MEMORIAL HOSPITAL | H02 | C | 03/06/2024 | HO2 -- ANNUAL 11/23 -- OTIS W/ TKE SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, AND ELEVATOR TWO-WAY COMMUNICATION. / -- MISSING TEST REPORT FROM WITNESS TEST LAST YEAR (Receipt #2040680) | BENH | BENH | | H02 | C | 8016379 |
MEMORIAL HOSPITAL | H03 | C | 11/08/2023 | ANNUAL 10/22 -- OTIS W/ TKE SERVICE -- WAS ON-SITE FOR RE-INSPECTION OF ELEVATOR SINCE ELEVATOR WAS OUT OF SERVICE AT MY LAST VISIT -- MISSING WITNESS TEST REPORT IN M.C.P FROM 10/2022 -- ANNUAL TRACTION SAFETY TEST IS PAST DUE AND PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL TEST HAS BEEN COMPLETED | BENH | BENH | | H03 | C | 7912935 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2023 | ANNUAL 10/22 -- OTIS W/ TKE SERVICE -- ELEVATOR WAS SHUTDOWN FOR REPAIRS -- HOLD PERMIT TO OPERATE UNTIL ELEVATOR IS FIXED AND OWNER HAS CONTACTED P.P.R.B.D. TO COME OUT AND RE-INSPECT ELEVATOR (Receipt #1989683) | BENH | BENH | | H01 | C | 7861078 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2023 | HO2 -- 5YR -- 10/22 -- ANNUAL 10/22 -- OTIS W/ TKE SERVICE | BENH | BENH | | H02 | C | 7701056 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - ELEVATOR OPERATING CORRECTLY ON GENERATOR POWER PER THE INSTALLATION CODE YEAR | ROBERTV | ROBERTV | | HE16 | C | 7657049 |
MEMORIAL HOSPITAL | H06 | C | 10/31/2022 | WITNESSED ANNUAL 5 YEAR TEST W/ TKE -- PIT LIGHT IS OUT (Receipt #1910909) | BENH | BENH | | H06 | C | 7567165 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2022 | ANNUAL 6/22 -- OTIS W/ TKE SERVICE -- 4TH FLOOR HOISTWAY FAST DOOR GIBB LOOSE (Receipt #1897747) | BENH | BENH | | H01 | C | 7509970 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2022 | HO2 -- OTIS W/ TKE SERVICE -- SEE PREVIOUS NOTES cat 1 6/22 | BENH | BENH | | H02 | C | 7320923 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2021 | 5YR -- 11/17 -- CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. 4TH FLOOR HOISTWAY FAST DOOR GIB LOOSE (Receipt #1809976) | ROBERTV | ROBERTV | | H01 | C | 7120652 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING IS SHOWING 3 MONTHS PAST DUE.......... 30 DAYS TO ADDRESS (Cat1 performed 4/2021) | ROBERTV | ROBERTV | | H02 | C | 6902345 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/TKE SERVICE. NO PIT LIGHT. NEED UP TO DATE FIRE SERVICE TESTING LOG. NEED QUARTERLY EMERGENCY PHONE TESTING LOG. NEED ELEVATOR EMERGENCY POWER TESTING LOG. (Receipt #1713665) | ROBERTV | ROBERTV | | H01 | C | 6708524 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | ANNUAL INSPECTION CONDUCTED ON 9/25/2019 FAILED TO GENERATE AN INVOICE, THIS ENTRY IS TO CORRECT THE ISSUE (Receipt #1663663) (Cat. 1 Performed 12/2019) | ERIC | ERIC | | H01 | C | 6488378 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | 5YR 11/17--ANNUAL 12/18--OTIS W/ TKE SERVICE--MISSING SAFETY RETAINERS FLOORS 1 & 2--ANTI-ROTATION CABLE IN MACHINE ROOM COMING APART (Receipt #1566017 from 12/27/2018) | CALE | CALE | | H01 | C | 6346729 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2019 | 5 YEAR 11/17, ANNUAL 12/18, OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 6142607 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2018 | 5YR -- 11/17 -- OTIS W/ TKE SERVICE. (Receipt #1566017)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 5972534 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2018 | H02 -- 5YR -- 11/17 -- ROPES AND SHEAVES HAVE BEEN REPLACED | ROBERTV | ROBERTV | | H02 | C | 5783821 |
MEMORIAL HOSPITAL | HE16 | C | 01/05/2018 | ROPES AND SHEAVE REPLACED | ERIC | ERIC | | HE16 | C | 5729701 |
MEMORIAL HOSPITAL | H06 | C | 11/13/2017 | WITNESSED 5 YEAR SAFETY TEST. THE ROPE NOISE ISSUE HAS RE-EMERGED AND EXTREME ROPE WEAR IS EVIDENT, ROPES SHALL BE RE-INSPECTED MONTHLY TO MONITOR WEAR (Receipt #1465277) | ERIC | ERIC | | H06 | C | 5682524 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2017 | 5 YEAR SCHEDULED FOR 10/17 (Receipt #1454960) | ERIC | ERIC | | H01 | C | 5635616 |
MEMORIAL HOSPITAL | H02 | C | 03/27/2017 | 5YR -- 6/12 -- OTIS W/ TKE SERVICE. CAR TOP SHEAVES ARE STILL OUT OF ALIGNMENT AND NEED TO BE ADDRESSED, REQUIRED ANNUAL CATEGORY 1 TEST HAS YET TO BE PERFORMED AND NEEDS TO BE COMPLETED. | ROBERTV | ROBERTV | | H02 | C | 5456425 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2016 | 5YR -- 6/12 -- OTIS W/ TKE SERVICE. CAR TOP SHEAVES ARE OUT OF ALIGNMENT, DRIVE MACHINE GEAR BOX INPUT SHAFT SEAL LEAKING PROFUSELY, NEED ANNUAL CATEGORY 1 TESTING COMPLETED | ROBERTV | ROBERTV | | H01 | C | 5306449 |
MEMORIAL HOSPITAL | H02 | C | 03/09/2016 | 5 YEAR 6/12 OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 5151420 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2015 | 5 YEAR 6/12 OTIS. TKE SERVICE (Receipt #1288943) | ERIC | ERIC | | H01 | C | 5042693 |
MEMORIAL HOSPITAL | H02 | C | 03/26/2015 | 5 YEAR 6/12 OTIS. TKE SERVICE. ROPES HAVE BEEN REPLACED | ERIC | ERIC | | H02 | C | 4924227 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2014 | 5 YEAR 6/12 OTIS. TKE SERVICE. ALARM BELL AND EMERGENCY LIGHTS NOT WORKING, SUSPENSION ROPES ARE STRETCHED PAST ALLOWABLE TOLERANCE AND MUST BE REPLACED, ALSO NEED TO FULLY INSPECT DRIVE SHEAVE, CLEAN CAR TOP (Receipt #1222672) | ERIC | ERIC | | H01 | C | 4824321 |
MEMORIAL HOSPITAL | H02 | C | 03/13/2014 | H02 5 YR 6/12 OTIS. TKE SERVICE | ERIC | ERIC | | H02 | C | 4701621 |
MEMORIAL HOSPITAL | H01 | C | 09/26/2013 | 5YR 6-12-OTIS SLIGHT ROUGE ON ROPES (Receipt #1156764) | TOM | TOM | | H01 | C | 4612767 |
MEMORIAL HOSPITAL | H02 | C | 03/26/2013 | 5YR 6-12-OTIS | TOM | TOM | | H02 | C | 4496975 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2012 | 5YR 6-12--OTIS POST FIRE SIGNS AT ALL LANDINGS (Receipt #1082942) | TOM | TOM | | H01 | C | 4392069 |
MEMORIAL HOSPITAL | H06 | C | 06/13/2012 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS AND ALARM BELL NOT WORKING WITH CAB CIRCUIT TURNED OFF (Receipt #1051844) | ERIC | ERIC | | H06 | C | 4326853 |
MEMORIAL HOSPITAL | H02 | C | 03/09/2012 | 5 YR 5-07--OTIS | TOM | TOM | | H02 | C | 4290630 |
MEMORIAL HOSPITAL | H01 | C | 09/15/2011 | 5 YR 5-07--OTIS (Receipt #1003046) | TOM | TOM | | H01 | C | 4215317 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2011 | 5 YR 5-07--OTIS--SEQUENCE NUMBER GOVENOR | TOM | TOM | | H02 | C | 4129162 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2010 | 5 YR 5-07--OTIS--SUMP PIT FULL OF WATER / PUMP NOT WORKING (Receipt #936195) | TOM | TOM | | H01 | C | 4049231 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2010 | 5 YEAR 5/07 OTIS. | ERIC | ERIC | | H02 | C | 3960700 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2009 | 5 YR 5-07--OTIS (Receipt #878688) | TOM | TOM | | H01 | C | 3892323 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2009 | 5YR 5-07--OTIS | TOM | TOM | | H02 | C | 3818702 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2008 | 5yr--5--07--otis and lockbox #21 (Receipt #828355) | TOM | TOM | | H01 | C | 3747602 |
MEMORIAL HOSPITAL | H02 | C | 03/14/2008 | 5 YR 5-07 --- OTIS LOCKBOX --- REPAIR FLOOR IN CAR | LES | LES | | H02 | C | 1318142 |
MEMORIAL HOSPITAL | H01 | C | 09/14/2007 | 5 YR 5-07 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1318134 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2007 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1318126 |
MEMORIAL HOSPITAL | H01 | C | 09/07/2006 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1318119 |
MEMORIAL HOSPITAL | H02 | C | 03/15/2006 | 5 YR 10-02 --- OTIS LOCKBOX --- CAR DOOR NOT CLOSING COMPLETELY ON LL FLOOR | LES | LES | | H02 | C | 1318111 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2005 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1318102 |
MEMORIAL HOSPITAL | H02 | C | 03/28/2005 | 5 YR 10-02 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 1318095 |
MEMORIAL HOSPITAL | H01 | C | 09/28/2004 | 5 YR 10-02 --- 0TIS ELEVATOR AND LOCKBOX | LES | LES | | H01 | C | 1318086 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2004 | 5 YR 10-02 --- OTIS | LES | LES | | H02 | C | 1318079 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2003 | 5 YR 10-02 | LES | LES | | H01 | C | 1318071 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2003 | 5 YR 9-02 | LES | LES | | H02 | C | 1318063 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2002 | 5 YR TEST DUE | LES | LES | | H01 | C | 1318055 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2002 | 5 YR 4-97 | LES | LES | | H02 | C | 1318047 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2001 | 5 YR 4-97 | LES | LES | | H01 | C | 1318041 |
MEMORIAL HOSPITAL | H02 | C | 03/30/2001 | 5 YR 4-97 --- OIL LEAK UNDER MACHINE | LES | LES | | H02 | C | 1318033 |
MEMORIAL HOSPITAL | H01 | P | 09/21/2000 | PHONE INOP. | LES | LES | | H01 | P | 1318025 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2000 | 5 YR 4-97--OTIS | TOM | TOM | | H02 | C | 1318017 |
MEMORIAL HOSPITAL | H01 | C | 09/22/1999 | | RUSS | RUSS | | H01 | C | 1318009 |
MEMORIAL HOSPITAL | H02 | C | 03/01/1999 | | RUSS | RUSS | | H02 | C | 1317993 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1998 | | RUSS | RUSS | | H01 | C | 1317986 |
MEMORIAL HOSPITAL | H02 | C | 02/13/1998 | | RUSS | RUSS | | H02 | C | 1317979 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1997 | INITIAL INSPECTION, PERMIT ISSUED. | RUSS | RUSS | | H01 | C | 1318002 |