U S OLYMPIC COMMITTEE | H01 | C | 01/16/2024 | ANNUAL 1/23 -- OTIS & SERVICE -- NOTE: ANNUAL CATEGORY 1 HYDRAULIC TEST IS DUE BY THE END OF THE MONTH (Receipt #2024918) | BENH | BENH | | H01 | C | 7968971 |
U S OLYMPIC COMMITTEE | H02 | C | 07/26/2023 | HO2 -- ANNUAL 1/23 -- OTIS & SERVICE | BENH | BENH | | H02 | C | 7809112 |
U S OLYMPIC COMMITTEE | H01 | C | 01/10/2023 | ANNUAL 1/22 -- OTIS & SERVICE -- NOTE: ANNUAL CATEGORY 1 HYDRAULIC TEST DUE BY THE END OF THE MONTH (Receipt #1925607) cat 1 1/23 BH | BENH | BENH | | H01 | C | 7630489 |
U S OLYMPIC COMMITTEE | H02 | C | 07/28/2022 | HO2 -- ANNUAL 1/22 -- OTIS & SERVICE | BENH | BENH | | H02 | C | 7463209 |
U S OLYMPIC COMMITTEE | H01 | C | 01/25/2022 | ANNUAL 01/2022-- OTIS AND SERVICE (Receipt #1838919) | MIKEM | MIKEM | | H01 | C | 7249865 |
U S OLYMPIC COMMITTEE | H02 | C | 07/12/2021 | RP 1/21 OTIS, HO2 cat 1 1/22 | ERIC | ERIC | | H02 | C | 7031496 |
U S OLYMPIC COMMITTEE | H06 | C | 01/20/2021 | WITNESSED HYDRO SAFETY TEST W/ OTIS - ELEVATOR EMERGENCY PHONE WILL NOT MAKE TWO-WAY COMMUNICATION. UPPER HORIZONTAL TRIM PIECES ABOVE INTERIOR CAB PANELS NEED TO BE SECURED W/ SCREWS, VELCRO IS UNACCEPTABLE. | ROBERTV | ROBERTV | | H06 | C | 6841558 |
U S OLYMPIC COMMITTEE | H01 | C | 01/20/2021 | WITNESSED AT H01 (Receipt #1744092) | ROBERTV | ROBERTV | | H01 | C | 6841548 |
U S OLYMPIC COMMITTEE | H02 | C | 07/22/2020 | H02 -- RP -- 5/20 -- OTIS. EMERGENCY LIGHT STILL NOT WORKING. STILL MISSING UPPER DOOR FLAG ON THE "B" FLOOR HOISTWAY DOOR. DOOR OPERATOR BELT IS STILL SHREDDED. ONSITE DOCUMENTATION DOES NOT INDICATE ANY REPAIRS TO THESE ITEMS HAVE BEEN PERFORMED OR ATTEMPTED...... THIS IS THE FINAL NOTICE FOR THESE ITEMS. | ROBERTV | ROBERTV | | H02 | C | 6646111 |
U S OLYMPIC COMMITTEE | H01 | C | 01/15/2020 | RP -- 4/19 -- OTIS. ITEMS LISTED ON LAST TWO PREVIOUS INSPECTION REPORTS HAVE NOT BEEN ADDRESSED AS LISTED:.........EMERGENCY LIGHT NOT WORKING. FIRE SERVICE PHASE II SWITCH NOT OPERATING CORRECTLY. MISSING UPPER DOOR RESTRICTOR FLAG ON BASEMENT HOISTWAY DOOR............ IN ADDITION, HOISTWAY DOOR CLOSE ROLLER ASSEMBLY ON "2" FLOOR IS STICKING. CAB DOOR VANE IS LOOSE......PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL ITEMS ARE ADDRESSED (Receipt #1655815 from 01/15/2020) | ROBERTV | ROBERTV | | H01 | C | 6453135 |
U S OLYMPIC COMMITTEE | H02 | C | 07/25/2019 | H02 -- RP -- 4/19 -- OTIS. ITEMS LISTED ON PREVIOUS INSPECTION REPORT HAVE NOT BEEN ADDRESSED AS LISTED:.........EMERGENCY LIGHT NOT WORKING. FIRE SERVICE PHASE II SWITCH NOT OPERATING CORRECTLY. MISSING UPPER DOOR RESTRICTOR FLAG ON BASEMENT HOISTWAY DOOR. DOOR OPERATOR DRIVE BELT IS SHREDDED.............. 30 DAYS TO ADDRESS. ALSO, NEED TO COMPLETELY FILL OUT TEST FORM TO INCLUDE BUILDING NUMBER AND MANUFACTURER JOB CONTRACT NUMBER, AND SEND COPIES TO PPRBD. | ROBERTV | ROBERTV | | H02 | C | 6277325 |
U S OLYMPIC COMMITTEE | H01 | C | 01/17/2019 | RP -- 5/18 -- OTIS. EMERGENCY LIGHT NOT WORKING. FIRE SERVICE PHASE II SWITCH WILL NOT CLICK INTO "ON' POSITION. MISSING UPPER DOOR RESTRICTOR FLAG ON BASEMENT HOISTWAY DOOR. DOOR OPERATOR DRIVE BELT IS SHREDDED. | ROBERTV | ROBERTV | | H01 | C | 6081352 |
U S OLYMPIC COMMITTEE | H02 | C | 07/11/2018 | H02 -- RP -- 5/18 -- OTIS | ROBERTV | ROBERTV | | H02 | C | 5899481 |
U S OLYMPIC COMMITTEE | H01 | C | 01/22/2018 | RP -- 1/17 -- OTIS. EMERGENCY LIGHT NOT WORKING AGAIN. FIRE SERVICE PHASE II SWITCH NOT TURNING IN CAR PANEL. (Receipt #1477569) | ROBERTV | ROBERTV | | H01 | C | 5744079 |
U S OLYMPIC COMMITTEE | H02 | C | 07/25/2017 | RP -- 1/17 -- OTIS. ITEMS HAVE BEEN ADDRESSED | ROBERTV | ROBERTV | | H02 | C | 5575192 |
U S OLYMPIC COMMITTEE | H01 | C | 01/26/2017 | RP -- 1/16 -- OTIS. EMERGENCY LIGHT AND ALARM STILL NOT WORKING UNDER BATTERY POWER, LOWER HOISTWAY DOOR RESTRICTOR FLAG ON 3RD FLOOR HAS NOT BEEN REINSTALLED (FLAG IS SITTING ON TOP OF CAR). 30 DAYS TO REMEDY ITEMS | ROBERTV | ROBERTV | | H01 | C | 5399669 |
U S OLYMPIC COMMITTEE | H02 | C | 07/01/2016 | H02 -- CHECK FOR REPAIRS FROM WITNESS TEST AT H01 | ROBERTV | ROBERTV | | H02 | C | 5235776 |
U S OLYMPIC COMMITTEE | H01 | C | 01/28/2016 | SEE WITNESS TEST INSPECTION (Receipt #1310766) | ROBERTV | ROBERTV | | H01 | C | 5125746 |
U S OLYMPIC COMMITTEE | H06 | C | 01/28/2016 | WITNESSED HYDRO SAFETY TEST W/ OTIS -- EMERGENCY PHONE NOT WORKING, EMERGENCY LIGHT AND ALARM NOT WORKING (2ND NOTICE), 3RD FLOOR HOISTWAY DOOR LOWER RESTRICTOR FLAG NEEDS REINSTALLED (2ND NOTICE), NEED COMPLETE MAINTENANCE CONTROL PROGRAM ONSITE. ITEMS NEED TO BE ADDRESSED PRIOR TO NEXT INSPECTION TO AVOID SERVICE INTERRUPTION. | ROBERTV | ROBERTV | | H06 | C | 5125742 |
U S OLYMPIC COMMITTEE | H02 | C | 07/29/2015 | RP -- 7/15 -- OTIS. MISSING BULB GUARD SLEEVES IN CAR, EMERGENCY LIGHT AND ALARM NOT WORKING, 3RD FLOOR HOISTWAY DOOR RESTRICTOR MISSING, 5 YEAR WITNESS TEST DUE 7/2016 | ROBERTV | ROBERTV | | H02 | C | 5003794 |
U S OLYMPIC COMMITTEE | H01 | C | 01/02/2015 | RP 3-14 OTIS (Receipt #1243632) | TOM | TOM | | H01 | C | 4894309 |
U S OLYMPIC COMMITTEE | H02 | C | 07/21/2014 | RP 3/14 OTIS. FIRE FIGHTERS CALL CANCEL BUTTON BROKEN | ERIC | ERIC | | H02 | C | 4780440 |
U S OLYMPIC COMMITTEE | H01 | C | 01/20/2014 | RP 2-13-OTIS-EMERGENCY LIGHT IN CAR NOT WORKING (Receipt #1177609) | TOM | TOM | | H01 | C | 4681773 |
U S OLYMPIC COMMITTEE | H02 | C | 07/24/2013 | HO2 | ERIC | ERIC | | H02 | C | 4570077 |
U S OLYMPIC COMMITTEE | H01 | C | 01/28/2013 | OTIS, RELIEF PRESSURE TEST EXPIRED (Receipt #1108121) | ERIC | ERIC | | H01 | C | 4462239 |
U S OLYMPIC COMMITTEE | H02 | C | 07/16/2012 | RP 12/11 OTIS | ERIC | ERIC | | H02 | C | 4342153 |
U S OLYMPIC COMMITTEE | H01 | C | 01/27/2012 | RP 12/11 OTIS (Receipt #1025107) | ERIC | ERIC | | H01 | C | 4265208 |
U S OLYMPIC COMMITTEE | H02 | C | 07/25/2011 | RP 1-11--OTIS | TOM | TOM | | H02 | C | 4183782 |
U S OLYMPIC COMMITTEE | H01 | C | 01/28/2011 | RP 1-11--OTIS--MACHINE ROOM STORAGE (Receipt #957560) | TOM | TOM | | H01 | C | 4106105 |
U S OLYMPIC COMMITTEE | H02 | C | 07/02/2010 | rp 1-10--otis new eru installed | TOM | TOM | | H02 | C | 4017371 |
U S OLYMPIC COMMITTEE | H01 | C | 01/29/2010 | rp 1-10--otis (Receipt #894792) | TOM | TOM | | H01 | C | 3938591 |
U S OLYMPIC COMMITTEE | H02 | C | 07/22/2009 | OTIS RP 1/09 | ERIC | ERIC | | H02 | C | 3861792 |
U S OLYMPIC COMMITTEE | H01 | C | 01/14/2009 | OTIS. RELIEF PRESSURE TEST EXPIRED, LAST TEST 10/07. MISSING BULB GUARDS IN CAR (Receipt #842346) | ERIC | ERIC | | H01 | C | 3790696 |
U S OLYMPIC COMMITTEE | H02 | C | 07/15/2008 | RP 10 - 07 [ 290 ] --- OTIS | LES | LES | | H02 | C | 3708578 |
U S OLYMPIC COMMITTEE | H01 | C | 01/29/2008 | RP 10-07 --- OTIS --- CHECK ALL DOOR GIBBS | LES | LES | | H01 | C | 1251998 |
U S OLYMPIC COMMITTEE | H02 | C | 07/25/2007 | RP 10-06 --- OTIS | LES | LES | | H02 | C | 1251993 |
U S OLYMPIC COMMITTEE | H01 | C | 01/31/2007 | RP 10-06 --- OTIS | LES | LES | | H01 | C | 1251986 |
U S OLYMPIC COMMITTEE | H02 | C | 07/31/2006 | RP TEST DUE --- OTIS | LES | LES | | H02 | C | 1251982 |
U S OLYMPIC COMMITTEE | H01 | C | 01/30/2006 | RP 5-05 --- OTIS | LES | LES | | H01 | C | 1251978 |
U S OLYMPIC COMMITTEE | H02 | C | 07/28/2005 | RP--5--05--OTIS | JOHNW | JOHNW | | H02 | C | 1251972 |
U S OLYMPIC COMMITTEE | H01 | C | 01/31/2005 | RP 3-04 --- OTIS | LES | LES | | H01 | C | 1251968 |
U S OLYMPIC COMMITTEE | H02 | C | 08/26/2004 | RP 3-04--OTIS--ADJUST OR REPLACE DOOR GIBBS-EXCESSIVE PLAY--DEE WINSTON--CELL 439-2883--FAX--632-9810 | TOM | TOM | | H02 | C | 1251964 |
U S OLYMPIC COMMITTEE | H01 | C | 01/28/2004 | RP 3-03--OTIS | TOM | TOM | | H01 | C | 1251960 |
U S OLYMPIC COMMITTEE | H02 | C | 07/30/2003 | RP 3-03--OTIS | TOM | TOM | | H02 | C | 1251952 |
U S OLYMPIC COMMITTEE | H03 | C | 07/30/2003 | | TOM | TOM | | H03 | C | 1251956 |
U S OLYMPIC COMMITTEE | H01 | P | 01/31/2003 | OTIS--RP EXP | TOM | TOM | | H01 | P | 1251948 |
U S OLYMPIC COMMITTEE | H02 | C | 07/30/2002 | RP 8-01--OTIS--BSMNT CALL BUTTON LIGHT OUT | TOM | TOM | | H02 | C | 1251944 |
U S OLYMPIC COMMITTEE | H01 | C | 01/31/2002 | RP 8-01 | LES | LES | | H01 | C | 1251940 |
U S OLYMPIC COMMITTEE | H03 | C | 09/25/2001 | RP 9-01 | TOM | TOM | | H03 | C | 1251935 |
U S OLYMPIC COMMITTEE | H02 | C | 07/31/2001 | RP EXP--LAST TEST 3-00--LEVELING IS OFF | TOM | TOM | | H02 | C | 1251930 |
U S OLYMPIC COMMITTEE | H01 | C | 01/31/2001 | RP 3-00 | LES | LES | | H01 | C | 1251925 |
U S OLYMPIC COMMITTEE | H02 | C | 07/21/2000 | RP 3-00--OTIS | TOM | TOM | | H02 | C | 1251921 |
U S OLYMPIC COMMITTEE | H01 | P | 02/14/2000 | RP EXPIRED (1-99) | TOM | TOM | | H01 | P | 1251917 |
U S OLYMPIC COMMITTEE | H02 | C | 08/02/1999 | RP 1-99--OTIS--IN 96 | TOM | TOM | | H02 | C | 1251912 |
U S OLYMPIC COMMITTEE | H01 | C | 02/17/1999 | | RUSS | RUSS | | H01 | C | 1251895 |
U S OLYMPIC COMMITTEE | H02 | C | 07/29/1998 | | RUSS | RUSS | | H02 | C | 1251890 |
U S OLYMPIC COMMITTEE | H01 | C | 01/08/1998 | | RUSS | RUSS | | H01 | C | 1251908 |
U S OLYMPIC COMMITTEE | H02 | C | 07/15/1997 | | RUSS | RUSS | | H02 | C | 1251904 |
U S OLYMPIC COMMITTEE | H01 | C | 01/22/1997 | INTIAL INSPECTION, PERMIT ISSUED | RUSS | RUSS | | H01 | C | 1251899 |