MEMORIAL HOSPITAL | H02 | C | 03/06/2024 | HO2 -- ANNUAL 11/23 -- OTIS W/ TKE SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS,AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040691) | BENH | BENH | | H02 | C | 8016395 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2023 | ANNUAL 10/22 -- OTIS W/TKE SERVICE -- MISSING TEST REPORT FROM 5 YEAR WITNESS TEST 10/31/2022 (Receipt #1989722) | BENH | BENH | | H01 | C | 7861185 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2023 | HO2 -- 5YR -- 10/22 -- ANNUAL 10/22 -- OTIS W/ TKE SERVICE | BENH | BENH | | H02 | C | 7701051 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - ELEVATOR OPERATING CORRECTLY ON GENERATOR POWER PER THE INSTALLATION CODE YEAR | ROBERTV | ROBERTV | | HE16 | C | 7657081 |
MEMORIAL HOSPITAL | H06 | C | 10/31/2022 | WITNESSED ANNUAL 5 YEAR TEST W/ TKE -- CLEAN CAR TOP -- MISSING SAFETY RETAINER ON 6TH FLOOR HOISTWAY DOOR -- S.O.S. SWITCH COVER IS MISSING (Receipt #1910901) | BENH | BENH | | H06 | C | 7567153 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2022 | ANNUAL 4/22 -- OTIS W/ TKE SERVICE (Receipt #1897763) | BENH | BENH | | H01 | C | 7510039 |
MEMORIAL HOSPITAL | H02 | C | 03/23/2022 | HO2 -- ANNUAL 3/21 -- OTIS W/ TKE SERVICE -- NOTE: ANNUAL CAT 1 SAFETY TEST DUE BY END OF THE MONTH cat 1 4/22 | BENH | BENH | | H02 | C | 7312273 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2021 | 5YR -- 11/17 -- CAT1 -- 3/21 -- OTIS W/ TKE SERVICE. (Receipt #1810001) | ROBERTV | ROBERTV | | H01 | C | 7120806 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 3/21 -- OTIS W/ TKE SERVICE.
| ROBERTV | ROBERTV | | H02 | C | 6902368 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/TKE SERVICE. "B" FLOOR HOISTWAY LOWER DOOR GIBBS LOOSE. NEED UP TO DATE FIRE SERVICE TESTING LOG. NEED QUARTERLY EMERGENCY PHONE TESTING LOG. NEED ELEVATOR EMERGENCY POWER TESTING LOG. (Receipt #1713673) | ROBERTV | ROBERTV | | H01 | C | 6708532 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | ANNUAL INSPECTION CONDUCTED ON 9/25/2019 FAILED TO GENERATE AN INVOICE, THIS ENTRY IS TO CORRECT THE ISSUE (Receipt #1663670) (Cat. 1 Performed 12/2019) | ERIC | ERIC | | H01 | C | 6488386 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | 5YR 11/17--ANNUAL 12/18--OTIS W/ TKE SERVICE (Receipt #1565974 from 12/27/2018) | CALE | CALE | | H01 | C | 6346758 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2019 | 5 YEAR 11/17, ANNUAL 12/18, OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 6142600 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2018 | 5YR -- 11/17 -- OTIS W/ TKE SERVICE. (Receipt #1565974)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 5972547 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2018 | H02 - 5YR PERFORMED 11/2017 | ROBERTV | ROBERTV | | H02 | C | 5783829 |
MEMORIAL HOSPITAL | H06 | C | 11/06/2017 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1463976) | ERIC | ERIC | | H06 | C | 5677142 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2017 | 5 YEAR SCHEDULED FOR 10/17 (Receipt #1454955) | ERIC | ERIC | | H01 | C | 5635610 |
MEMORIAL HOSPITAL | H02 | C | 03/27/2017 | 5YR -- 6/12 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING HAS YET TO BE PERFORMED AND NEEDS TO BE COMPLETED. ALARM BELL NOT WORKING. | ROBERTV | ROBERTV | | H02 | C | 5456453 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2016 | 5YR -- 6/12 -- OTIS W/ TKE SERVICE. MISSING DOOR GIBB AT FLOOR 6, ALARM BELL NOT WORKING, NEED ANNUAL CATEGORY 1 TESTING COMPLETED. | ROBERTV | ROBERTV | | H01 | C | 5306513 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2016 | 5 YEAR 6/12 OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 5151434 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2015 | 5 YEAR 6/12 OTIS. TKE SERVICE (Receipt #1288947) | ERIC | ERIC | | H01 | C | 5042703 |
MEMORIAL HOSPITAL | H02 | C | 03/26/2015 | 5 YEAR 6/12 OTIS. TKE SERVICE. STILL NEED TO INSTALL GUARDS OVER BULBS INSIDE CAR | ERIC | ERIC | | H02 | C | 4924240 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2014 | 5 YEAR 6/12 OTIS. TKE SERVICE. ALARM BELL AND EMERGENCY LIGHTS NOT WORKING, NEED LIGHT BULB GUARDS IN CAR (Receipt #1222653) | ERIC | ERIC | | H01 | C | 4824271 |
MEMORIAL HOSPITAL | H02 | C | 03/13/2014 | H02 5 YR 6/12 OTIS. TKE SERVICE | ERIC | ERIC | | H02 | C | 4701624 |
MEMORIAL HOSPITAL | H01 | C | 09/20/2013 | 5YR 6-12-OTIS (Receipt #1156749) | TOM | TOM | | H01 | C | 4612752 |
MEMORIAL HOSPITAL | H02 | C | 03/27/2013 | 5YR 6-12-OTIS--ALARM IN CAR NOR WORKING | TOM | TOM | | H02 | C | 4496980 |
MEMORIAL HOSPITAL | H01 | C | 09/26/2012 | 5YR 6-12--PHONE IN CAR NOT WORKING / ALARM IN CAR NOT WORKING (Receipt #1082935) | TOM | TOM | | H01 | C | 4392064 |
MEMORIAL HOSPITAL | H06 | C | 06/14/2012 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS AND ALARM BELL NOT WORKING WITH CAB CIRCUIT TURNED OFF (Receipt #1051852) | ERIC | ERIC | | H06 | C | 4326860 |
MEMORIAL HOSPITAL | H02 | C | 03/09/2012 | 5 YR 5-07--OTIS | TOM | TOM | | H02 | C | 4290628 |
MEMORIAL HOSPITAL | H01 | C | 09/15/2011 | 5YR 5-07--OTIS (Receipt #1003051) | TOM | TOM | | H01 | C | 4215328 |
MEMORIAL HOSPITAL | H02 | C | 03/21/2011 | 5 YR 5--07--OTIS | TOM | TOM | | H02 | C | 4129231 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2010 | 5 YR 5-07--OTIS (Receipt #936180) | TOM | TOM | | H01 | C | 4049218 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2010 | 5 YEAR 5/07. OTIS. NEED LIGHT BULB GUARDS IN CAR | ERIC | ERIC | | H02 | C | 3960522 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2009 | 5 YR 5-07--OTIS CAR BEING SERVICED (Receipt #878692) | TOM | TOM | | H01 | C | 3892328 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2009 | 5YR 5-07--OTIS | TOM | TOM | | H02 | C | 3818708 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2008 | 5yr--5--07--otis and lockbox #26 (Receipt #828382) | TOM | TOM | | H01 | C | 3747740 |
MEMORIAL HOSPITAL | H02 | C | 03/13/2008 | 5 YR 5-07 --- 0TIS LOCKBOX | LES | LES | | H02 | C | 1330616 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2007 | 5 YR 5-07 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1330608 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2007 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1330600 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2006 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1330592 |
MEMORIAL HOSPITAL | H02 | C | 03/16/2006 | 5 YR 10-02 --- OTIS LOCKBOX --- ELEVATOR STALLED ON 4TH FLOOR --- PROBLEM WITH HALLWAY DOOR | LES | LES | | H02 | C | 1330584 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2005 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1330576 |
MEMORIAL HOSPITAL | H02 | C | 03/23/2005 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1330567 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2004 | 5 YR 10-02 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 1330560 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2004 | 5 YR 10-02 --- OTIS --- ONE LIGHT OUT IN CAR | LES | LES | | H02 | C | 1330553 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2003 | 5 YR 10-02 --- NEED LIGHT BULB GUARDS --- ONE LIGHT OUT IN CAR | LES | LES | | H01 | C | 1330546 |
MEMORIAL HOSPITAL | H02 | C | 03/18/2003 | 5 YR 10-02 | LES | LES | | H02 | C | 1330539 |
MEMORIAL HOSPITAL | H01 | C | 09/24/2002 | 5 YR TEST DUE | LES | LES | | H01 | C | 1330532 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2002 | 5 YR 4-97 | LES | LES | | H02 | C | 1330525 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2001 | 5 YR 4-97 | LES | LES | | H01 | C | 1330518 |
MEMORIAL HOSPITAL | H02 | C | 03/30/2001 | 5 YR 4-97 --- NEED LIGHT BULB GUARDS | LES | LES | | H02 | C | 1330511 |
MEMORIAL HOSPITAL | H01 | P | 09/19/2000 | 5 YR 4-97--OTIS--PHONE INOP | TOM | TOM | | H01 | P | 1330504 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2000 | 5 YR 4-97--OTIS | TOM | TOM | | H02 | C | 1330496 |
MEMORIAL HOSPITAL | H01 | C | 09/23/1999 | | RUSS | RUSS | | H01 | C | 1330489 |
MEMORIAL HOSPITAL | H02 | C | 03/01/1999 | | RUSS | RUSS | | H02 | C | 1330455 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1998 | | RUSS | RUSS | | H01 | C | 1330447 |
MEMORIAL HOSPITAL | H02 | C | 02/13/1998 | | RUSS | RUSS | | H02 | C | 1330438 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1997 | INITIAL INSPECTION, PERMIT ISSUED | RUSS | RUSS | | H01 | C | 1330482 |