MEMORIAL HOSPITAL | H02 | C | 03/06/2024 | HO2 -- ANNUAL 12/23 -- OTIS W/ TKE SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040685) | BENH | BENH | | H02 | C | 8016390 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2023 | ANNUAL 10/22 -- OTIS W/TKE SERVICE -- MISSING TEST REPORT FROM 5 YEAR WITNESS TEST 10/31/2022 (Receipt #1989707) | BENH | BENH | | H01 | C | 7861161 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2023 | HO2 -- 5YR -- 10/22 -- ANNUAL 10/22 -- OTIS W/ TKE SERVICE | BENH | BENH | | H02 | C | 7701053 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - ELEVATOR OPERATING CORRECTLY ON GENERATOR POWER PER THE INSTALLATION CODE YEAR | ROBERTV | ROBERTV | | HE16 | C | 7657066 |
MEMORIAL HOSPITAL | H06 | C | 10/31/2022 | WITNESSED ANNUAL 5 YEAR TEST W/ TKE -- ESCAPE HATCH NEEDS TO BE SECURED -- CAR TOP BULB GAURD IS IN CONTACT WITH LIGHT AND MELTING WHEN LIGHT IS TURNED ON (Receipt #1910894) | BENH | BENH | | H06 | C | 7567144 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2022 | ANNUAL 6/22 -- OTIS W/ TKE SERVICE -- CAR TOP LIGHT OUT (Receipt #1897759) | BENH | BENH | | H01 | C | 7510005 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2022 | H02 -- 5YR -- 11/17 -- CAT 1 -- 4/21 -- OTIS W/ TKE SERVICE cat 1 6/22 | DUSTINS | DUSTINS | | H02 | C | 7320938 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2021 | 5YR -- 11/17 -- CAT1 -- 4/21 -- OTIS W/ TKE SERVICE. SUSPENSION ROPES ARE ROUGED AND UNDERSIZED AND WILL NEED REPLACED. 7TH FLOOR HOISTWAY DOOR GIB IS LOOSE. (Receipt #1809985) (Ropes have been replaced RV) | ROBERTV | ROBERTV | | H01 | C | 7120743 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING IS SHOWING 3 MONTHS PAST DUE.......... 30 DAYS TO ADDRESS. (NOTE: SUSPENSION ROPES ARE ROUGED AND AT MINIMUM DIAMETER) (Cat1 performed 4/2021) | ROBERTV | ROBERTV | | H02 | C | 6902361 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/TKE SERVICE. NEED UP TO DATE FIRE SERVICE TESTING LOG. NEED QUARTERLY EMERGENCY PHONE TESTING LOG. NEED ELEVATOR EMERGENCY POWER TESTING LOG....... (NOTE: NEED TO MONITOR WIRE ROPE BREAKS AND DIAMETERS) (Receipt #1713671) | ROBERTV | ROBERTV | | H01 | C | 6708529 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | ANNUAL INSPECTION CONDUCTED ON 9/25/2019 FAILED TO GENERATE AN INVOICE, THIS ENTRY IS TO CORRECT THE ISSUE (Receipt #1663666) (Cat. 1 Performed 12/2019) | ERIC | ERIC | | H01 | C | 6488382 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | 5YR 11/17--ANNUAL 12/18--OTIS W/ TKE SERVICE--MISSING SAFETY RETAINER FLOOR 5--NEED COVER ON TOP OF ESCAPE HATCH CONTACT (OPEN J BOX--WIRES EXPOSED) (Receipt #1565970 from 12/27/2018) | CALE | CALE | | H01 | C | 6346747 |
MEMORIAL HOSPITAL | H02 | C | 03/27/2019 | 5 YEAR 11/17, ANNUAL 12/18 OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 6146450 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2018 | 5YR -- 11/17 -- OTIS W/ TKE SERVICE. DRIVE SHEAVE IS WEARING RAPIDLY, SUSPENSION ROPE DIAMETERS ARE GETTING SMALLER AND WILL BE MONITORED UNTIL REPLACEMENT IS NEEDED PER ASME A17.6 (Receipt #1565970)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 5972523 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2018 | H02 - 5YR PERFORMED 11/2017 | ROBERTV | ROBERTV | | H02 | C | 5783779 |
MEMORIAL HOSPITAL | H06 | C | 11/06/2017 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1463985) | ERIC | ERIC | | H06 | C | 5677154 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2017 | 5 YEAR SCHEDULED FOR 10/17 (Receipt #1454953) | ERIC | ERIC | | H01 | C | 5635607 |
MEMORIAL HOSPITAL | H02 | C | 03/27/2017 | 5YR -- 6/12 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING HAS YET TO BE PERFORMED AND MUST BE COMPLETED, DRIVE MACHINE SHEAVE IS STARTING TO WEAR AND WILL BE MONITORED, COUNTERWEIGHT SIDE ROPES ARE GETTING THIN AT 7TH FLOOR AND WILL ALSO BE MONITORED. | ROBERTV | ROBERTV | | H02 | C | 5456402 |
MEMORIAL HOSPITAL | HE16 | C | 03/16/2017 | Changed H01 to H02 to accommodate owner billing. | ROBERTV | ROBERTV | | HE16 | C | 5442635 |
MEMORIAL HOSPITAL | H02 | C | 09/29/2016 | 5YR -- 6/12 -- OTIS W/ TKE SERVICE. DRIVE MACHINE SHEAVE IS STARTING TO WEAR, DRIVE MACHINE GEAR BOX INPUT SHAFT IS LEAKING PROFUSELY, MISSING HOISTWAY UPPER DOOR RESTRICTOR FLAG AT 3RD FLOOR, SUSPENSION ROPES ARE GETTING THIN AND WILL BE MONITORED UNTIL DEEMED REPLACEMENT NEEDED, NEED ANNUAL CATEGORY 1 TESTING COMPLETED | ROBERTV | ROBERTV | | H02 | C | 5306492 |
MEMORIAL HOSPITAL | H01 | C | 03/29/2016 | 5 YR -- 6/12 -- OTIS W/ TKE SERVICE. MISSING 3RD FLOOR HOISTWAY DOOR RESTRICTOR FLAG, NEED ANNUAL CATEGORY 1 TESTING COMPLETED, NEED MAINTENANCE CONTROL PROGRAM ONSITE. | ROBERTV | ROBERTV | | H01 | C | 5164391 |
MEMORIAL HOSPITAL | H02 | C | 09/23/2015 | 5 YEAR 6/12 OTIS. TKE SERVICE | ERIC | ERIC | | H02 | C | 5042699 |
MEMORIAL HOSPITAL | H01 | C | 03/26/2015 | 5 YEAR 6/12 OTIS. TKE SERVICE. STILL NEED TO INSTALL GUARDS OVER BULBS INSIDE CAR (Receipt #1252767) | ERIC | ERIC | | H01 | C | 4924238 |
MEMORIAL HOSPITAL | H02 | C | 09/29/2014 | 5 YEAR 6/12 OTIS. TKE SERVICE. ALARM BELL AND EMERGENCY LIGHTS NOT WORKING, NEED LIGHT BULB GUARDS IN CAR | ERIC | ERIC | | H02 | C | 4824281 |
MEMORIAL HOSPITAL | H01 | C | 03/31/2014 | 5 YEAR 6/12 OTIS. TKE SERVICE. CAR NOT RUNNING AT TIME OF INSPECTION. NEED CALL STATION FIRE SIGNS AT ALL LANDINGS ( IN CASE OF FIRE, DO NOT USE ELEVATOR, USE STAIRS ) (Receipt #1186553) | ERIC | ERIC | | H01 | C | 4711720 |
MEMORIAL HOSPITAL | H02 | C | 09/26/2013 | 5YR 6-12-OTIS | TOM | TOM | | H02 | C | 4612770 |
MEMORIAL HOSPITAL | H01 | C | 03/26/2013 | 5YR 6-12-OTIS (Receipt #1120255) | TOM | TOM | | H01 | C | 4496978 |
MEMORIAL HOSPITAL | H02 | C | 09/27/2012 | 5YR 6-12--OTIS | TOM | TOM | | H02 | C | 4392072 |
MEMORIAL HOSPITAL | H06 | C | 06/13/2012 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS AND ALARM BELL NOT WORKING WITH CAB CIRCUIT TURNED OFF (Receipt #1051848) | ERIC | ERIC | | H06 | C | 4326855 |
MEMORIAL HOSPITAL | H01 | C | 03/08/2012 | 5 YR 5-07--OTIS--CK ALARM IN CAR NEXT INSP (Receipt #1036483) | TOM | TOM | | H01 | C | 4290626 |
MEMORIAL HOSPITAL | H02 | C | 09/15/2011 | 5 YR 5-07--OTIS | TOM | TOM | | H02 | C | 4215321 |
MEMORIAL HOSPITAL | H01 | C | 03/21/2011 | 5 YR 5-07--OTIS (Receipt #966508) | TOM | TOM | | H01 | C | 4129225 |
MEMORIAL HOSPITAL | H02 | C | 09/17/2010 | 5 YR 5 07--OTIS | TOM | TOM | | H02 | C | 4049244 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2010 | 5 YR 5-07--OTIS (Receipt #936200) | TOM | TOM | | H01 | C | 4049240 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2010 | 5 YEAR 5/07. OTIS | ERIC | ERIC | | H02 | C | 3960690 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2009 | 5 YR 5-07 OTIS LOCKBOX (Receipt #878691) | TOM | TOM | | H01 | C | 3892326 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2009 | 5YR 5-07--OTIS | TOM | TOM | | H02 | C | 3818705 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2008 | 5yr--5--07--otis and lockbox #24 (Receipt #828362) | TOM | TOM | | H01 | C | 3747650 |
MEMORIAL HOSPITAL | H02 | C | 03/14/2008 | 5 YR 5-07 --- OTIS LOCKBOX --- REPAIR FLOOR IN CAR | LES | LES | | H02 | C | 1330035 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2007 | 5 YR 5-07 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1330026 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2007 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1330018 |
MEMORIAL HOSPITAL | H01 | C | 09/07/2006 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1330010 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2006 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1330003 |
MEMORIAL HOSPITAL | H01 | C | 09/28/2005 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1329996 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2005 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1329987 |
MEMORIAL HOSPITAL | H01 | C | 09/24/2004 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1329979 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2004 | 5 YR 10-02 --- OTIS | LES | LES | | H02 | C | 1329972 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2003 | 5 YR 10-02 | LES | LES | | H01 | C | 1329964 |
MEMORIAL HOSPITAL | H02 | C | 03/18/2003 | 5 YR 10-02 | LES | LES | | H02 | C | 1329956 |
MEMORIAL HOSPITAL | H01 | C | 09/24/2002 | 5 YR TEST DUE | LES | LES | | H01 | C | 1329948 |
MEMORIAL HOSPITAL | H02 | C | 03/21/2002 | 5 YR 4-97 | LES | LES | | H02 | C | 1329940 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2001 | 5 YR 4-97 | LES | LES | | H01 | C | 1329933 |
MEMORIAL HOSPITAL | H02 | C | 03/30/2001 | 5 YR 4-97 --- OIL LEAK ON MACHINE | LES | LES | | H02 | C | 1329926 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2000 | | LES | LES | | H01 | C | 1329919 |
MEMORIAL HOSPITAL | H02 | P | 03/29/2000 | 5 YR 4-97--OTIS--PHONE INOP | TOM | TOM | | H02 | P | 1329911 |
MEMORIAL HOSPITAL | H01 | C | 09/22/1999 | | RUSS | RUSS | | H01 | C | 1329903 |
MEMORIAL HOSPITAL | H02 | C | 03/01/1999 | | RUSS | RUSS | | H02 | C | 1329880 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1998 | | RUSS | RUSS | | H01 | C | 1329872 |
MEMORIAL HOSPITAL | H02 | C | 02/13/1998 | | RUSS | RUSS | | H02 | C | 1329864 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1997 | INITIAL INSPECTION, PERMIT ISSUED | RUSS | RUSS | | H01 | C | 1329894 |