CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/05/2024 | 5 YEAR 2/22 -- ANNUAL 5/23 -- OTIS W/ TKE LOCKBOX AT P1 -- / PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040155) | DUSTINS | DUSTINS | | H02 | C | 8015087 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/19/2023 | 5 YEAR 2/22 -- ANNUAL 5/23 -- OTIS W/ TKE LOCKBOX AT P1 -- / BUILDING TO KEEP MONTHLY FIREFIGHTERS’ EMERGENCY OPERATION TEST LOGS UP TO DATE / RBD NOTE: CONTINUE TO MONITOR ROPE DIAMETER & ROUGE (Receipt #1989678) | DUSTINS | DUSTINS | | H01 | C | 7861060 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/23/2023 | HO2 -- ANNUAL 2/22 -- OTIS W/ TKE LOCKBOX -- ANNUAL CATEGORY 1 HYDRAULIC TEST PAST DUE -- 30 DAYS TO ADDRESS TO PREVENT ELEVATOR REMOVED FROM SERVICE cat 1 5/23 BH | BENH | BENH | | H02 | C | 7695748 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/19/2022 | 5 YEAR 2/22 -- OTIS W/ TKE LOCKBOX -- / PIT LIGHT OUT / CLEAN PIT / NOTE: CONTINUE TO MONITOR ROPE DIAMETER AND ROUGE (Receipt #1900455) | DUSTINS | DUSTINS | | H01 | C | 7522101 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/22/2022 | H02 -- 5 YEAR -- 2/22 -- CAT 1 -- 2/22 -- OTIS W/ TKE LOCKBOX. CHECK PREVIOUS ITEMS LISTED | DUSTINS | DUSTINS | | H02 | C | 7309631 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 02/18/2022 | WITNESSED CATEGORY 1 AND 5 SAFETY TESTS WITH TKE--/ ROPE DIAMETER AND ROUGE TO BE MONITORED UNTIL DEEMED REPLACEABLE--/ PROVIDE PIT LIGHTING--/ ELEVATOR IS RE LEVELING FREQUENTLY AND THE VALVE NEEDS TO BE DIAGNOSED--/ CAR RIDE QUALITY ON TOP FLOORS IS NOTICEABLY ROUGH (NOTE: BUILDING STATES THAT THEY HAVE CALLED THIS IN THE PAST BUT IT IS STILL A PREVALENT ISSUE)--/ 60 DAY FOLLOW UP SCHEDULED-- (items addressed per onsite visit 5/24/2022 mm) (Receipt #1844676) | MIKEM | MIKEM | | H06 | C | 7275344 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/27/2021 | 5 YEAR 12/2016 - ANNUAL 4/2021 -- OTIS W/ TKE LOCKBOX -- (note: will continue to monitor rope diameters. 5 year witness testing due by end of year) (Receipt #1809835) | RANDYB | RANDYB | | H01 | C | 7120198 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/17/2021 | 5YR -- 12/16 -- CAT1 -- 11/19 -- OTIS W/ TKE LOCKBOX. REQUIRED ANNUAL CATEGORY 1 TESTING IS SHOWING 4 MONTHS PAST DUE. RIGHT JACK HEAD IS SPILLING OVER WITH OIL......30 DAYS TO ADDRESS. (NOTE - WILL CONTINUE TO MONITOR SUSPENSION ROPE ROUGE AND DIAMETERS) (Cat 1 performed and oil leakage repaired 4/2021 per TKE) | ROBERTV | ROBERTV | | H02 | C | 6902272 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/30/2020 | 5YR -- 12/16 -- CAT1 -- 11/19 -- OTIS W/ TKE LOCKBOX. LEFT HYDRAULIC JACK IS STILL LEAKING PROFUSELY. STILL MISSING HOISTWAY DOOR RESTRICTOR FLAG ON "P2" LEVEL. NEED HOISTWAY DOOR NUMBERING. NEED OPERABLE PIT LIGHT. NEED QUARTERLY EMERGENCY PHONE TESTING LOG ONSITE.......... NOTE: WILL MONITOR SUSPENSION ROPE ROUGE AND DIAMETERS (Receipt #1717639) (Items addressed per onsite inspection, except annual RV) | ROBERTV | ROBERTV | | H01 | C | 6725444 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/31/2020 | RP--11--19--OTIS--HO2 | JOHNW | JOHNW | | H02 | C | 6526730 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/27/2019 | RP -- 11/18 -- OTIS AND LOCKBOX. LEFT JACK IS LEAKING PROFUSELY. MISSING HOISTWAY DOOR RESTRICTOR FLAG AT P2 LEVEL. (Receipt #1633359) (Cat. 1 Performed 11/19) | ROBERTV | ROBERTV | | H01 | C | 6350406 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/07/2019 | 5YR -- 12/16 -- OTIS AND LOCKBOX. ANNUAL CATEGORY 1 TEST FORM AND TAGS DO NOT HAVE ANY DATES. | ROBERTV | ROBERTV | | H02 | C | 6126381 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2018 | RP 9/17, 5 YEAR 12/16 OTIS AND LOCKBOX (Receipt #1542240) | ERIC | ERIC | | H01 | C | 5979565 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/29/2018 | RP 9/17, 5 YEAR 12/16 OTIS, PEAK SERVICE | ERIC | ERIC | | H02 | C | 5803020 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/26/2017 | RP 12/16 OTIS, PEAK SERVICE. NEED MCP ON SITE AND NEED TO NUMBER INSIDE OF HOISTWAY DOORS (Receipt #1455381) | ERIC | ERIC | | H01 | C | 5637406 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/14/2017 | RP 12/16 OTIS AND LOCKBOX, H02 | ERIC | ERIC | | H02 | C | 5439855 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 12/28/2016 | WITNESSED 5 YEAR SAFETY TEST ON ROPED HYDRO. STILL NEED TO NUMBER HOISTWAY DOORS (Receipt #1391877) | ERIC | ERIC | | H06 | C | 5378187 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/26/2016 | RP -- 1/16 -- 5YR -- 12/11 -- OTIS AND LOCKBOX. MISSING INTERIOR HOISTWAY FLOOR NUMBERS, PHONE VOLUME TO LOW, ROPES ON NORTH JACK SHOWING ROUGE IN SEVERAL AREAS, 5YR FULL LOAD SAFETY TEST DUE 12/2016 (Receipt #1364752 from 09/26/2016) | ROBERTV | ROBERTV | | H01 | C | 5301946 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/31/2016 | RP -- 1/16 -- 5 YR -- 12/11 -- OTIS AND LOCKBOX. MISSING INTERIOR HOISTWAY DOOR NUMBERS, REINSTALL CAB DOOR RESTRICTOR BAR THIS IS SITTING IN MACHINE ROOM, NEED MAINTENANCE CONTROL PROGRAM ONSITE. | ROBERTV | ROBERTV | | H02 | C | 5166435 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/21/2015 | RP 12/14, OTIS AND LOCKBOX. 5 YEAR ROPED HYDRO TEST 12/11. OTIS (Receipt #1288979) | ERIC | ERIC | | H01 | C | 5042823 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/13/2015 | RP 12/14, 5 YEAR roped hydro 12/11. OTIS | ERIC | ERIC | | H02 | C | 4916578 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/18/2014 | RP 12/13 OTIS AND LOCKBOX (Receipt #1220760) | ERIC | ERIC | | H01 | C | 4818655 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/25/2014 | RP 12/13 OTIS H02 | ERIC | ERIC | | H02 | C | 4707987 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/10/2013 | RP 12-12-OTIS (Receipt #1156712) | TOM | TOM | | H01 | C | 4612693 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/26/2013 | RP 12/12 OTIS AND LOCKBOX | ERIC | ERIC | | H02 | C | 4493808 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/05/2012 | RP 12-11--OTIS--ROPED HYDRO 5YR 12-11 (Receipt #1082508) | TOM | TOM | | H01 | C | 4390963 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/24/2012 | RP 9-11--MONTGOMERY | TOM | TOM | | H02 | C | 4289933 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 12/09/2011 | WITNESSED 5 YEAR ROPED HYDRO SAFETY TEST AND RELIEF PRESSURE TEST (Receipt #1016768) | ERIC | ERIC | | H06 | C | 4246766 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2011 | RP 2-11--OTIS--5 YR SAFETY TEST FOR ROPED HYDRO PAST DUE--TEST MUST BE PERFORMED ASAP (Receipt #1002979) | TOM | TOM | | H01 | C | 4215137 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/02/2011 | RP 2-11--OTIS NEED FIVE YEAR SAFETY TEST FOR ROPED HYDRO | TOM | TOM | | H02 | C | 4128916 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/20/2010 | 5YR 6-10--OTIS (Receipt #936084) | TOM | TOM | | H01 | C | 4049062 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/19/2010 | OTIS AND LOCKBOX. RP 1/10. ROPED HYDRO REQUIRES GOVERNOR AND SAFETY TESTING, NO TEST TAGS ON ROPES OR GOVERNOR | ERIC | ERIC | | H02 | C | 3956151 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/09/2009 | TEST (Receipt #875256) | TOM | TOM | | H01 | C | 3882521 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/12/2009 | OTIS RP 12/08. MR AND LOCKBOX AT P3 | ERIC | ERIC | | H02 | C | 3811821 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/29/2008 | rp--10--07--otis glass atrium (Receipt #828406) | TOM | TOM | | H01 | C | 3747825 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/25/2008 | RP 12-07 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 1499843 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/18/2007 | RP 10-06 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 1499836 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/21/2007 | RP 10-06 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 1499829 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2006 | RP 9-05 --- OTIS ELEVATOR AND LOCKBOX --- CLEAN UP OIL ON MACHINE ROOM FLOOR --- ALARM IN CAR INOP. --- GLASS ELEV. | LES | LES | | H01 | C | 1499820 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/27/2006 | RP 9-05 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 1499813 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/30/2005 | RP 9-05 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 1499804 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/08/2005 | RP 7-04 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 1499797 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/29/2004 | RP 7-04 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 1499788 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/30/2004 | RP 7-03 --- OTIS ELEVATOR AND LOCKBOX | LES | LES | | H02 | C | 1499779 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/27/2002 | RP 6-02--OTIS | TOM | TOM | | H01 | C | 1499771 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/20/2002 | RP 4-01--OTIS--VIC | TOM | TOM | | H02 | C | 1499762 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/21/2001 | RP 5-01--OTIS--GLASS FRONT--LOCKBOX @ P3 | TOM | TOM | | H01 | C | 1499753 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/15/2001 | RP 4-00--OTIS | TOM | TOM | | H02 | C | 1499744 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/26/2000 | RP 4-00 | LES | LES | | H01 | C | 1499734 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/09/2000 | | DAVEL | DAVEL | | H02 | C | 1499718 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/16/1999 | OTIS | LES | LES | | H01 | C | 1499710 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/11/1999 | | RUSS | RUSS | | H02 | C | 1499704 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | P | 09/15/1998 | INITIAL INSPECTION PERMIT ISSUED,,MUCHO PROBLEMO, NEEDS FIRE RATED MACHINE RM. GLASS MUST BE LAMINATED, CHECK FOLDER | RUSS | RUSS | | H01 | P | 1499726 |