G. A. MAXWELL CONSTRUCT., INC. | B= | C | 01/20/2000 | | FRANK | FRANK | | B= | C | 1640899 |
G. A. MAXWELL CONSTRUCT., INC. | B= | P | 01/14/2000 | handrail to close to wall at back exit/ | FRANK | FRANK | | B= | P | 1640892 |
G. A. MAXWELL CONSTRUCT., INC. | B= | P | 09/16/1999 | insulate crawl space/ok letter on pads on file | FRANK | FRANK | | B= | P | 1640885 |
G. A. MAXWELL CONSTRUCT., INC. | BSP | P | 08/24/1999 | west side stair well walls ok | FRANK | FRANK | | BSP | P | 1640879 |
G. A. MAXWELL CONSTRUCT., INC. | BSP | P | 08/18/1999 | PADS AT CANOPY OK NEED ENG. DESIGN NOTHING ON PLANS / FOOTER FOR BASEMENT EXIT OK NEED OPEN HOLE LETTER | JIMA | JIMA | | BSP | P | 1640869 |
G. A. MAXWELL CONSTRUCT., INC. | BLA | C | 08/10/1999 | corner beads asap | FRANK | FRANK | | BLA | C | 1640862 |
G. A. MAXWELL CONSTRUCT., INC. | BFR | C | 08/09/1999 | | CLOVIS | CLOVIS | | BFR | C | 1640853 |
G. A. MAXWELL CONSTRUCT., INC. | BFR | P | 08/04/1999 | truss detail on girder ok, drywall above cans ok, still need engineering on drilled trusses, told the super ok to proceed | TERRYB | TERRYB | | BFR | P | 1640845 |
G. A. MAXWELL CONSTRUCT., INC. | BFR | R | 08/03/1999 | strap plate at braKER box------eng letter drill holes in trusses--------drywall trusses at lights-------girder truss detail | JOE | JOE | | BFR | R | 1640837 |
G. A. MAXWELL CONSTRUCT., INC. | BFN | C | 06/28/1999 | | JOHNP | JOHNP | | BFN | C | 1640829 |
G. A. MAXWELL CONSTRUCT., INC. | BFT | C | 06/23/1999 | | FRANK | FRANK | | BFT | C | 1640820 |
SPECTRUM, INC. | E= | C | 09/14/1999 | | IKE | IKE | | E= | C | 1640795 |
SPECTRUM, INC. | E= | P | 09/13/1999 | lights not complete, light and switch crawl space, move a/c cable by access hole. | IKE | IKE | | E= | P | 1640788 |
SPECTRUM, INC. | ES | C | 09/09/1999 | 300 amp 3/wire underground spectrum inc. new service, c/t metering. | IKE | IKE | | ES | C | 1640780 |
SPECTRUM, INC. | ES | R | 09/08/1999 | bond water and gas pipe, jumper water meter, bond service riser pipe with #2 to neutral, use lugs on neutral for 2/0 wire. | IKE | IKE | | ES | R | 1640773 |
SPECTRUM, INC. | ES | R | 09/01/1999 | need fuses, reroute ground wire in meter socket to lug with white wire. remove paint under lugs, where is cold water ground. | IKE | IKE | | ES | R | 1640765 |
SPECTRUM, INC. | ER | C | 08/02/1999 | | IKE | IKE | | ER | C | 1640757 |
SPECTRUM, INC. | ER | R | 07/30/1999 | rewire exam room. 1 1/4 spaceing. | IKE | IKE | | ER | R | 1640750 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | C | 09/15/1999 | | JOHNW | JOHNW | | H= | C | 1640743 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | P | 09/13/1999 | no walkway over A/C coil in attic/ will not final untill this happens | JOHNW | JOHNW | | H= | P | 1640736 |
D J HANNON PLBG. & HTG., INC. | H= | C | 09/10/1999 | gas piping | JIMV | JIMV | | H= | C | 1640705 |
D J HANNON PLBG. & HTG., INC. | HI | C | 09/10/1999 | | JIMV | JIMV | | HI | C | 1640713 |
RIAL HEATING AND AIR CONDITIONING, INC. | H= | R | 09/08/1999 | not ready/ need gas work done / need to complete light and outlet in attic / build walk way over A/C coil in attic | JOHNW | JOHNW | | H= | R | 1640729 |
RIAL HEATING AND AIR CONDITIONING, INC. | HD | P | 07/30/1999 | above ceiling rough ok / need support on all 4 cornners of radiation dampers also before final need 110v outlet ,a light and unubstructed catwalk to furnace and rated access door | JOHNW | JOHNW | | HD | P | 1640721 |
FRONTIER MECHANICAL SYSTEMS INC | P= | C | 09/10/1999 | | JIMV | JIMV | | P= | C | 1640811 |
FRONTIER MECHANICAL SYSTEMS INC | PTO | C | 07/26/1999 | | JIMV | JIMV | | PTO | C | 1640803 |