MEMORIAL HOSPITAL | H02 | C | 03/06/2024 | HO2 -- ANNUAL 12/23 -- OTIS W/ TKE SERVICE -- PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS,AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040700) | BENH | BENH | | H02 | C | 8016417 |
MEMORIAL HOSPITAL | H03 | C | 11/08/2023 | WAS ON-SITE FOR REINSPECTION AND ITEMS WRITTEN UP FROM THE LAST REPORT HAVE BEEN ADDRESSED (Receipt #2006400) | BENH | BENH | | H03 | C | 7912917 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2023 | ANNUAL 1/23 -- TKE & SERVICE -- HOISTWAY DOOR EXCEEDS 1" MAX PER PANEL(2ND NOTICE) -- HOISTWAY DOOR MISSING SAFETY RETAINER (2ND NOTICE) (Receipt #1989741) | BENH | BENH | | H01 | C | 7861250 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2023 | HO2 -- ANNUAL 1/23 -- TKE & SERVICE | BENH | BENH | | H02 | C | 7701131 |
MEMORIAL HOSPITAL | H01 | C | 09/08/2022 | ANNUAL 1/22 -- TKE & SERVICE -- EMERGENCY LIGHT & ALARM BELL NONFUNCTIONAL WHEN CAB 110V IS DISCONNECTED -- CAR DOOR DOESN'T RESTRICT ON B LEVEL -- HOISTWAY DOOR GAPS EXCEED 1" PER PANEL -- HOISTWAY FAST DOOR MISSING SAFETY RETAINER (Receipt #1897743) cat 1 -- 1/23 DS | BENH | BENH | | H01 | C | 7509961 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2022 | HO2 -- CAT 1 1/2022 -- TKE & SERVICE -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7310633 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2021 | CAT1 -- 1/21 -- TKE AND SERVICE. TOP FLOOR MISSING SAFE RETAINER ON FAST AND SLOW DOORS (Receipt #1809965) (cat 1 -- 1/2022 check items listed at next inspection) | ROBERTV | ROBERTV | | H01 | C | 7120598 |
MEMORIAL HOSPITAL | H02 | C | 03/17/2021 | H02 -- CAT1 -- 1/21 -- TKE AND LOCKBOX | ROBERTV | ROBERTV | | H02 | C | 6902332 |
MEMORIAL HOSPITAL | H01 | C | 09/16/2020 | CAT1 -- 2/20 -- TKE AND LOCKBOX. NEED FIRE SERVICE TEST LOG. NEED QUARTERLY EMERGENCY PHONE TEST LOG. (Receipt #1713661) cat 1 1/21 | ROBERTV | ROBERTV | | H01 | C | 6708520 |
MEMORIAL HOSPITAL | H02 | C | 03/18/2020 | RP--2--20--TKE--HO2 | JOHNW | JOHNW | | H02 | C | 6513949 |
MEMORIAL HOSPITAL | H06 | C | 02/07/2020 | WITNESSED CATEGORY 1 HYDRAULIC TEST WITH TKE - MISSING FIRE EXTINGUISHER WITHIN MACHINE ROOM. | RANDYB | RANDYB | | H06 | C | 6476748 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2019 | RP 1/19--OTIS W/ TKE SERVICE & LOCKBOX--NEED DOOR RESTRICTOR COMPONENTS TO BE RE-INSTALLED- -UC HEALTH FACILITIES NEEDS TO GET MACHINE ROOM VENTILATION OPERABLE (Receipt #1633253) 10/11/19 waive the requirement for door restrictor due to mechanical and use constraints ER | CALE | CALE | | H01 | C | 6350081 |
MEMORIAL HOSPITAL | H02 | C | 03/25/2019 | RP 1/19 OTIS, TKE SERVICE, HO2 | ERIC | ERIC | | H02 | C | 6142616 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2018 | RP -- 1/18 -- DOVER W/ TKE LOCKBOX. CLEAN OIL ABSORBENT FROM ELEVATOR PIT. UC HEALTH FACILITIES NEEDS TO GET MACHINE ROOM VENTILATION OPERABLE. (Receipt #1565984) (RP 1-19) | ROBERTV | ROBERTV | | H01 | C | 5972559 |
MEMORIAL HOSPITAL | H02 | C | 03/08/2018 | H02 | ROBERTV | ROBERTV | | H02 | C | 5783842 |
MEMORIAL HOSPITAL | H01 | C | 09/26/2017 | RP 1/17 TKE AND LOCKBOX (Receipt #1455193) | ERIC | ERIC | | H01 | C | 5636674 |
MEMORIAL HOSPITAL | H02 | C | 03/24/2017 | H02 | ROBERTV | ROBERTV | | H02 | C | 5455138 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2016 | RP -- 2/16 -- DOVER W/ TKE SERVICE (NO ISSUES) | ROBERTV | ROBERTV | | H01 | C | 5306538 |
MEMORIAL HOSPITAL | H02 | C | 03/29/2016 | RP -- 2/16 -- TKE. NEED CALL STATION FIRE SIGNS AT ALL LANDINGS, NEED MAINTENANCE CONTROL PROGRAM ONSITE. | ROBERTV | ROBERTV | | H02 | C | 5164404 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2015 | RP 2/15 TKE. NEED CALL STATION FIRE SIGNS AT ALL LANDINGS, THIS IS THE RESPONSIBILITY OF THE HOSPITAL NOT THE ELEVATOR SERVICE CONTRACTOR (Receipt #1288953) | ERIC | ERIC | | H01 | C | 5042716 |
MEMORIAL HOSPITAL | H02 | C | 03/04/2015 | WITNESSED 2/15 | ERIC | ERIC | | H02 | C | 4911395 |
MEMORIAL HOSPITAL | H06 | C | 02/26/2015 | WITNESSED 5 YEAR SAFETY INSPECTION. NEED CALL STATION FIRE SIGNS AT BOTH LANDINGS AND NEED DOOR RESTRICTORS INSTALLED | ERIC | ERIC | | H06 | C | 4909373 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2014 | RP 3/14 TKE AND LOCKBOX (Receipt #1222635) | ERIC | ERIC | | H01 | C | 4824242 |
MEMORIAL HOSPITAL | H02 | C | 03/13/2014 | H02 DOVER, TKE SERVICE | ERIC | ERIC | | H02 | C | 4701581 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2013 | OTIS--RP EXPIRED LAST TEST 8-12 / REPAIR OR REPLACE CAR DOOR GIBBS / POST FLOOR DESIGNATION NUMBERS AT ALL LANDINGS (Receipt #1156753) | TOM | TOM | | H01 | C | 4612756 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2013 | RP 8-12-OTIS | TOM | TOM | | H02 | C | 4496969 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2012 | RP 8-12--OTIS (Receipt #1082941) | TOM | TOM | | H01 | C | 4392068 |
MEMORIAL HOSPITAL | H02 | C | 03/07/2012 | RP 7-11--OTIS | TOM | TOM | | H02 | C | 4290622 |
MEMORIAL HOSPITAL | H01 | C | 09/15/2011 | RP 8-11--OTIS (Receipt #1003056) | TOM | TOM | | H01 | C | 4215335 |
MEMORIAL HOSPITAL | H02 | C | 03/18/2011 | RP 7-10--OTIS | TOM | TOM | | H02 | C | 4129213 |
MEMORIAL HOSPITAL | H01 | C | 09/17/2010 | RP 7-10--OTIS--DOOR EDGE BROKEN / REPAIR OR REPLACE BOTTOM DOOR GUIDES (Receipt #936190) | TOM | TOM | | H01 | C | 4049227 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2010 | RP 7/09 DOVER. OTIS LOCKBOX. DOOR EDGE BROKEN, CHECK DOOR GIBBS, CHECK BASEMENT LEVEL HOISTWAY DOORS, THEY CAN BE OPENED ABOUT 3" AT THE BOTTOM. | ERIC | ERIC | | H02 | C | 3960617 |
MEMORIAL HOSPITAL | H01 | C | 09/30/2009 | RP 8-09--OTIS LOCKBOX (Receipt #878701) | TOM | TOM | | H01 | C | 3892337 |
MEMORIAL HOSPITAL | H02 | C | 03/31/2009 | RP 8-07--OTIS | TOM | TOM | | H02 | C | 3818712 |
MEMORIAL HOSPITAL | H01 | C | 09/29/2008 | rp--8--08--otis and lockbox #15--relief pressure expired (Receipt #828351) | TOM | TOM | | H01 | C | 3747593 |
MEMORIAL HOSPITAL | H02 | C | 03/14/2008 | RP 8-07 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1331316 |
MEMORIAL HOSPITAL | H01 | C | 09/14/2007 | RP 8-07 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1331309 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2007 | RP 9-06 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1331301 |
MEMORIAL HOSPITAL | H01 | C | 09/11/2006 | RP 9-05 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1331290 |
MEMORIAL HOSPITAL | H02 | C | 03/20/2006 | RP 9-05 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1331284 |
MEMORIAL HOSPITAL | H01 | C | 09/27/2005 | RP TEST DUE --- OTIS LOCKBOX | LES | LES | | H01 | C | 1331275 |
MEMORIAL HOSPITAL | H02 | C | 03/23/2005 | RP 8-04 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1331268 |
MEMORIAL HOSPITAL | H01 | C | 09/24/2004 | RP 8-04 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1331260 |
MEMORIAL HOSPITAL | H02 | C | 03/19/2004 | RP 8-03 --- DOVER | LES | LES | | H02 | C | 1331253 |
MEMORIAL HOSPITAL | H01 | C | 09/23/2003 | RP 8-03 | LES | LES | | H01 | C | 1331245 |
MEMORIAL HOSPITAL | H02 | C | 03/18/2003 | RP 7-02 --- CLEAN PIT | LES | LES | | H02 | C | 1331238 |
MEMORIAL HOSPITAL | H01 | C | 09/24/2002 | RP 8-02 | LES | LES | | H01 | C | 1331229 |
MEMORIAL HOSPITAL | H02 | C | 03/22/2002 | RP 7-01 | LES | LES | | H02 | C | 1331221 |
MEMORIAL HOSPITAL | H01 | C | 09/21/2001 | RP 7-01 | LES | LES | | H01 | C | 1331213 |
MEMORIAL HOSPITAL | H02 | C | 03/30/2001 | RP 3-00 | LES | LES | | H02 | C | 1331206 |
MEMORIAL HOSPITAL | H01 | C | 09/19/2000 | RP 3-00--DOVER--CAR IS MARKED # 15 | TOM | TOM | | H01 | C | 1331198 |
MEMORIAL HOSPITAL | H02 | P | 03/30/2000 | RP 3-00--DOVER--PHONE INOP | TOM | TOM | | H02 | P | 1331191 |
MEMORIAL HOSPITAL | H01 | C | 09/22/1999 | | RUSS | RUSS | | H01 | C | 1331184 |
MEMORIAL HOSPITAL | H02 | C | 03/01/1999 | | RUSS | RUSS | | H02 | C | 1331168 |
MEMORIAL HOSPITAL | H01 | C | 08/11/1998 | | RUSS | RUSS | | H01 | C | 1331160 |
MEMORIAL HOSPITAL | H02 | C | 02/13/1998 | | RUSS | RUSS | | H02 | C | 1331152 |
MEMORIAL HOSPITAL | H01 | C | 08/13/1997 | INITIAL INSPECTION, PERMIT ISSUED, ORDER: SEAL HOLES IN MR WALLS, REMOVE FLEX FROM TOP OF SHAFT | RUSS | RUSS | | H01 | C | 1331177 |