COMMERCE CENTER COMMERCIAL BUILDERS, INC. | B= | C | 04/06/1999 | | DAVE JONES | DAVE JONES | | B= | C | 1561976 |
COMMERCE CENTER COMMERCIAL BUILDERS, INC. | B= | R | 04/05/1999 | STAIR RISE DIFF.>3/8"/LAVATORY CLR.<29"/WATER CLOSET SIDE CLEARANCE<18" | DAVE JONES | DAVE JONES | | B= | R | 1561960 |
COMMERCE CENTER COMMERCIAL BUILDERS, INC. | BFR | C | 04/05/1999 | | DAVE JONES | DAVE JONES | | BFR | C | 1561968 |
COMMERCE CENTER COMMERCIAL BUILDERS, INC. | BFR | P | 02/08/1999 | NEED SEP.WALL SEALS | DAVE JONES | DAVE JONES | | BFR | P | 1561952 |
COMMERCE CENTER COMMERCIAL BUILDERS, INC. | BFR | P | 01/13/1999 | CONSULTATION | DAVE JONES | DAVE JONES | | BFR | P | 1561944 |
COMMERCE CENTER COMMERCIAL BUILDERS, INC. | BFT | C | 12/24/1998 | | DAVE JONES | DAVE JONES | | BFT | C | 1561936 |
DRY ELECTRIC | E= | C | 03/20/1999 | | IKE | IKE | | E= | C | 1561855 |
DRY ELECTRIC | ER | P | 03/17/1999 | SUPPORT MC TO CODE-CEILING INSP-ALSO ID WIRING PER ART 210-4D | ARNOLD | ARNOLD | | ER | P | 1561873 |
DRY ELECTRIC | ES | C | 02/23/1999 | new set ct meter for 4 w/3phase 277/480 volt service by dry elec. | ARNOLD | ARNOLD | | ES | C | 1561847 |
DRY ELECTRIC | ES | R | 02/19/1999 | bond nipples | ARNOLD | ARNOLD | | ES | R | 1561840 |
DRY ELECTRIC | ER | P | 02/06/1999 | WALLS AND HARD LIDS | ARNOLD | ARNOLD | | ER | P | 1561864 |
HEADLEY MECH HGT & AIR COND | H= | C | 03/18/1999 | | JOHNW | JOHNW | | H= | C | 1561928 |
HEADLEY MECH HGT & AIR COND | H= | P | 03/17/1999 | need to tie-in waterheater | JOHNW | JOHNW | | H= | P | 1561920 |
HEADLEY MECH HGT & AIR COND | HV | C | 03/02/1999 | | JOHNW | JOHNW | | HV | C | 1561912 |
HEADLEY MECH HGT & AIR COND | HD | C | 03/01/1999 | | JOHNW | JOHNW | | HD | C | 1561896 |
HEADLEY MECH HGT & AIR COND | HV | P | 03/01/1999 | the 3 units in the front of gym , the bvents are undersized need to be 5" [too many offsets for the btu load] also inclose bvents on 2nd level | JOHNW | JOHNW | | HV | P | 1561904 |
SOUTHWEST PLUMBING & HTG, INC | H= | C | 02/18/1999 | | JOHNW | JOHNW | | H= | C | 1562024 |
HEADLEY MECH HGT & AIR COND | HC | R | 02/08/1999 | no permit or inspection done on gas line yet/the gas work that has been completed is only stubed into building [pipe to all the units before calling the inside gas inspection | JOHNW | JOHNW | | HC | R | 1561888 |
HEADLEY MECH HGT & AIR COND | HD | P | 02/03/1999 | ductwork complete in restroom area need to revise plans to show new location of furnaces | JOHNW | JOHNW | | HD | P | 1561880 |
SOUTHWEST PLUMBING & HTG, INC | P= | C | 03/29/1999 | Floor c/o next to water-closet | LEE | LEE | | P= | C | 1562017 |
SOUTHWEST PLUMBING & HTG, INC | P= | P | 03/26/1999 | Need to expose the full size c/o @ east restrooms, rest ok | LEE | LEE | | P= | P | 1562009 |
SOUTHWEST PLUMBING & HTG, INC | PTO | C | 02/11/1999 | ONLY WORLD GYM SIDE, NOT SALON | LEE | LEE | | PTO | C | 1562041 |
SOUTHWEST PLUMBING & HTG, INC | PTO | P | 02/05/1999 | There is no plumbing plan on site, Need to see VTR to complete insp. | LEE | LEE | | PTO | P | 1562001 |
SOUTHWEST PLUMBING & HTG, INC | PB | P | 01/19/1999 | World gym side ok, (permit problems) | LEE | LEE | | PB | P | 1561993 |
SOUTHWEST PLUMBING & HTG, INC | PB | P | 01/05/1999 | CHANGED FROM COMPLETE NEED ANOTHER INSPECTION
| LEE | LEE | | PB | P | 1562033 |
SOUTHWEST PLUMBING & HTG, INC | PB | P | 01/04/1999 | Lacks (2)- 1/2 baths east side. | LEE | LEE | | PB | P | 1561984 |