP | | BFN | R | 1211699 |
M. A. MORTENSON COMPANY | BFN | P | 01/22/1997 | Waffle floor | JOHNP | JOHNP | | BFN | P | 1211692 |
M. A. MORTENSON COMPANY | BFN | P | 01/21/1997 | | JOHNP | JOHNP | | BFN | P | 1211685 |
M. A. MORTENSON COMPANY | BFN | P | 01/17/1997 | | JOHNP | JOHNP | | BFN | P | 1211678 |
M. A. MORTENSON COMPANY | BFN | P | 01/16/1997 | | JOHNP | JOHNP | | BFN | P | 1211671 |
M. A. MORTENSON COMPANY | BFN | P | 01/13/1997 | Cancelled by contractor | JOHNP | JOHNP | | BFN | P | 1211665 |
M. A. MORTENSON COMPANY | BFN | P | 01/09/1997 | | JOHNP | JOHNP | | BFN | P | 1211656 |
M. A. MORTENSON COMPANY | BFN | P | 01/07/1997 | See plans | JOHNP | JOHNP | | BFN | P | 1211644 |
M. A. MORTENSON COMPANY | BFN | R | 01/06/1997 | Canceled by contractor | JOHNP | JOHNP | | BFN | R | 1211640 |
M. A. MORTENSON COMPANY | BFT | P | 01/03/1997 | SEE SHEET S2.1 | DAVE JONES | DAVE JONES | | BFT | P | 1211632 |
M. A. MORTENSON COMPANY | BFN | P | 01/02/1997 | | JOHNP | JOHNP | | BFN | P | 1211626 |
M. A. MORTENSON COMPANY | BFN | P | 12/31/1996 | see plans | JIMA | JIMA | | BFN | P | 1211596 |
M. A. MORTENSON COMPANY | BFN | R | 12/30/1996 | canceled by builder | JIMA | JIMA | | BFN | R | 1211589 |
M. A. MORTENSON COMPANY | BFN | P | 12/27/1996 | | DAVE JONES | DAVE JONES | | BFN | P | 1211573 |
M. A. MORTENSON COMPANY | BFT | P | 12/27/1996 | PADS EAST | DAVE JONES | DAVE JONES | | BFT | P | 1211581 |
M. A. MORTENSON COMPANY | BFN | P | 12/26/1996 | COLS.N.E. | DAVE JONES | DAVE JONES | | BFN | P | 1211564 |
M. A. MORTENSON COMPANY | BFN | P | 12/24/1996 | | JOHNP | JOHNP | | BFN | P | 1211556 |
M. A. MORTENSON COMPANY | BFN | P | 12/23/1996 | | JOHNP | JOHNP | | BFN | P | 1211548 |
M. A. MORTENSON COMPANY | BFN | P | 12/20/1996 | 6 columns, 2 pads, page S2.1 | JOHNP | JOHNP | | BFN | P | 1211540 |
M. A. MORTENSON COMPANY | BFN | P | 12/19/1996 | See plans, frost removed | JOHNP | JOHNP | | BFN | P | 1211532 |
M. A. MORTENSON COMPANY | BFN | R | 12/17/1996 | Canceled by contractor | JOHNP | JOHNP | | BFN | R | 1211524 |
M. A. MORTENSON COMPANY | BFN | P | 12/16/1996 | See Plans S2.1 | JOHNP | JOHNP | | BFN | P | 1211517 |
M. A. MORTENSON COMPANY | BFN | P | 12/13/1996 | Pads & columns, See S2.1 | JOHNP | JOHNP | | BFN | P | 1211510 |
M. A. MORTENSON COMPANY | BFN | P | 12/12/1996 | 11 columns, 4 pads | JOHNP | JOHNP | | BFN | P | 1211500 |
M. A. MORTENSON COMPANY | BFN | P | 12/11/1996 | | JOHNP | JOHNP | | BFN | P | 1211348 |
M. A. MORTENSON COMPANY | BFN | P | 12/10/1996 | Pas. elevator pit walls: S2.1 | JOHNP | JOHNP | | BFN | P | 1211339 |
M. A. MORTENSON COMPANY | BFT | P | 12/09/1996 | Pas. ele pit, See S2.1 | JOHNP | JOHNP | | BFT | P | 1211330 |
M. A. MORTENSON COMPANY | BFN | P | 12/06/1996 | Frt elevator walls, See S2.1 | JOHNP | JOHNP | | BFN | P | 1211322 |
M. A. MORTENSON COMPANY | BFN | P | 12/05/1996 | Elevator pit ftg, see page S2.1 | JOHNP | JOHNP | | BFN | P | 1211315 |
M. A. MORTENSON COMPANY | BFN | P | 12/02/1996 | Containment pit walls | JOHNP | JOHNP | | BFN | P | 1211307 |
M. A. MORTENSON COMPANY | BFN | P | 11/27/1996 | Containment pits (4) | JOHNP | JOHNP | | BFN | P | 1211299 |
WHITNEY ELECTRIC CO | E= | C | 10/01/1997 | rooms 282to285, 200,201,2ooa,104,105, and 109 | IKE | IKE | | E= | C | 1211290 |
WHITNEY ELECTRIC CO | ER | P | 09/05/1997 | 109 AND FRONT ENTRY | MIKEC | MIKEC | | ER | P | 1211283 |
WHITNEY ELECTRIC CO | ER | P | 08/26/1997 | WALLS 120 | MIKEC | MIKEC | | ER | P | 1211274 |
WHITNEY ELECTRIC CO | ER | P | 08/15/1997 | CEILING 109 | MIKEC | MIKEC | | ER | P | 1211266 |
WHITNEY ELECTRIC CO | E= | P | 08/13/1997 | EXCEPT 282,83,84,85,200A,200,201,104,105,109 | MIKEC | MIKEC | | E= | P | 1211259 |
WHITNEY ELECTRIC CO | ER | P | 08/08/1997 | fire pump ok.ceilings rooms 101,120,131,133, and 138. remove sheetrock one side 2 nd floor 2 office. | IKE | IKE | | ER | P | 1211240 |
WHITNEY ELECTRIC CO | ES | C | 08/08/1997 | fire pump ok. | IKE | IKE | | ES | C | 1211247 |
WHITNEY ELECTRIC CO | E= | P | 08/04/1997 | DISCONNECT LOCATION CHANGED | MIKEC | MIKEC | | E= | P | 1211233 |
WHITNEY ELECTRIC CO | E= | R | 08/01/1997 | I DO NOT FEEL THAT AND ELECTRICAL FINAL IS JUSTIFIED AT THIS TIME. | MIKEC | MIKEC | | E= | R | 1211225 |
WHITNEY ELECTRIC CO | ER | P | 07/29/1997 | CEILINGS RM.172,CORR.142,274 | MIKEC | MIKEC | | ER | P | 1211213 |
WHITNEY ELECTRIC CO | ER | P | 07/22/1997 | ceiling 210 | MIKEC | MIKEC | | ER | P | 1211206 |
WHITNEY ELECTRIC CO | ER | P | 07/21/1997 | RM 108,142 | MIKEC | MIKEC | | ER | P | 1211197 |
WHITNEY ELECTRIC CO | ER | P | 07/17/1997 | WALLS RM. 230 | MIKEC | MIKEC | | ER | P | 1211190 |
WHITNEY ELECTRIC CO | ER | P | 07/14/1997 | RMS.100,101,103,104,105,120,133,134,135,136,138 | MIKEC | MIKEC | | ER | P | 1211181 |
WHITNEY ELECTRIC CO | ER | P | 07/09/1997 | CEILINGS RM. 221,230.271,272,219 | MIKEC | MIKEC | | ER | P | 1211173 |
WHITNEY ELECTRIC CO | ER | P | 06/27/1997 | WALLS RM 210,221,219,224,225,244,242 | MIKEC | MIKEC | | ER | P | 1211165 |
WHITNEY ELECTRIC CO | ER | P | 06/11/1997 | walls | RON | RON | | ER | P | 1211150 |
WHITNEY ELECTRIC CO | ES | C | 06/11/1997 | 4w/ug 1000 amp.277/480. whitney. | RON | RON | | ES | C | 1211157 |
WHITNEY ELECTRIC CO | ER | P | 06/05/1997 | CORR. 274, 280,ROOMS 242,244,271,272 | MIKEC | MIKEC | | ER | P | 1211145 |
WHITNEY ELECTRIC CO | ER | P | 06/02/1997 | WALLS RM 266,267,268.269 | MIKEC | MIKEC | | ER | P | 1211137 |
WHITNEY ELECTRIC CO | ER | P | 04/23/1997 | WALLS RMS. 167,168 169 | MIKEC | MIKEC | | ER | P | 1211129 |
WHITNEY ELECTRIC CO | ER | P | 04/10/1997 | partial walls | MIKEC | MIKEC | | ER | P | 1211120 |
WHITNEY ELECTRIC CO | ES | P | 04/02/1997 | CONTRACTOR WOULD LIKE TO ENERGIZE SERVICE TEMP. TO BE CHECKED BY FACTORY REP.3 PHASE 4 WIRE 480 VOLT 3000 AMP.OK TO SET C-T METERS.COORDINATE WITH ELEC. CONTRACTOR WHITNEY ELEC. | MIKEC | MIKEC | | ES | P | 1211112 |
WHITNEY ELECTRIC CO | EST | P | 03/11/1997 | 3 PHASE 4 WIRE 480 VOLT 200 AMP CONST. TEMP OK TO ENERGIZE WHITNEY ELECT | MIKEC | MIKEC | | EST | P | 1211105 |
WHITNEY ELECTRIC CO | ESL | P | 01/21/1997 | | MIKEC | MIKEC | | ESL | P | 1211097 |
WHITNEY ELECTRIC CO | EUG | P | 12/26/1996 | SECONDARY CONDUITS | GLENN | GLENN | | EUG | P | 1211089 |
COMMERCIAL DESIGN ENGEERING LTD | H= | C | 11/24/1997 | | JOHNW | JOHNW | | H= | C | 1210837 |
GENERAL SHEET METAL CORP. | H= | C | 11/24/1997 | | JOHNW | JOHNW | | H= | C | 1212139 |
GENERAL SHEET METAL CORP. | H= | P | 09/17/1997 | TALKED ABOUT THE REQ. FOR CHILLER ROOM | JOHNW | JOHNW | | H= | P | 1212131 |
GENERAL SHEET METAL CORP. | H= | P | 09/16/1997 | General sheet metal complete/still need chiller controls report | JOHNW | JOHNW | | H= | P | 1212123 |
GENERAL SHEET METAL CORP. | H= | P | 08/13/1997 | 1ST & 2ND LEVELS HVAC OK / STILL NEED INSPECTION ON CHILLER SAFETY SHUTDOWNS AND CONTROLS | JOHNW | JOHNW | | H= | P | 1212116 |
GENERAL SHEET METAL CORP. | H= | P | 07/31/1997 | need to complete office area 1st floor west end and lobby | JOHNW | JOHNW | | H= | P | 1212092 |
GENERAL SHEET METAL CORP. | H= | P | 07/31/1997 | ok for part final/need to verify chiller shutdown and controls also need to start up equipment | JOHNW | JOHNW | | H= | P | 1212100 |
GENERAL SHEET METAL CORP. | HV | C | 07/31/1997 | | JOHNW | JOHNW | | HV | C | 1212108 |
GENERAL SHEET METAL CORP. | HD | P | 07/28/1997 | had a meeting on elevator shaft requirments | JOHNW | JOHNW | | HD | P | 1212082 |
GENERAL SHEET METAL CORP. | HD | P | 07/24/1997 | 2nd floor office area ok/ sub fab level ok pending testing of saftey shutdown and controls in mech rooms also need tie-in on exhaust fan for bottle storage room | JOHNW | JOHNW | | HD | P | 1212077 |
COMMERCIAL DESIGN ENGEERING LTD | HC | C | 06/11/1997 | OK FOR METER | JOHNW | JOHNW | | HC | C | 1210829 |
COMMERCIAL DESIGN ENGEERING LTD | HI | C | 06/06/1997 | 60# test ok / welders stamp is P.T.P. | JOHNW | JOHNW | | HI | C | 1210821 |
GENERAL SHEET METAL CORP. | HV | P | 06/06/1997 | boiler room thru the roof ok to enclose | JOHNW | JOHNW | | HV | P | 1212065 |
GENERAL SHEET METAL CORP. | HD | P | 06/06/1997 | 1st and 2nd office area rough in ok | JOHNW | JOHNW | | HD | P | 1212050 |
GENERAL SHEET METAL CORP. | HD | P | 06/06/1997 | offices 1st and 2nd floors rough duct | JOHNW | JOHNW | | HD | P | 1212056 |
GENERAL SHEET METAL CORP. | HD | P | 05/20/1997 | 2nd level west end corridor fan room and 1st level sub fab | JOHNW | JOHNW | | HD | P | 1212042 |
GENERAL SHEET METAL CORP. | H16 | P | 04/17/1997 | DUCT IN EAST SIDE 2ND FLOOR FOR CLEAN ROOM OK | JOHNW | JOHNW | | H16 | P | 1212036 |
COMMERCIAL DESIGN ENGEERING LTD | P= | C | 08/21/1997 | Could not find permit | KYE | KYE | | P= | C | 1211081 |
COMMERCIAL DESIGN ENGEERING LTD | P= | P | 08/15/1997 | Second floor OK for TCO | KYE | KYE | | P= | P | 1211073 |
COMMERCIAL DESIGN ENGEERING LTD | P= | R | 08/14/1997 | cancelled | KYE | KYE | | P= | R | 1211065 |
COMMERCIAL DESIGN ENGEERING LTD | P= | R | 08/06/1997 | Cancelled | KYE | KYE | | P= | R | 1211057 |
COMMERCIAL DESIGN ENGEERING LTD | P= | R | 08/01/1997 | fixtures not set | DAVEL | DAVEL | | P= | R | 1211050 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 06/20/1997 | A thru K, 9 thru 11 first and second floors | KYE | KYE | | PTO | P | 1211041 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 06/19/1997 | Vents in southwest corner area | KYE | KYE | | PTO | P | 1211034 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 06/18/1997 | Northwest office area | KYE | KYE | | PTO | P | 1211026 |
COMMERCIAL DESIGN ENGEERING LTD | PRD | P | 06/18/1997 | Northwest office area | KYE | KYE | | PRD | P | 1211018 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 06/12/1997 | 1st and 2nd floor east side offices | DAVEL | DAVEL | | PTO | P | 1211010 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 06/11/1997 | VENTS OVER MECH ROOMS | KYE | KYE | | PTO | P | 1211003 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 06/02/1997 | R00r drains in north office area | KYE | KYE | | PTO | P | 1210996 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 05/23/1997 | Vents out of mechanical room | KYE | KYE | | PTO | P | 1210989 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 05/14/1997 | COLUMNS NORTH OF BOILER ROOM | KYE | KYE | | PTO | P | 1210982 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 05/13/1997 | Boiler room columns | KYE | KYE | | PTO | P | 1210974 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 05/08/1997 | | KYE | KYE | | PTO | P | 1210966 |
COMMERCIAL DESIGN ENGEERING LTD | PRD | C | 05/06/1997 | | KYE | KYE | | PRD | C | 1210956 |
COMMERCIAL DESIGN ENGEERING LTD | PRD | P | 05/05/1997 | A thru Q, 1 thru 2.5 | KYE | KYE | | PRD | P | 1210949 |
COMMERCIAL DESIGN ENGEERING LTD | PB | R | 05/05/1997 | | KYE | KYE | | PB | R | 1210942 |
COMMERCIAL DESIGN ENGEERING LTD | PTO | P | 05/02/1997 | | KYE | KYE | | PTO | P | 1210934 |
COMMERCIAL DESIGN ENGEERING LTD | PB | P | 04/01/1997 | | KYE | KYE | | PB | P | 1210926 |
COMMERCIAL DESIGN ENGEERING LTD | PB | P | 03/31/1997 | 1 thru 12, Q thru K.5 | KYE | KYE | | PB | P | 1210919 |
COMMERCIAL DESIGN ENGEERING LTD | PB | P | 03/20/1997 | | KYE | KYE | | PB | P | 1210910 |
COMMERCIAL DESIGN ENGEERING LTD | PRD | P | 03/18/1997 | Lower west base | KYE | KYE | | PRD | P | 1210903 |
COMMERCIAL DESIGN ENGEERING LTD | PRD | P | 03/13/1997 | Base at south west corner | KYE | KYE | | PRD | P | 1210896 |
COMMERCIAL DESIGN ENGEERING LTD | PB | P | 03/12/1997 | Column A to C, 9 to 12 | KYE | KYE | | PB | P | 1210888 |
COMMERCIAL DESIGN ENGEERING LTD | PB | P | 03/11/1997 | Acid waste | KYE | KYE | | PB | P | 1210880 |
COMMERCIAL DESIGN ENGEERING LTD | PB | P | 03/03/1997 | No approved plans available | KYE | KYE | | PB | P | 1210872 |
COMMERCIAL DESIGN ENGEERING LTD | PB | P | 02/27/1997 | A to C, 1 to 4.6 | KYE | KYE | | PB | P | 1210867 |
COMMERCIAL DESIGN ENGEERING LTD | PB | P | 02/25/1997 | See red lines on plans | KYE | KYE | | PB | P | 1210859 |
COMMERCIAL DESIGN ENGEERING LTD | PB | P | 02/20/1997 | Main trunk line at south end of building | KYE | KYE | | PB | P | 1210851 |
COMMERCIAL DESIGN ENGEERING LTD | PB | P | 02/19/1997 | East side of building, Marked on drawings and sign sheet, no approved plans on job | KYE | KYE | | PB | P | 1210845 |