MEMORIAL HOSPITAL | H02 | C | 03/06/2024 | HO2 -- ANNUAL 1/24 -- OTIS W/ TKE SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS,AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040697) | BENH | BENH | | H02 | C | 8016412 |
MEMORIAL HOSPITAL | H03 | C | 11/08/2023 | ANNUAL 1/23 -- TKE & LOCKBOX -- WAS ON-SITE FOR RE-INSPECTION SINCE ELEVATOR WAS OUT OF SERVICE LAST TIME I WAS ON-SITE -- LOWER LEVEL HOISTWAY DOOR EXCEEDS 1" PER PANEL OPENING -- MECHANIC NOTE: DOOR OPERATOR BELTS IS CLOSE TO BREAKING | BENH | BENH | | H03 | C | 7912927 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2023 | ANNUAL 1/23 -- TKE & LOCKBOX -- UPON ARRIVAL ELEVATOR WAS DOWN FOR REPAIRS (Receipt #1989728) | BENH | BENH | | H01 | C | 7861201 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2023 | HO2 -- ANNUA;L 1/23 -- TKE & LOCKBOX | BENH | BENH | | H02 | C | 7701123 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2022 | ANNUAL 1/22 -- TKE & LOCKBOX -- HOISTWAY DOOR GAP EXCEEDS 1" PER PANEL (Receipt #1897734) cat 1 -- 1/23 DS | BENH | BENH | | H01 | C | 7509910 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2022 | H02 -- CAT 1 -- 1/22 -- TKE AND LOCKBOX | DUSTINS | DUSTINS | | H02 | C | 7321025 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2021 | CAT1 -- 1/21 -- TKE AND LOCKBOX. TOP FLOOR FAST HOISTWAY DOOR MISSING GIB. "B" FLOOR HOISTWAY DOOR PICKUP ROLLERS ARE MISSING. BUILDING ENGINEER TO CHECK MACHINE ROOM EXHAUST FAN FOR PROPER AIRFLOW (ROOM IS VERY HOT) (Receipt #1809963) (cat 1 -- 1/2022 check items listed at next inspection) | ROBERTV | ROBERTV | | H01 | C | 7120582 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2021 | H02 -- CAT1 -- 1/21 -- TKE AND SERVICE. (GATE LOCK CODE 2002) | ROBERTV | ROBERTV | | H02 | C | 6902331 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2020 | CAT1 -- 3/20 -- TKE. EMERGENCY ALARM BELL STILL NOT WORKING. "M" FLOOR MISSING HOISTWAY DOOR PICKUP ROLLERS. BASEMENT FLOOR HOISTWAY FAST DOOR MISSING LOWER GIBB. NEED FIRE SERVICE TEST LOG. NEED QUARTERLY EMERGENCY PHONE TEST LOG. (Receipt #1713658) (Gate Lock Code 2002) cat 1 1/21 | ROBERTV | ROBERTV | | H01 | C | 6708518 |
MEMORIAL HOSPITAL | H06 | C | 02/03/2020 | WITNESSED CATEGORY 1 HYDRAULIC TEST WITH TKE. BUILDING OWNER TO ADDRESS EMERGENCY PHONE CONNECTIVITY ISSUES. / MISSING FIRE EXTINGUISHER WITHIN MACHINE ROOM. / EMERGENCY ALARM BELL NON-FUNCTIONING. Gate code to enter machine room 2002. | RANDYB | RANDYB | | H06 | C | 6471838 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2019 | ANNUAL INSPECTION CONDUCTED ON 9/27/2019 FAILED TO GENERATE AN INVOICE, THIS ENTRY IS TO CORRECT THE ISSUE (Receipt #1663673) | ERIC | ERIC | | H01 | C | 6488391 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2019 | RP 1/19--DOVER W/ TKE SERVICE--NEED DOOR RESTRICTOR COMPONENTS TO BE RE-INSTALLED-- UC HEALTH FACILITIES NEEDS TO GET MACHINE ROOM VENTILATION OPERABLE (Receipt #1565983 from 12/27/2018) 10/11/19 waive the requirement for door restrictor due to mechanical and use constraints ER | CALE | CALE | | H01 | C | 6350058 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2019 | RP 1/19 TKE, HO2 | ERIC | ERIC | | H02 | C | 6142614 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2018 | RP -- 1/18 -- DOVER W/ TKE SERVICE. UC HEALTH FACILITIES NEEDS TO GET MACHINE ROOM VENTILATION OPERABLE. (Receipt #1565983) (RP 1-19) | ROBERTV | ROBERTV | | H01 | C | 5972554 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2018 | H02 | ROBERTV | ROBERTV | | H02 | C | 5783839 |
MEMORIAL HOSPITAL | H01 | C | 09/26/2017 | RP 1/17 TKE. MACHINE ROOM VENTILATOR MUST BE OPERABLE (Receipt #1455191) | ERIC | ERIC | | H01 | C | 5636668 |
MEMORIAL HOSPITAL | H02 | C | 03/24/2017 | H02 | ROBERTV | ROBERTV | | H02 | C | 5455133 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2016 | RP -- 2/16 -- DOVER W/ TKE SERVICE (NO ISSUES) | ROBERTV | ROBERTV | | H01 | C | 5306534 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2016 | RP -- 2/16 -- TKE. NEED CALL STATION FIRE SIGNS AT ALL LANDINGS, NEED MAINTENANCE CONTROL PROGRAM ONSITE. | ROBERTV | ROBERTV | | H02 | C | 5164399 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2015 | RP 2/15 TKE. NEED CALL STATION FIRE SIGNS AT ALL LANDINGS, THIS IS THE RESPONSIBILITY OF THE HOSPITAL NOT THE ELEVATOR SERVICE CONTRACTOR (Receipt #1288952) | ERIC | ERIC | | H01 | C | 5042712 |
MEMORIAL HOSPITAL | H02 | C | 03/04/2015 | WITNESSED 2/15 | ERIC | ERIC | | H02 | C | 4911392 |
MEMORIAL HOSPITAL | H06 | C | 02/26/2015 | WITNESSED 5 YEAR SAFETY INSPECTION. PHASE 1 RECALL DOES NOT FUNCTION PROPERLY, NEED CAPACITY RATE POSTED INSIDE CAR, NEED CALL STATION FIRE SIGNS AT ALL LANDINGS, NEED DOOR RESTRICTORS INSTALLED | ERIC | ERIC | | H06 | C | 4909372 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2014 | RP 3/14 TKE. MISSING DOOR GIBB AT M LANDING (Receipt #1222640) | ERIC | ERIC | | H01 | C | 4824251 |
MEMORIAL HOSPITAL | H02 | C | 03/13/2014 | H02 DOVER, TKE SERVICE | ERIC | ERIC | | H02 | C | 4701575 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2013 | DOVER--RP EXPIRED LAST TEST 8-12 / SWITCH PLATE COVER MISSING FROM PIT SWITCH (Receipt #1156752) | TOM | TOM | | H01 | C | 4612755 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2013 | RP 8-12-DOVER--SWITCH PLATE COVER PLATE STILL MISSING FROM PIT LIGHT SWITCH / REPAIR ENTRY SILL, CONCRETE HAS DISINTEGRATED / COMBO FOR MACHINE ROOM ACCESS DOES NOT WORK (6978) | TOM | TOM | | H02 | C | 4496968 |
MEMORIAL HOSPITAL | H01 | C | 09/25/2012 | RP 8-12--OTIS (Receipt #1082940) | TOM | TOM | | H01 | C | 4392067 |
MEMORIAL HOSPITAL | H02 | C | 03/07/2012 | RP 8-11--DOVER--SWITCH PLATE COVER MISSING ON PIT LIGHT SWITCH / REPAIR ENTRY SILL (CONCRETE HAS DISINTEGRATED) | TOM | TOM | | H02 | C | 4290621 |
MEMORIAL HOSPITAL | H01 | C | 09/15/2011 | RP 8-11--OTIS--SAFETY EDGE BROKEN / CAPACITY PLAQUE IN CAR (Receipt #1003055) | TOM | TOM | | H01 | C | 4215334 |
MEMORIAL HOSPITAL | H02 | C | 03/18/2011 | RP 7-10--DOVER | TOM | TOM | | H02 | C | 4129207 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2010 | RP 7-10--DOVER--DOOR SAFETY EDGES / DIRECTIONAL LANTERN IN CAR / CAPACITY RATING PLAQUE IN CAR (Receipt #936177) | TOM | TOM | | H01 | C | 4049211 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2010 | RP 7/09. DOVER. OTIS SERVICE AND LOCK BOX. DOOR SAFETY EDGES BROKEN, DIRECTIONAL ARROWS IN CAR BROKEN, NEED CAPACITY RATING POSTED IN CAR | ERIC | ERIC | | H02 | C | 3960602 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2009 | RP TAG MISSING OTIS LOCKBOX (Receipt #878695) | TOM | TOM | | H01 | C | 3892331 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2009 | RP 8-07--OTIS | TOM | TOM | | H02 | C | 3818711 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2008 | rp--4--08--otis--re-number #14 (Receipt #828346) | TOM | TOM | | H01 | C | 3747581 |
MEMORIAL HOSPITAL | H02 | C | 03/14/2008 | RP 8-07 --- OTIS LOCKBOX --- LOCK COMBO 6-9-7-8 | LES | LES | | H02 | C | 1331144 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2007 | RP 8-07 --- OTIS LOCKBOX --- LOCK COMBO 6-9-7-8 | LES | LES | | H01 | C | 1331137 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2007 | RP 9-06 --- OTIS LOCKBOX --- GATE LOCK COMBO. 6-9-7-8 --- SAFETY EDGE BROKEN | LES | LES | | H02 | C | 1331131 |
MEMORIAL HOSPITAL | H01 | C | 09/11/2006 | RP 9-05 --- OTIS LOCKBOX --- DOOR SAFETY EDGE BROKEN | LES | LES | | H01 | C | 1331122 |
MEMORIAL HOSPITAL | H02 | C | 03/20/2006 | RP 9-05 --- OTIS LOCKBOX --- DOOR SAFETY EDGE BROKEN | LES | LES | | H02 | C | 1331115 |
MEMORIAL HOSPITAL | H01 | C | 09/28/2005 | RP TEST DUE --- OTIS ELEVATOR | LES | LES | | H01 | C | 1331107 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2005 | RP 8-04 --- DOVER --- OTIS LOCKBOX | LES | LES | | H02 | C | 1331099 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2004 | RP 8-04 --- DOVER --- OTIS LOCKBOX | LES | LES | | H01 | C | 1331092 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2004 | RP 8-03 --- DOVER | LES | LES | | H02 | C | 1331084 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2003 | RP 8-03 | LES | LES | | H01 | C | 1331076 |
MEMORIAL HOSPITAL | H02 | C | 03/18/2003 | RP 7-02 | LES | LES | | H02 | C | 1331068 |
MEMORIAL HOSPITAL | H01 | C | 09/24/2002 | RP 7-02 | LES | LES | | H01 | C | 1331060 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2002 | RP 7-01 --- NEED SIGNS | LES | LES | | H02 | C | 1331052 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2001 | RP 7-01 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1331044 |
MEMORIAL HOSPITAL | H02 | C | 03/30/2001 | RP 3-00 ---- UNIT #14 | LES | LES | | H02 | C | 1331037 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2000 | RP 3-00--DOVER--CAR IS MARKED # 14 | TOM | TOM | | H01 | C | 1331029 |
MEMORIAL HOSPITAL | H02 | C | 03/30/2000 | POWER PLANT | TOM | TOM | | H02 | C | 1331021 |
MEMORIAL HOSPITAL | H01 | C | 09/23/1999 | | RUSS | RUSS | | H01 | C | 1331014 |
MEMORIAL HOSPITAL | H02 | C | 03/01/1999 | | RUSS | RUSS | | H02 | C | 1330998 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1998 | | RUSS | RUSS | | H01 | C | 1330989 |
MEMORIAL HOSPITAL | H02 | C | 02/13/1998 | | RUSS | RUSS | | H02 | C | 1330981 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1997 | INITIAL INSPECTION, PERMIT ISSUED, ORDER: MR DOOR AND SMOKE DETECTOR, PHONE,110V SWITCH FOR CAR LIGHTS | RUSS | RUSS | | H01 | C | 1331005 |