GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 09/09/1999 | | DAVE JONES | DAVE JONES | | B= | C | 1621726 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 07/30/1999 | SKYLIGHTS/LAV.UNDER CLR.<29" | DAVE JONES | DAVE JONES | | B= | P | 1621719 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 07/09/1999 | VERIFY EXIT WEST SIDE/FINISH GLAZINGS | DAVE JONES | DAVE JONES | | B= | P | 1621712 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 06/18/1999 | RECALL | DAVE JONES | DAVE JONES | | B= | P | 1621704 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 06/14/1999 | NEED SEALS AT CORRIDOR FOR EXISTING PIPES | DAVE JONES | DAVE JONES | | BFR | P | 1621698 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 06/09/1999 | NEED CORRIDOR WALL TO DECK AND PENETRATION SEALS | DAVE JONES | DAVE JONES | | BFR | P | 1621689 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 05/26/1999 | BATHS N.E. WITH PLUMBING/WALLS AT SPRINKLER ROOM | DAVE JONES | DAVE JONES | | BFR | P | 1621678 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 05/21/1999 | CORE AREA WALLS | DAVE JONES | DAVE JONES | | BFR | P | 1621670 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 05/05/1999 | 1ST OFFICE POD EAST/EAST OFFICES AT EXT.WALL | DAVE JONES | DAVE JONES | | BFR | P | 1621661 |
RIVIERA ELECTRIC, INC. | E= | C | 07/09/1999 | | ARNOLD | ARNOLD | | E= | C | 1621883 |
RIVIERA ELECTRIC, INC. | E= | P | 07/09/1999 | STRAP MC 12" OF BOXS-SUPPORT ALL BOXS AND WIRE FROM STRUCTURE NOT FROM OTHER CEILING-BREAK ROOM AREAS-NEED TO INSP PANELS AND TRANS. | ARNOLD | ARNOLD | | E= | P | 1621890 |
RIVIERA ELECTRIC, INC. | ER | P | 06/24/1999 | walls for breakrooms | ARNOLD | ARNOLD | | ER | P | 1621875 |
RIVIERA ELECTRIC, INC. | ER | P | 06/21/1999 | walls on west end except for break rooms | ARNOLD | ARNOLD | | ER | P | 1621866 |
RIVIERA ELECTRIC, INC. | ES | P | 06/17/1999 | TRANSFORMER AND PANELS FOR PHASE 1 OK | RED | RED | | ES | P | 1621916 |
RIVIERA ELECTRIC, INC. | E= | P | 06/17/1999 | WEST END NOT COMPLETE-FIXTURE SUPPORTSNOT DONE YET | RED | RED | | E= | P | 1621907 |
RIVIERA ELECTRIC, INC. | ER | P | 06/15/1999 | all fixturers not attached to grid ceiling must be support by other means than wire, all boxs must be rigidly supported to structure-all mc cable supported with 12" of boxs and every 6' any fixture in laid in grid must be secured to grid wires must be tied at both ends | ARNOLD | ARNOLD | | ER | P | 1621858 |
RIVIERA ELECTRIC, INC. | ER | P | 06/14/1999 | east end-secure all mc 12" and 6' fill ko i | ARNOLD | ARNOLD | | ER | P | 1621851 |
RIVIERA ELECTRIC, INC. | ER | P | 06/10/1999 | recessed cans in hard ceiling area 5 | ARNOLD | ARNOLD | | ER | P | 1621843 |
RIVIERA ELECTRIC, INC. | ER | P | 05/19/1999 | ALL PERMANENT WALLS OK | ARNOLD | ARNOLD | | ER | P | 1621835 |
RIVIERA ELECTRIC, INC. | ER | R | 05/18/1999 | not ready need to use nail plates where 1-1/4" cannot be maintained | ARNOLD | ARNOLD | | ER | R | 1621827 |
RIVIERA ELECTRIC, INC. | ER | P | 05/06/1999 | HIGHLIGHTED WALLS | MIKEC | MIKEC | | ER | P | 1621898 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 07/09/1999 | | JIMV | JIMV | | H= | C | 1621801 |
HEATING & PLUMBING ENGINEERS, INC | H16 | C | 06/18/1999 | process piping complete | JOHNW | JOHNW | | H16 | C | 1621793 |
HEATING & PLUMBING ENGINEERS, INC | HD | C | 06/09/1999 | | JIMV | JIMV | | HD | C | 1621766 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 06/09/1999 | E. side of area complete | JIMV | JIMV | | H= | P | 1621758 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 05/04/1999 | 90% ROUGH IN IN AREA 5 ON HIGH PRESSURE SIDE | JOHNW | JOHNW | | HD | P | 1621819 |
HEATING & PLUMBING ENGINEERS, INC | P= | C | 07/09/1999 | | JIMV | JIMV | | P= | C | 1621810 |
HEATING & PLUMBING ENGINEERS, INC | P= | P | 06/18/1999 | N/East restrooms and kit area ok, still need other restroom group | LEE | LEE | | P= | P | 1621786 |
HEATING & PLUMBING ENGINEERS, INC | PTO | C | 06/09/1999 | | JIMV | JIMV | | PTO | C | 1621775 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 05/28/1999 | NE. restroom & breakroom ok | JIMV | JIMV | | PTO | P | 1621749 |
HEATING & PLUMBING ENGINEERS, INC | PB | C | 05/03/1999 | Break room and south restroom complete, area 5 base plumb.complete. | LEE | LEE | | PB | C | 1621741 |
HEATING & PLUMBING ENGINEERS, INC | PB | P | 04/30/1999 | North-east restrooms, floor drains in mech room and break room sink, ok | LEE | LEE | | PB | P | 1621733 |