MEMORIAL HOSPITAL | H02 | C | 03/06/2024 | HO2 -- ANNUAL 11/23 -- OTIS W/ TKE SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS,AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040692) | BENH | BENH | | H02 | C | 8016396 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2023 | ANNUAL 10/22 -- OTIS W/TKE SERVICE -- MISSING TEST REPORT FROM 5 YEAR WITNESS TEST 10/31/2022 (Receipt #1989724) | BENH | BENH | | H01 | C | 7861192 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2023 | HO2 -- 5YR -- 10/22 -- ANNUAL 10/22 -- OTIS W/ TKE SERVICE | BENH | BENH | | H02 | C | 7701047 |
MEMORIAL HOSPITAL | HE16 | C | 02/05/2023 | WITNESSED ELEVATOR OPERATION ON GENERATOR POWER W/ FACILITY ENGINEERS - ELEVATOR OPERATING CORRECTLY ON GENERATOR POWER PER THE INSTALLATION CODE YEAR | ROBERTV | ROBERTV | | HE16 | C | 7657085 |
MEMORIAL HOSPITAL | H06 | C | 10/31/2022 | WITNESSED ANNUAL 5 YEAR TEST W/ TKE -- EMERGENCY LIGHT IS NONFUNCTIONAL (Receipt #1910902) | BENH | BENH | | H06 | C | 7567155 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2022 | ANNUAL 4/22 -- OTIS W/ TKE SERVICE (Receipt #1897764) | BENH | BENH | | H01 | C | 7510042 |
MEMORIAL HOSPITAL | H02 | C | 03/23/2022 | HO2 -- ANNUAL 3/21 -- OTIS W/ TKE SERVICE -- NOTE: ANNUAL TRACTION SAFETY TEST IS DUE BY THE END OF THE MONTH cat 1 4/22 | BENH | BENH | | H02 | C | 7312284 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2021 | 5YR -- 11/17 -- CAT1 -- 3/21 -- OTIS W/ TKE SERVICE. (Receipt #1810003) | ROBERTV | ROBERTV | | H01 | C | 7120820 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2021 | H02 -- 5YR -- 11/17 -- CAT1 -- 3/21 -- OTIS W/ TKE SERVICE. | ROBERTV | ROBERTV | | H02 | C | 6902369 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2020 | 5YR -- 11/17 -- CAT1 -- 12/19 -- OTIS W/TKE SERVICE. SECURE TOP OF CAR ESCAPE HATCH. NEED UP TO DATE FIRE SERVICE TESTING LOG. NEED QUARTERLY EMERGENCY PHONE TESTING LOG. NEED ELEVATOR EMERGENCY POWER TESTING LOG. (Receipt #1713674) | ROBERTV | ROBERTV | | H01 | C | 6708533 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | ANNUAL INSPECTION CONDUCTED ON 9/25/2019 FAILED TO GENERATE AN INVOICE, THIS ENTRY IS TO CORRECT THE ISSUE (Receipt #1663671) (Cat. 1 Performed 12/2019) | ERIC | ERIC | | H01 | C | 6488388 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2019 | 5YR 11/17--ANNUAL 12/18--OTIS W/ TKE SERVICE (Receipt #1565975 from 12/27/2018) | CALE | CALE | | H01 | C | 6346757 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2019 | 5 YEAR 11/17, ANNUAL 12/18, OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 6142602 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2018 | 5YR -- 11/17 -- OTIS W/ TKE SERVICE. (Receipt #1565975)--(Cat 1 completed 12-18) | ROBERTV | ROBERTV | | H01 | C | 5972548 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2018 | H02 - 5YR PERFORMED 11/2017 | ROBERTV | ROBERTV | | H02 | C | 5783833 |
MEMORIAL HOSPITAL | H06 | C | 11/06/2017 | WITNESSED 5 YEAR SAFETY TEST (Receipt #1463974) | ERIC | ERIC | | H06 | C | 5677136 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2017 | 5 YEAR SCHEDULED FOR 10/17 (Receipt #1454956) | ERIC | ERIC | | H01 | C | 5635611 |
MEMORIAL HOSPITAL | H02 | C | 03/27/2017 | 5YR -- 6/12 -- OTIS W/ TKE SERVICE. REQUIRED ANNUAL CATEGORY 1 TESTING HAS YET TO BE PERFORMED AND MUST BE COMPLETED, ROPES ARE ONSITE FOR REPLACEMENT | ROBERTV | ROBERTV | | H02 | C | 5456461 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2016 | 5YR -- 6/12 -- OTIS W/ TKE SERVICE. COUNTERWEIGHT SIDE SUSPENSION ROPES ARE ROUGED AND UNDERSIZED BETWEEN FLOOR LEVEL 4 AND 5, - (ALL SUSPENSION ROPES NEED REPLACED WITHIN 90 DAYS), NEED ANNUAL CATEGORY 1 TESTING COMPLETED. (Receipt #1366639) | ROBERTV | ROBERTV | | H01 | C | 5306517 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2016 | 5 YEAR 6/12 OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 5151435 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2015 | 5 YEAR 6/12 OTIS. TKE SERVICE (Receipt #1288948) | ERIC | ERIC | | H01 | C | 5042706 |
MEMORIAL HOSPITAL | H02 | C | 03/26/2015 | 5 YEAR 6/12 OTIS. TKE SERVICE. STILL NEED TO INSTALL GUARDS OVER BULBS INSIDE CAR | ERIC | ERIC | | H02 | C | 4924241 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2014 | 5 YEAR 6/12 OTIS. TKE SERVICE. ALARM BELL AND EMERGENCY LIGHTS NOT WORKING, NEED LIGHT BULB GUARDS IN CAR (Receipt #1222650) | ERIC | ERIC | | H01 | C | 4824267 |
MEMORIAL HOSPITAL | H02 | C | 03/13/2014 | H02 5 YR 6/12 OTIS. TKE SERVICE | ERIC | ERIC | | H02 | C | 4701625 |
MEMORIAL HOSPITAL | H01 | C | 09/20/2013 | 5YR 6-12-OTIS (Receipt #1156750) | TOM | TOM | | H01 | C | 4612753 |
MEMORIAL HOSPITAL | H02 | C | 03/27/2013 | 5YR 6-12-OTIS | TOM | TOM | | H02 | C | 4496981 |
MEMORIAL HOSPITAL | H01 | C | 09/26/2012 | 5YR 6-12--OTIS (Receipt #1082936) | TOM | TOM | | H01 | C | 4392065 |
MEMORIAL HOSPITAL | H06 | C | 06/14/2012 | WITNESSED 5 YEAR SAFETY TEST. EMERGENCY LIGHTS AND ALARM BELL NOT WORKING WITH CAB CIRCUIT TURNED OFF (Receipt #1051854) | ERIC | ERIC | | H06 | C | 4326861 |
MEMORIAL HOSPITAL | H02 | C | 03/09/2012 | 5 YR 5-07--OTIS | TOM | TOM | | H02 | C | 4290629 |
MEMORIAL HOSPITAL | H01 | C | 09/15/2011 | 5 YR 5-07--OTIS (Receipt #1003052) | TOM | TOM | | H01 | C | 4215330 |
MEMORIAL HOSPITAL | H02 | C | 03/21/2011 | 5 YR 5-07--OTIS | TOM | TOM | | H02 | C | 4129233 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2010 | 5 YR 5-07--OTIS (Receipt #936183) | TOM | TOM | | H01 | C | 4049220 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2010 | 5 YEAR 5/07 OTIS | ERIC | ERIC | | H02 | C | 3960528 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2009 | 5 YR 5-07--OTIS LBG INSTALLED (Receipt #878693) | TOM | TOM | | H01 | C | 3892329 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2009 | 5YR 5-07--OTIS--LIGHT BULB GUARDING IN CAR | TOM | TOM | | H02 | C | 3818709 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2008 | 5yr--5--07--otis #27--light bulb guards in car missing (Receipt #828386) | TOM | TOM | | H01 | C | 3747751 |
MEMORIAL HOSPITAL | H02 | C | 03/14/2008 | 5 YR 5-07 ---OTIS LOCKBOX --- NEED LIGHT BULB GUARDS IN CAR | LES | LES | | H02 | C | 1330785 |
MEMORIAL HOSPITAL | H01 | C | 09/14/2007 | 5 YR 5-07 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1330779 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2007 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1330771 |
MEMORIAL HOSPITAL | H01 | C | 09/11/2006 | 5 YR 10-02 --- OTIS LOCKBOX --- CAR STALLED ON 4TH FLOOR | LES | LES | | H01 | C | 1330761 |
MEMORIAL HOSPITAL | H02 | C | 03/15/2006 | 5 YR 10-02 --- OTIS LOCKBOX --- NEED LIGHT BULB GUARDS IN CAR | LES | LES | | H02 | C | 1330754 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2005 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1330747 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2005 | 5 YR 10-02 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1330739 |
MEMORIAL HOSPITAL | H01 | C | 09/28/2004 | 5 YR 10-02 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 1330733 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2004 | 5 YR 10-02 --- OTIS | LES | LES | | H02 | C | 1330724 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2003 | 5 YR 10-02 --- NEED LIGHT BULB GUARDS | LES | LES | | H01 | C | 1330716 |
MEMORIAL HOSPITAL | H02 | C | 03/18/2003 | 5 YR 10-02 | LES | LES | | H02 | C | 1330709 |
MEMORIAL HOSPITAL | H01 | C | 09/24/2002 | 5 YR TEST DUE | LES | LES | | H01 | C | 1330702 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2002 | 5 YR 4-97 --- OIL ON FLOOR IN MACHINE ROOM AROUND THIS UNIT | LES | LES | | H02 | C | 1330695 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2001 | 5 YR 4-97 --- OTIS | LES | LES | | H01 | C | 1330686 |
MEMORIAL HOSPITAL | H02 | C | 03/30/2001 | 5 YR 4-97 | LES | LES | | H02 | C | 1330678 |
MEMORIAL HOSPITAL | H01 | P | 09/19/2000 | 5 YR 4-97--OTIS--PHONE INOP | TOM | TOM | | H01 | P | 1330670 |
MEMORIAL HOSPITAL | H02 | P | 03/29/2000 | 5 YR 4-97--OTIS--PHONE INOP | TOM | TOM | | H02 | P | 1330662 |
MEMORIAL HOSPITAL | H01 | C | 09/23/1999 | | RUSS | RUSS | | H01 | C | 1330654 |
MEMORIAL HOSPITAL | H02 | C | 03/01/1999 | | RUSS | RUSS | | H02 | C | 1330638 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1998 | | RUSS | RUSS | | H01 | C | 1330630 |
MEMORIAL HOSPITAL | H02 | C | 02/13/1998 | | RUSS | RUSS | | H02 | C | 1330624 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1997 | INITIAL INSPECTION, PERMIT ISSUED | RUSS | RUSS | | H01 | C | 1330647 |