BROOKDALE SKYLINE | H01 | C | 01/19/2024 | ANNUAL 5/23 -- OTIS & LOCKBOX -- / FRONT CAR DOOR RESTRICTING MEANS BETWEEN FLOORS NEEDS TO BE ADDRESSED / ERU BATTERY VOLTAGE IS READING 0 VOLTS / RBD NOTE: 5 YEAR WITNESS TEST DUE JULY 2024 (Receipt #2026206) | DUSTINS | DUSTINS | | H01 | C | 7972536 |
BROOKDALE SKYLINE | H02 | C | 07/11/2023 | HO2 -- ANNUAL 5/23 -- OTIS & LOCKBOX -- SEE PREVIOUS NOTES moved H06 to align with H02, DS | BENH | BENH | | H02 | C | 7794504 |
BROOKDALE SKYLINE | H01 | C | 01/10/2023 | ANNUAL 05/2022 -- OTIS AND LOCK BOX --/ MONTHLY FIRE FIGHTERS SERVICE TESTING AND QUARTERLY EMERGENCY PHONE TESTING LOGS NOT BEING MAINTAINED --/ EMERGENCY TWO WAY COMMUNICATION NON-FUNCTIONAL WITHOUT THE 110v CAB CIRCUIT --/ REMOVE ALL NON-ELEVATOR RELATED ITEMS FROM THE MACHINE ROOM (Receipt #1925704) --/ (note : all items taken care of per discussion with Mike from Otis) cat1 5/23 BH per report restrictor flags need to be installed between floors on fascia | MIKEM | MIKEM | | H01 | C | 7630959 |
BROOKDALE SKYLINE | H02 | C | 07/19/2022 | HO2 -- ANNUAL 05/2022 -- OTIS AND LOCKBOX | MIKEM | MIKEM | | H02 | C | 7451824 |
BROOKDALE SKYLINE | H01 | C | 01/06/2022 | ANNUAL 04/2021-- OTIS AND LOCKBOX--/ EMERGENCY LIGHT AND BELL NON FUNCTIONAL WITHOUT 110v CAB CIRCUIT--/ PROVIDE UP TO DATE 2022 MAINTENANCE RECORDS (Receipt #1834440) | MIKEM | MIKEM | | H01 | C | 7230373 |
BROOKDALE SKYLINE | H02 | C | 07/08/2021 | H02 -- CAT1 -- 4/21 -- OTIS AND LOCKBOX | ROBERTV | ROBERTV | | H02 | C | 7028227 |
BROOKDALE SKYLINE | H01 | C | 01/13/2021 | ANNUAL 5/2020 -- OTIS & LOCKBOX (Receipt #1742747) | RANDYB | RANDYB | | H01 | C | 6835162 |
BROOKDALE SKYLINE | H02 | C | 07/29/2020 | RP 05/20--5YR 04/19--OTIS & LOCKBOX--HO2 | CALE | CALE | | H02 | C | 6653746 |
BROOKDALE SKYLINE | H01 | C | 01/27/2020 | 5YR 4/19--OTIS & LOCKBOX (Receipt #1658299) | CALE | CALE | | H01 | C | 6464343 |
BROOKDALE SKYLINE | H02 | C | 07/25/2019 | RP 4/19--OTIS & LOCKBOX--HO2 | CALE | CALE | | H02 | C | 6276612 |
BROOKDALE SKYLINE | H06 | C | 04/11/2019 | WITNESSED 5YR HYDRO SAFETY TEST W/ OTIS--OTIS & LOCKBOX | CALE | CALE | | H06 | C | 6162894 |
BROOKDALE SKYLINE | H01 | C | 01/17/2019 | RP--2--18--OTIS AND LOCKBOX------------------------------------------------NOTE 5YR WITNESSED TEST IS COMING UP IN MARCH 2019 (Receipt #1570382) | JOHNW | JOHNW | | H01 | C | 6081814 |
BROOKDALE SKYLINE | H02 | C | 07/06/2018 | RP 2/18 OTIS AND LOCKBOX, HO2 | ERIC | ERIC | | H02 | C | 5895322 |
BROOKDALE SKYLINE | H01 | C | 01/16/2018 | RP 1/17 OTIS AND LOCKBOX. NO INSPECTION TEST FORMS IN MCP (Receipt #1476478) | ERIC | ERIC | | H01 | C | 5738694 |
BROOKDALE SKYLINE | H02 | C | 07/17/2017 | RP 1/17 OTIS AND LOCKBOX, HO2 | ERIC | ERIC | | H02 | C | 5565919 |
BROOKDALE SKYLINE | H01 | C | 01/06/2017 | RP 1/16 OTIS AND LOCKBOX. TOP OF CAR CAB STEADIERS NEED TO BE REPAIRED (Receipt #1393437) | ERIC | ERIC | | H01 | C | 5383547 |
BROOKDALE SKYLINE | H02 | C | 07/20/2016 | RP -- 1/16 -- OTIS AND LOCKBOX. MISSING REAR CAB MOUNTED DOOR RESTRICTOR BAR (FINAL NOTICE), THIS MUST BE RESOLVED BY NEXT INSPECTION TO RECEIVE PERMIT TO OPERATE. | ROBERTV | ROBERTV | | H02 | C | 5249168 |
BROOKDALE SKYLINE | H01 | C | 01/25/2016 | RP -- 1/16 -- OTIS AND LOCKBOX. MISSING REAR CAB DOOR RESTRICTOR BAR, NEED COMPLETE MAINTENANCE CONTROL PROGRAM ONSITE NEXT INSPECTION (MISSING CATEGORY 1 TEST FORM AND EVACUATION PROCEDURES) (Receipt #1309794) | ROBERTV | ROBERTV | | H01 | C | 5121985 |
BROOKDALE SKYLINE | H02 | C | 07/13/2015 | PRESSURE RELIEF TEST EXPIRED, LAST PERFORMED 3/2014. MISSING REAR CAR DOOR RESTRICTOR ACTUATOR. | ROBERTV | ROBERTV | | H02 | C | 4991263 |
BROOKDALE SKYLINE | H01 | C | 01/30/2015 | RP 3-14-OTIS-LOCKBOX RE-NUMBER EQUIPMENT FOR BOTH CARS IN DUPLEX MACHINE ROOM & INSIDE OF BOTH CARS---CONTROLLERS & TANKS NUMBERED 1&2--DISCONNECTS ARE NUMBERED 7&8--OPERATING PANEL IN CAR IS NUMBERED 2&8 / MAINTAIN MONTHLY FIRE LOG / CLEAN TRASH FROM PIT (Receipt #1243625) | TOM | TOM | | H01 | C | 4894300 |
BROOKDALE SKYLINE | H02 | C | 07/08/2014 | RP--3--14--OTIS AND LOCKBOX | JOHNW | JOHNW | | H02 | C | 4772118 |
BROOKDALE SKYLINE | H06 | C | 03/06/2014 | WITNESSED--3--5--14--OTIS | JOHNW | JOHNW | | H06 | C | 4698342 |
BROOKDALE SKYLINE | H01 | C | 01/27/2014 | RP--6--12--OTIS --PRESSURE RELIEF EXPIRED MUST BE WITNESSED (Receipt #1176650) | JOHNW | JOHNW | | H01 | C | 4677798 |
BROOKDALE SKYLINE | H02 | C | 07/02/2013 | HO2 | JOHNW | JOHNW | | H02 | C | 4555294 |
BROOKDALE SKYLINE | H01 | C | 01/10/2013 | RP--6--12--OTIS AND LOCKBOX--SEE TOM FOR CONTACT (Receipt #1104832) | JOHNW | JOHNW | | H01 | C | 4452032 |
BROOKDALE SKYLINE | H02 | C | 07/13/2012 | RP--6--12---OTIS AND LOCKBOX--ANNUAL REPORT NOT COMPLETE | JOHNW | JOHNW | | H02 | C | 4341005 |
BROOKDALE SKYLINE | H01 | C | 01/12/2012 | RP--1--11--OTIS AND LOCKBOX (Receipt #1022353) | JOHNW | JOHNW | | H01 | C | 4258762 |
BROOKDALE SKYLINE | H02 | C | 07/15/2011 | RP--1--11--OTIS AND LOCKBOX | JOHNW | JOHNW | | H02 | C | 4178236 |
BROOKDALE SKYLINE | H01 | C | 01/05/2011 | RP--11--09--OTIS--AND LOCKBOX -RELIEF PRESSURE TEST EXPIRED (Receipt #953648) | JOHNW | JOHNW | | H01 | C | 4094242 |
BROOKDALE SKYLINE | H02 | C | 07/07/2010 | RP--11--09--OTIS--AND LOCKBOX--STILL NO SHUNT TRIP | JOHNW | JOHNW | | H02 | C | 4005650 |
BROOKDALE SKYLINE | H01 | C | 01/06/2010 | RP--11--09-OTIS AND OTIS LOCKOBX--SPRINKLER HAS BEEN ADDED TO THE MACHINE ROOM WITH NO SHUNT PROTECTION (Receipt #891622) | JOHNW | JOHNW | | H01 | C | 3929247 |
BROOKDALE SKYLINE | H02 | C | 07/17/2009 | RP--9--08--OTIS-- OTIS LOCKBOX--CLEAN PIT | JOHNW | JOHNW | | H02 | C | 3859449 |
BROOKDALE SKYLINE | H01 | C | 01/06/2009 | rp--9--08--otis and otis lockbox (Receipt #841500) | JOHNW | JOHNW | | H01 | C | 3788113 |
BROOKDALE SKYLINE | H02 | C | 07/01/2008 | RP TEST EXPIRED - LAST TEST 4-07 [335-420] --- OTIS --- GAVE INFORMATION TO JIM TO PASS ON TO TOM BISBEY MAINTENANCE MANAGER | LES | LES | | H02 | C | 3701523 |
BROOKDALE SKYLINE | H01 | C | 01/03/2008 | RP 4-07 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 1580694 |
BROOKDALE SKYLINE | H02 | C | 07/02/2007 | RP 4-07 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 1580684 |
BROOKDALE SKYLINE | H01 | C | 01/05/2007 | RP 5-06 --- OTIS ELEV. AND LOCKBOX --- FS OK | LES | LES | | H01 | C | 1580676 |
BROOKDALE SKYLINE | H02 | C | 07/05/2006 | RP 5-06 --- OTIS ELEVATOR AND LOCKBOX | LES | LES | | H02 | C | 1580668 |
BROOKDALE SKYLINE | H01 | C | 01/03/2006 | RP 6-05 --- OTIS ELEV. AND LOCKBOX --- ALARM INOP. [ 2ND NOTICE ] | LES | LES | | H01 | C | 1580660 |
BROOKDALE SKYLINE | H02 | C | 07/04/2005 | RP 6-05 --- OTIS --- ALARM INOP. | LES | LES | | H02 | C | 1580652 |
BROOKDALE SKYLINE | H01 | C | 01/03/2005 | RP 6-04 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 1580645 |
BROOKDALE SKYLINE | H02 | C | 07/05/2004 | RP 6-04 --- OTIS ELEVATOR AND LOCKBOX | LES | LES | | H02 | C | 1580638 |
BROOKDALE SKYLINE | H01 | C | 01/06/2004 | RP 5-03 --- OTIS ELEVATOR AND LOCKBOX --- SIGN MISSING 3RD FLOOR | LES | LES | | H01 | C | 1580630 |
BROOKDALE SKYLINE | H02 | C | 07/01/2003 | RP 5-03 | LES | LES | | H02 | C | 1580622 |
BROOKDALE SKYLINE | H01 | C | 01/02/2003 | RP 5-02 | LES | LES | | H01 | C | 1580614 |
BROOKDALE SKYLINE | H02 | C | 07/02/2002 | RP 5-02 | LES | LES | | H02 | C | 1580606 |
BROOKDALE SKYLINE | H01 | C | 01/03/2002 | RP 4-01 --- OTIS LOCKBOX | LES | LES | | H01 | C | 1580597 |
BROOKDALE SKYLINE | H02 | C | 07/09/2001 | RP 4-01 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1580589 |
BROOKDALE SKYLINE | H01 | C | 01/03/2001 | RP 1-00 --- BUILDING 2365 | LES | LES | | H01 | C | 1580582 |
BROOKDALE SKYLINE | H02 | C | 07/21/2000 | rp 2-00 | LES | LES | | H02 | C | 1580551 |
BROOKDALE SKYLINE | H01 | P | 01/14/2000 | RP EXPIRED--OTIS | TOM | TOM | | H01 | P | 1580575 |
BROOKDALE SKYLINE | H02 | P | 07/12/1999 | RP 9-98 OTIS INSTALL JAN 99---PIT IS FLOODED WITH WATER | TOM | TOM | | H02 | P | 1580567 |
BROOKDALE SKYLINE | H01 | C | 01/22/1999 | INITIAL INSPECTION | RUSS | RUSS | | H01 | C | 1580559 |