BROOKDALE SKYLINE | H01 | C | 01/19/2024 | ANNUAL 5/23 -- OTIS & LOCKBOX -- / FRONT CAR DOOR RESTRICTING MEANS BETWEEN FLOORS NEEDS TO BE ADDRESSED / ERU BATTERY VOLTAGE IS READING 0 VOLTS / MACHINE ROOM VENTILATION IS NON OPERABLE / RBD NOTE: 5 YEAR WITNESS TEST DUE JULY 2024 (Receipt #2026204) | DUSTINS | DUSTINS | | H01 | C | 7972525 |
BROOKDALE SKYLINE | H02 | C | 07/11/2023 | HO2 -- ANNUAL 5/23 -- OTIS & LOCKBOX -- SEE PREVIOUS NOTES moved H06 to align with H02, DS | BENH | BENH | | H02 | C | 7794520 |
BROOKDALE SKYLINE | H01 | C | 01/10/2023 | ANNUAL 05/2022 -- OTIS AND LOCKBOX --/ MONTHLY FIRE FIGHTERS SERVICE TESTING AND QUARTERLY EMERGENCY PHONE TESTING LOGS NOT BEING MAINTAINED (Receipt #1925688) cat 1 5/23 BH per report restrictor flags to be installed between floors on fascia | MIKEM | MIKEM | | H01 | C | 7630890 |
BROOKDALE SKYLINE | H02 | C | 07/20/2022 | HO2 -- ANNUAL 05/2022 -- OTIS AND LOCKBOX | MIKEM | MIKEM | | H02 | C | 7453896 |
BROOKDALE SKYLINE | H01 | C | 01/06/2022 | ANNUAL 04/2021-- OTIS AND LOCKBOX--/ EMERGENCY LIGHT AND BELL NON FUNCTIONAL WITHOUT 110v CAB CIRCUIT (SECOND NOTICE)--/ 60 DAYS TO CORRECT--/ PROVIDE UP TO DATE 2022 MAINTENANCE LOGS (items addressed per reinspect on 03/11/2022 mm) (Receipt #1834468) cat 1 5/22 | MIKEM | MIKEM | | H01 | C | 7230423 |
BROOKDALE SKYLINE | H02 | C | 07/08/2021 | H02 -- CAT1 -- 4/21 -- OTIS AND LOCKBOX. CHECK EMERGENCY LIGHTS AND ALARM BELL AT H01 | ROBERTV | ROBERTV | | H02 | C | 7028231 |
BROOKDALE SKYLINE | H01 | C | 01/13/2021 | ANNUAL 5/2020 -- OTIS & LOCKBOX -- / EMERGENCY LIGHTS AND ALARM BELL NONFUNCTIONAL (Receipt #1742751) | RANDYB | RANDYB | | H01 | C | 6835173 |
BROOKDALE SKYLINE | H02 | C | 07/29/2020 | RP 05/20--5YR 04/19--OTIS & LOCKBOX--HO2 | CALE | CALE | | H02 | C | 6653748 |
BROOKDALE SKYLINE | H01 | C | 01/27/2020 | 5YR 4/19--OTIS & LOCKBOX (Receipt #1658296) | CALE | CALE | | H01 | C | 6464336 |
BROOKDALE SKYLINE | H02 | C | 07/25/2019 | RP 4/19--OTIS & LOCKBOX--HO2 | CALE | CALE | | H02 | C | 6276617 |
BROOKDALE SKYLINE | H06 | C | 04/11/2019 | WITNESSED 5YR HYDRO SAFETY TEST W/ OTIS--OTIS & LOCKBOX | CALE | CALE | | H06 | C | 6162875 |
BROOKDALE SKYLINE | H01 | C | 01/17/2019 | RP--5--18--OTIS AND LOCKBOX------------------------------------------------------------------------NOTE 5YR WITNESSED DUE MARCH 2019 (Receipt #1570386) | JOHNW | JOHNW | | H01 | C | 6081847 |
BROOKDALE SKYLINE | H02 | C | 07/06/2018 | RP 2/18 OTIS AND LOCKBOX, HO2 | ERIC | ERIC | | H02 | C | 5895327 |
BROOKDALE SKYLINE | H01 | C | 01/16/2018 | RP 1/17 OTIS AND LOCKBOX. NO INSPECTION TEST FORMS IN MCP (Receipt #1476481) | ERIC | ERIC | | H01 | C | 5738711 |
BROOKDALE SKYLINE | H02 | C | 07/17/2017 | RP 1/17 OTIS AND LOCKBOX, HO2 | ERIC | ERIC | | H02 | C | 5565914 |
BROOKDALE SKYLINE | H01 | C | 01/06/2017 | RP 1/16 OTIS AND LOCKBOX. (Receipt #1393435) | ERIC | ERIC | | H01 | C | 5383545 |
BROOKDALE SKYLINE | H02 | C | 07/20/2016 | RP -- 1/16 -- OTIS AND LOCKBOX (NO ISSUES) | ROBERTV | ROBERTV | | H02 | C | 5249173 |
BROOKDALE SKYLINE | H01 | C | 01/25/2016 | RP -- 1/16 -- OTIS AND LOCKBOX. NEED COMPLETE MAINTENANCE CONTROL PROGRAM ONSITE NEXT INSPECTION (MISSING CATEGORY 1 TEST FORM AND EVACUATION PROCEDURES) | ROBERTV | ROBERTV | | H01 | C | 5121992 |
BROOKDALE SKYLINE | H02 | C | 07/13/2015 | PRESSURE RELIEF TEST EXPIRED, LAST PERFORMED 3/2014. EMERGENCY PHONE DOES NOT CONNECT | ROBERTV | ROBERTV | | H02 | C | 4991254 |
BROOKDALE SKYLINE | H01 | C | 01/30/2015 | RP 3-14 OTIS--RE-NUMBER MAINLINE DISCONNECT TO MATCH THE REST OF THE EQUIPMENT FOR THIS CAR / MAINTAIN FIRE LOG / CLEAN TRASH FROM PIT (Receipt #1243627) | TOM | TOM | | H01 | C | 4894302 |
BROOKDALE SKYLINE | H02 | C | 07/08/2014 | RP--3--14--OTIS AND LOCKBOX | JOHNW | JOHNW | | H02 | C | 4772113 |
BROOKDALE SKYLINE | H06 | C | 03/06/2014 | WITNESSED RP--3--5--14--OTIS | JOHNW | JOHNW | | H06 | C | 4698334 |
BROOKDALE SKYLINE | H01 | C | 01/27/2014 | RP--6--12--OTIS --PRESSURE RELIEF TEST EXPIRED MUST BE WITNESSED (Receipt #1176646) | JOHNW | JOHNW | | H01 | C | 4677789 |
BROOKDALE SKYLINE | H02 | C | 07/02/2013 | HO2
| JOHNW | JOHNW | | H02 | C | 4555290 |
BROOKDALE SKYLINE | H01 | C | 01/10/2013 | RP--6--12--OTIS--LOCKBOX--ALARM IN CAB NOT WORKING---------------------------------------------------NOTE: ROUGH RIDE AT 2ND LEVEL (Receipt #1104818) | JOHNW | JOHNW | | H01 | C | 4452025 |
BROOKDALE SKYLINE | H02 | C | 07/13/2012 | RP--6--12--OTIS--AND LOCKBOX--ANNUAL REPORT NOT COMPLETELY FILLED OUT | JOHNW | JOHNW | | H02 | C | 4340993 |
BROOKDALE SKYLINE | H01 | C | 01/12/2012 | RP--1--11--OTIS LOCKBOX (Receipt #1022357) | JOHNW | JOHNW | | H01 | C | 4258764 |
BROOKDALE SKYLINE | H02 | C | 07/15/2011 | RP--1--11--OTIS AND LOCKBOX | JOHNW | JOHNW | | H02 | C | 4178233 |
BROOKDALE SKYLINE | H01 | C | 01/05/2011 | RP--11--09--OTIS AND LOCKBOX--RELIEF PRESSURE TEST EXPIRED (Receipt #953645) | JOHNW | JOHNW | | H01 | C | 4094231 |
BROOKDALE SKYLINE | H02 | C | 07/07/2010 | RP--11--09--OTIS--AND LOCKBOX--STILL NO SHUNT TRIP | JOHNW | JOHNW | | H02 | C | 4005648 |
BROOKDALE SKYLINE | H01 | C | 01/06/2010 | RP--11--09--OTIS AND OTIS LOCKBOX--SPRINKLERS HAVE BEEN ADDED TO MACHINE ROOM WITH NO SHUNT PROTECTION (Receipt #891620) | JOHNW | JOHNW | | H01 | C | 3929240 |
BROOKDALE SKYLINE | H02 | C | 07/17/2009 | RP--9--08--OTIS--OTIS LOCKBOX--CLEAN PIT | JOHNW | JOHNW | | H02 | C | 3859411 |
BROOKDALE SKYLINE | H01 | C | 01/06/2009 | rp--9--08--otis--otis lockbox (Receipt #841506) | JOHNW | JOHNW | | H01 | C | 3788141 |
BROOKDALE SKYLINE | H02 | C | 07/01/2008 | RP TEST EXPIRED - LAST TEST 4-07 [ 460-580] --- OTIS ELEVATOR AND LOCK BOX --- GAVE INFORMATION TO JIM TO PASS ON TO TOM BISBE THE MAINTENANCE MANAGER | LES | LES | | H02 | C | 3701542 |
BROOKDALE SKYLINE | H01 | C | 01/03/2008 | RP 4-07 --- OTIS ELEV. AND LOCKBOX --- FS OK | LES | LES | | H01 | C | 1581059 |
BROOKDALE SKYLINE | H02 | C | 07/02/2007 | RP 4-07 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H02 | C | 1581052 |
BROOKDALE SKYLINE | H01 | C | 01/05/2007 | RP 5-06 --- OTIS ELEV. AND LOCKBOX --- FS OX | LES | LES | | H01 | C | 1581044 |
BROOKDALE SKYLINE | H02 | C | 07/05/2006 | RP 5-06 --- OTIS ELEVATOR AND LOCKBOX | LES | LES | | H02 | C | 1581035 |
BROOKDALE SKYLINE | H01 | C | 01/03/2006 | RP 6-05 --- OTIS ELEV. AND LOCKBOX --- HANDRAIL LOSE IN CAR | LES | LES | | H01 | C | 1581027 |
BROOKDALE SKYLINE | H02 | C | 07/04/2005 | RP 6-05 --- OTIS | LES | LES | | H02 | C | 1581019 |
BROOKDALE SKYLINE | H01 | C | 01/03/2005 | RP 5-04 --- OTIS ELEV. AND LOCKBOX | LES | LES | | H01 | C | 1581011 |
BROOKDALE SKYLINE | H02 | C | 07/05/2004 | RP 5-04 --- OTIS ELEVATOR AND LOCKBOX | LES | LES | | H02 | C | 1581004 |
BROOKDALE SKYLINE | H01 | C | 01/06/2004 | RP 5-03 --- OTIS ELEVATOR AND LOCKBOX --- NO STORAGE ALLOWED IN MACHINE ROOM | LES | LES | | H01 | C | 1580996 |
BROOKDALE SKYLINE | H02 | C | 07/01/2003 | RP 5-03 | LES | LES | | H02 | C | 1580988 |
BROOKDALE SKYLINE | H01 | C | 01/02/2003 | RP 5-02 | LES | LES | | H01 | C | 1580980 |
BROOKDALE SKYLINE | H02 | C | 07/02/2002 | RP 5-02 | LES | LES | | H02 | C | 1580973 |
BROOKDALE SKYLINE | H01 | C | 01/03/2002 | RP 4-01 | LES | LES | | H01 | C | 1580965 |
BROOKDALE SKYLINE | H02 | C | 07/09/2001 | RP 4-01 --- OTIS LOCKBOX | LES | LES | | H02 | C | 1580956 |
BROOKDALE SKYLINE | H01 | C | 01/03/2001 | RP 1-00 --- BUILDING 2365 | LES | LES | | H01 | C | 1580947 |
BROOKDALE SKYLINE | H02 | C | 07/21/2000 | rp 2-00 | LES | LES | | H02 | C | 1580916 |
BROOKDALE SKYLINE | H01 | P | 01/14/2000 | RP EXPIRED--OTIS | TOM | TOM | | H01 | P | 1580940 |
BROOKDALE SKYLINE | H02 | C | 07/12/1999 | RP 11-98 OTIS INSTALL JAN 99--ELEV #5 | TOM | TOM | | H02 | C | 1580932 |
BROOKDALE SKYLINE | H01 | C | 01/22/1999 | INITIAL INSPECTION | RUSS | RUSS | | H01 | C | 1580924 |