MEMORIAL HOSPITAL | H02 | C | 03/06/2024 | HO2 -- ANNUAL 11/23 -- OTIS W/ TKE SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS,AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040695) | BENH | BENH | | H02 | C | 8016408 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2023 | ANNUAL 10/22 -- OTIS W/ TKE SERVICE -- MISSING TEST REPORT FROM 5 YEAR WITNESS TEST -- DRIVE MACHINE IS LEAKING OIL AND MISSING A CATCH PAN (Receipt #1989731) | BENH | BENH | | H01 | C | 7861220 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2023 | HO2 -- 5YR -- 10/22 -- ANNUAL 10/22 -- OTIS W/ TKE SERVICE | BENH | BENH | | H02 | C | 7701128 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - ELEVATOR OPERATING CORRECTLY ON GENERATOR POWER PER THE INSTALLATION CODE YEAR | ROBERTV | ROBERTV | | HE16 | C | 7657055 |
MEMORIAL HOSPITAL | H06 | C | 10/31/2022 | WITNESSED ANNUAL 5 YEAR TEST W/ TKE -- NEED TO CLEAN CAR TOP -- PIT LIGHT IS OUT (Receipt #1910908) | BENH | BENH | | H06 | C | 7567163 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2022 | ANNUAL 6/22 -- OTIS W/ TKE SERVICE -- OIL LEAKING FROM DRIVE MACHINE INPUT SHAFT SEAL & ON MACHINE ROOM FLOOR (Receipt #1897753) | BENH | BENH | | H01 | C | 7509987 |
MEMORIAL HOSPITAL | H02 | C | 03/23/2022 | HO2 -- ANNUAL 4/21 -- OTIS W/ TKE SERVICE -- SEE PREVIOUS NOTES cat 1 6/22 | BENH | BENH | | H02 | C | 7312334 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2021 | 5YR -- 11/17 -- CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. NEED TO UPDATE MAINTENANCE LOGS NOTING DRIVE MACHINE INPUT SHAFT SEAL HAS BEEN REPAIRED. (Receipt #1809977) | ROBERTV | ROBERTV | | H01 | C | 7120666 |
MEMORIAL HOSPITAL | HE16 | C | 04/26/2021 | DRIVE MACHINE INPUT SHAFT SEAL IS LEAKING AND SLINGING OIL ONTO DRIVE MACHINE MAIN BRAKE DRUM. | ROBERTV | ROBERTV | | HE16 | C | 6947684 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING IS SHOWING 3 MONTHS PAST DUE.......... 30 DAYS TO ADDRESS. DRIVE MACHINE INPUT SHAFT IS LEAKING PROFUSELY (Cat1 performed 4/2021, input shaft on Drive Machine still leaking) | ROBERTV | ROBERTV | | H02 | C | 6902350 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/TKE SERVICE. NEED UP TO DATE FIRE SERVICE TESTING LOG. NEED QUARTERLY EMERGENCY PHONE TESTING LOG. NEED ELEVATOR EMERGENCY POWER TESTING LOG. (Receipt #1713667) | ROBERTV | ROBERTV | | H01 | C | 6708525 |
MEMORIAL HOSPITAL | H02 | C | 03/03/2020 | H02 -- 5YR -- 1/17 -- ANNUAL 12/2019 -- OTIS W/ TKE SERVICE | ROBERTV | ROBERTV | | H02 | C | 6498086 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | 5YR 1/17--ANNUAL 12/18--OTIS W/ TKE SERVICE--MISSING SAFETY RETAINER FLOOR 4 (Receipt #1632585) Cat 1 performed 12/2019 | CALE | CALE | | H01 | C | 6346719 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2019 | 5 YEAR 11/17, ANNUAL 12/18, OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 6142606 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2018 | 5YR -- 11/17 -- OTIS W/ TKE SERVICE. (Receipt #1565987)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 5972538 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2018 | H02 - 5YR PERFORMED 11/2017 | ROBERTV | ROBERTV | | H02 | C | 5783827 |
MEMORIAL HOSPITAL | H06 | C | 11/06/2017 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1463983) | ERIC | ERIC | | H06 | C | 5677152 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2017 | 5 YEAR SCHEDULED FOR 10/17 (Receipt #1454961) | ERIC | ERIC | | H01 | C | 5635617 |
MEMORIAL HOSPITAL | H02 | C | 03/27/2017 | 5YR -- 6/12 -- OTIS W/ TKE SERVICE. ELEVATOR SUMP PUMP IS STILL NOT WORKING AND NEEDS TO BE REPAIRED, REQUIRED ANNUAL CATEGORY 1 TESTING HAS YET TO BE PERFORMED AND NEEDS TO BE COMPLETED | ROBERTV | ROBERTV | | H02 | C | 5456439 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2016 | 5YR -- 6/12 -- OTIS W/ TKE SERVICE. MISSING DOOR GIBBS AT FLOOR 4, ELEVATOR PIT HAS WATER IN IT AND SUMP PUMP IS UNPLUGGED, NEED ANNUAL CATEGORY 1 TESTING COMPLETED. | ROBERTV | ROBERTV | | H01 | C | 5306459 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2016 | 5 YEAR 6/12 OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 5151423 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2015 | 5 YEAR 6/12 OTIS. TKE SERVICE (Receipt #1288944) | ERIC | ERIC | | H01 | C | 5042695 |
MEMORIAL HOSPITAL | H02 | C | 03/26/2015 | 5 YEAR 6/12 OTIS. TKE SERVICE. ROPES HAVE BEEN REPLACED | ERIC | ERIC | | H02 | C | 4924228 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2014 | 5 YEAR 6/12 OTIS. TKE SERVICE. ALARM BELL AND EMERGENCY LIGHTS NOT WORKING, SUSPENSION ROPES ARE STRETCHED PAST ALLOWABLE TOLERANCE AND MUST BE REPLACED, CLEAN CAR TOP (Receipt #1222668) | ERIC | ERIC | | H01 | C | 4824312 |
MEMORIAL HOSPITAL | H02 | C | 03/13/2014 | H02 5 YR 6/12 OTIS. TKE SERVICE | ERIC | ERIC | | H02 | C | 4701622 |
MEMORIAL HOSPITAL | H01 | C | 09/26/2013 | 5YR 6-12-OTIS SLIGHT ROUGE ON ROPES (Receipt #1156765) | TOM | TOM | | H01 | C | 4612768 |
MEMORIAL HOSPITAL | H02 | C | 03/26/2013 | 5YR 6-12-OTIS | TOM | TOM | | H02 | C | 4496976 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2012 | 5YR 6-12--OTIS (Receipt #1082943) | TOM | TOM | | H01 | C | 4392070 |
MEMORIAL HOSPITAL | H06 | C | 06/07/2012 | WITNESSED 5 YEAR SAFETY TEST. ALARM BELL AND EMERGENCY LIGHTS NOT WORKING WHEN 110V CIRCUIT IS SHUT OFF. (Receipt #1050078) | ERIC | ERIC | | H06 | C | 4322835 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2012 | 5 YR 5-07--OTIS--PHONE NOW WORKING | TOM | TOM | | H02 | C | 4290624 |
MEMORIAL HOSPITAL | H01 | C | 09/15/2011 | 5 YR 5-07--OTIS--PHONE IN CAR NOT WORKING (Receipt #1003047) | TOM | TOM | | H01 | C | 4215318 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2011 | 5 YR 5=07--OTIS--SEQUENCE NUMBER GOVENOR / PHONE IN CAR NOT WORKING | TOM | TOM | | H02 | C | 4129164 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2010 | 5 YR 5-07--OTIS (Receipt #936196) | TOM | TOM | | H01 | C | 4049234 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2010 | 5 YEAR 5/07 OTIS | ERIC | ERIC | | H02 | C | 3960701 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2009 | 5 YR 5-07--OTIS (Receipt #878689) | TOM | TOM | | H01 | C | 3892324 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2009 | 5YR 5-07--OTIS | TOM | TOM | | H02 | C | 3818703 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2008 | 5yr--5--07--otis and lockbox--#22 (Receipt #828358) | TOM | TOM | | H01 | C | 3747608 |
MEMORIAL HOSPITAL | H02 | C | 03/14/2008 | 5 YR 5-07 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1318445 |
MEMORIAL HOSPITAL | H01 | C | 09/14/2007 | 5 YR 5-07 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1318437 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2007 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1318429 |
MEMORIAL HOSPITAL | H01 | C | 09/07/2006 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1318421 |
MEMORIAL HOSPITAL | H02 | C | 03/20/2006 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1318413 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2005 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1318405 |
MEMORIAL HOSPITAL | H02 | C | 03/28/2005 | 5 YR 10-02 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 1318395 |
MEMORIAL HOSPITAL | H01 | C | 09/28/2004 | 5 YR 10-02 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 1318387 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2004 | 5 YR 10-02 --- OTIS | LES | LES | | H02 | C | 1318380 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2003 | 5 YR 10-02 | LES | LES | | H01 | C | 1318372 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2003 | 5 YR 9-02 | LES | LES | | H02 | C | 1318367 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2002 | 5 YR TEST DUE | LES | LES | | H01 | C | 1318357 |
MEMORIAL HOSPITAL | H02 | C | 03/21/2002 | 5 YR 4-97 | LES | LES | | H02 | C | 1318347 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2001 | 5 YR 4-97 | LES | LES | | H01 | C | 1318340 |
MEMORIAL HOSPITAL | H02 | C | 03/30/2001 | 5 YR 4-97 | LES | LES | | H02 | C | 1318331 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2000 | | LES | LES | | H01 | C | 1318323 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2000 | 5 YR 4-97 OTIS | TOM | TOM | | H02 | C | 1318315 |
MEMORIAL HOSPITAL | H01 | C | 09/22/1999 | | RUSS | RUSS | | H01 | C | 1318305 |
MEMORIAL HOSPITAL | H02 | C | 03/01/1999 | | RUSS | RUSS | | H02 | C | 1318288 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1998 | | RUSS | RUSS | | H01 | C | 1318281 |
MEMORIAL HOSPITAL | H02 | C | 02/13/1998 | | RUSS | RUSS | | H02 | C | 1318272 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1997 | INITAL INSPECTION, PERMIT ISSUED | RUSS | RUSS | | H01 | C | 1318297 |