COLORADO SPRINGS UTILITIES | H05 | C | 11/17/2023 | PPRBD HAS RECEIVED CONFIRMATION FROM BUILDING OWNER THAT POWER HAS BEEN REMOVED FROM BUILDING AND ELEVATOR IS NO LONGER IN SERVICE. ONCE DEMO PERMIT HAS BEEN PULLED/COMPLETED, PERMIT CAN BE VOIDED | DUSTINS | DUSTINS | | H05 | C | 7922295 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/31/2023 | H02 - 5YR 06/2019 - ANNUAL 05/2022 - OTIS WITH INNOVATION KEYS AND PEAK SERVICE -/ PPRBD NOTE: CATEGORY 1 TESTING IS DUE THIS MONTH - (PPRBD NOTE: BUILDING IS TO BE DEMOLISHED IN THE UPCOMING MONTHS. NEED VERIFICATION FROM OWNERS ONCE THE ELEVATORS HAVE BEEN REMOVED) | MIKEM | MIKEM | | H02 | C | 7758085 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/29/2022 | 5YR -- 06/2019 -- ANNUAL 05/2022 -- OTIS WITH INNOVATION KEYS AND PEAK SERVICE (Receipt #1917415) | MIKEM | MIKEM | | H01 | C | 7594998 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/31/2022 | H02 -- 6/19 -- CAT1 -- 5/2022 -- OTIS W/ INNOVATION KEYS AND PEAK SERVICE. | ROBERTV | ROBERTV | | H02 | C | 7394044 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/29/2021 | 5YR -- 6/19 -- CAT1 -- 4/21 -- DOVER W/ INNOVATION KEYS AND PEAK SERVICE. (NO CODE ISSUES) (Receipt #1825609) (Cat1 -- 5/2022) | ROBERTV | ROBERTV | | H01 | C | 7189688 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/13/2021 | HO2 -- 5YR -- 6/19 -- CAT1 -- 5/21 -- OTIS W / PEAK SERVICE. CHECK PREVIOUS LISTED ITEMS AT H01 | ROBERTV | ROBERTV | | H02 | C | 6967078 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/23/2020 | 5YR -- 6/19 -- OTIS W/ PEAK SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING IS PAST DUE. COUNTERWEIGHT GUIDE ROLLERS NEED ATTENTION. (Receipt #1731673) (Cat1 performed 4/2021, check for other remaining items at H01) | ROBERTV | ROBERTV | | H01 | C | 6785256 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/21/2020 | H02 -- 6/19 -- OTIS W/ INNOVATION KEYS AND PEAK SERVICE | ROBERTV | ROBERTV | | H02 | C | 6580389 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/21/2019 | 5 YEAR WITNESSED TEST PERFORMED IN JUNE (Receipt #1646036) | ERIC | ERIC | | H01 | C | 6406511 |
COLORADO SPRINGS UTILITIES | H06 | C | 06/05/2019 | WITNESSED CATEGORY 5 TRACTION TESTING W/ PEAK - (MONITOR SUSPENSION ROPES AS THEY ARE BECOMING THIN) (Receipt #1603895) | ROBERTV | ROBERTV | | H06 | C | 6220295 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/23/2019 | 5 YEAR TESTING SCHEDULED FOR JUNE | ERIC | ERIC | | H02 | C | 6208790 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/20/2018 | 5YR -- 8/15 -- DOVER / INNOVATION KEYS / PEAK SERVICE. REQUIRED ANNUAL TESTING HAS NOT BEEN PERFORMED SINCE 8/2015. FIRE SERVICE PHASE II "HOLD" NOT WORKING. ESCAPE HATCH PLUG NOT CONNECTED TO CAR TOP BRACKET. CAR TOP LIGHT NOT WORKING. PHASE I SWITCH DIFFICULT TO TURN........... ITEMS NEED ADDRESSED WITHIN 30 DAYS. ALSO, GEAR BOX SIGHT GLASS IS LEAKING AND NEEDS TO BE ADDRESSED A SOON AS POSSIBLE. (Cat 1 done 11/30/2018) (Receipt #1557634) | ROBERTV | ROBERTV | | H01 | C | 6030386 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/31/2018 | 5YR --8--14--DOVER --NEED CATEGORY 1 REPORT | JOHNW | JOHNW | | H02 | C | 5860723 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/29/2017 | 5YR -- 8/14 -- DOVER / INNOVATION KEYS / PEAK SERVICE. ELEVATOR OUT OF SERVICE AT TIME OF INSPECTION. NO DOCUMENTS ONSITE INDICATING REQUIRED ANNUAL CATEGORY 1 TESTING HAS BEEN PERFORMED, NEED TRACTION ELEVATOR MAINTENANCE CONTROL PROGRAM ONSITE. (Receipt #1468321) | ROBERTV | ROBERTV | | H01 | C | 5697201 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/17/2017 | H02
| ROBERTV | ROBERTV | | H02 | C | 5508699 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/29/2016 | 5YR -- 8/14 -- DOVER / INNOVATION KEYS / PEAK SERVICE. ELEVATOR OUT OF SERVICE AT TIME OF INSPECTION. (Receipt #1385379) | ROBERTV | ROBERTV | | H01 | C | 5354505 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/20/2016 | 5 YEAR 8/14 OTIS, PEAK SERVICE. H02 | ERIC | ERIC | | H02 | C | 5204173 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/27/2015 | 5YR 8-14 BUTTONS ON CONTROL OPERATING PANEL STICK IN ON POSITION / WATER IN PIT (Receipt #1301285) | TOM | TOM | | H01 | C | 5087946 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/22/2015 | HO2 | JOHNW | JOHNW | | H02 | C | 4959334 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/19/2014 | ELEVATOR WITNESSED IN AUGUST (Receipt #1232995) | JOHNW | JOHNW | | H01 | C | 4856061 |
COLORADO SPRINGS UTILITIES | H06 | C | 08/08/2014 | WITNESSED 5 YEAR SAFETY TEST TO PUT BACK INTO SERVICE AFTER FIRE (Receipt #1212580) | ERIC | ERIC | | H06 | C | 4793079 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/20/2014 | NO ACCESS DUE TO FIRE | ERIC | ERIC | | H02 | C | 4742082 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/12/2013 | 5YR 12-11-OTIS (Receipt #1168719) | TOM | TOM | | H01 | C | 4649529 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/28/2013 | 5YR 12-11--OTIS | TOM | TOM | | H02 | C | 4531954 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/19/2012 | 5YR 12-11--OTIS (Receipt #1097920) | TOM | TOM | | H01 | C | 4432114 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/30/2012 | 5 YR 12-11--OTIS | TOM | TOM | | H02 | C | 4317823 |
COLORADO SPRINGS UTILITIES | HE16 | C | 12/23/2011 | NEW CONTROLLER, DOOR CONTROLLER, ROPE GRIPPER, COP AND CALL STATIONS. ALSO PERFORMED 5 YEAR SAFETY TEST | ERIC | ERIC | | HE16 | C | 4252970 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/29/2011 | 5 YR 2-08--OTIS--LIGHT BULB GUARDING IN CAR / POST FLOOR DESIGNATION NUMBERS AT ALL LANDINGS (Receipt #1014941) | TOM | TOM | | H01 | C | 4242574 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/04/2011 | 5 YR 2-08--OTIS | TOM | TOM | | H02 | C | 4154554 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/23/2010 | 5YR 2-08--OTIS (Receipt #948376) | TOM | TOM | | H01 | C | 4078440 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/04/2010 | 5 yr 2-08--otis alarm in car inop / post floor designation numbers at all landings | TOM | TOM | | H02 | C | 3987963 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/05/2009 | TKE 5 YR 2/08. ALARM BELL NOT WORKING (Receipt #884228) | ERIC | ERIC | | H01 | C | 3907726 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/16/2009 | 5 YR EXPIRED LAST TEST 3-02--OTIS--SAME ITEMS AS LAST INSP TO CORRECT | TOM | TOM | | H02 | C | 3835391 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/29/2008 | same items as last insp--barry @ otis called (Receipt #837421) | TOM | TOM | | H01 | C | 3775918 |
COLORADO SPRINGS UTILITIES | H02 | C | 11/23/2004 | 5 YR--3--02--OTIS--NOTHING HAS CHANGED ALSO NOW THE A/C UNIT IS FROZEN UP SOLID | JOHNW | JOHNW | | H02 | C | 1275296 |
COLORADO SPRINGS UTILITIES | H01 | C | 05/08/2004 | 5YR 3-02--OTIS---CONDENSATE LEAKING FROM THE A/C UNIT THAT SERVES ELEVATOR EQUIPMENT ROOM ----BASEMENT LANDING OUTER DOOR DOESEN'T AUTO OPEN | JOHNW | JOHNW | | H01 | C | 1275289 |
COLORADO SPRINGS UTILITIES | H02 | C | 06/25/2003 | 5 YR 3-02 | LES | LES | | H02 | C | 1275282 |
COLORADO SPRINGS UTILITIES | H01 | P | 11/08/2002 | 5 YR 3-02--OTIS--2 WWY--ALARM INOP--EMER LIGHTS INOP | TOM | TOM | | H01 | P | 1275266 |
COLORADO SPRINGS UTILITIES | H03 | C | 11/08/2002 | | TOM | TOM | | H03 | C | 1275274 |
COLORADO SPRINGS UTILITIES | H02 | P | 05/31/2002 | ELEV IS STUCK BETWEEN FLOORS 6 & 7--UNABLE TO CALL UP OR DOWN | TOM | TOM | | H02 | P | 1275259 |
COLORADO SPRINGS UTILITIES | H01 | P | 11/29/2001 | 5 YR 12-96--NEED 2 WAY COMM--ALARM INOP--EMERGENCY LIGHTS INOP | TOM | TOM | | H01 | P | 1275251 |
COLORADO SPRINGS UTILITIES | H02 | C | 11/30/2000 | | TOM | TOM | | H02 | C | 1275243 |
COLORADO SPRINGS UTILITIES | H01 | C | 05/02/2000 | 5 YR 12-96 | TOM | TOM | | H01 | C | 1275234 |
COLORADO SPRINGS UTILITIES | H02 | C | 11/02/1999 | 5-YR 12-96--DOVER | TOM | TOM | | H02 | C | 1275226 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/07/1999 | | RUSS | RUSS | | H02 | C | 1275196 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/16/1998 | | DAVEL | DAVEL | | H01 | C | 1275218 |
COLORADO SPRINGS UTILITIES | H02 | C | 05/11/1998 | | DAVEL | DAVEL | | H02 | C | 1275188 |
COLORADO SPRINGS UTILITIES | H01 | C | 11/24/1997 | | RUSS | RUSS | | H01 | C | 1275211 |
COLORADO SPRINGS UTILITIES | H01 | C | 05/21/1997 | INITIAL INSPECTION, PERMIT ISSUED, ORDER: CLOSE 6" GAP IN SHAFT ON LOADING DOCK SIDE. | RUSS | RUSS | | H01 | C | 1275204 |