GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 08/15/2000 | | DANF | DANF | | B= | C | 1800615 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | P | 07/31/2000 | seal penetration at east clset ,next to conference room, plumbing boots at traps, restrooms, finish and seal west door at goverment room,stair riser <7",<3/8" at breakout area, | RICH | RICH | | B= | P | 1800609 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 07/17/2000 | AREA 2 SITE AT COMPAQ, RECALL RATED WALL PENETRATIONS AND DOUBLE DOOR INSTALL AT FIRST FLOOR CORRIDOR | RICH | RICH | | BFR | P | 1800602 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 06/14/2000 | UPPER LEVEL ELEVATOR LOBBY SEP.WALLS INTERIOR SIDE OK | DAVE JONES | DAVE JONES | | BFR | P | 1800595 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | R | 06/13/2000 | NO ONE ON SITE | DAVE JONES | DAVE JONES | | BFR | R | 1800622 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 06/01/2000 | 2ND.FLOOR ELEVATOR LOBBY SHAFT WALL | DAVE JONES | DAVE JONES | | BFR | P | 1800588 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 05/15/2000 | CORRIDOR SEALS OK IN BATHROOMS LESS DUCTS | DAVE JONES | DAVE JONES | | BFR | P | 1800584 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 05/11/2000 | BATHS AND CONF.ROOM OK NEED SEALS | DAVE JONES | DAVE JONES | | BFR | P | 1800576 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 04/18/2000 | NEED VERIFICATION OF HORT.SHAFT WALL CEILING LOBBY/AREA 2 COMPUTER LAB AND LOBBY SOFFITS OK | DAVE JONES | DAVE JONES | | BFR | P | 1800570 |
RIVIERA ELECTRIC, INC. | E= | C | 07/26/2000 | | MIKEC | MIKEC | | E= | C | 1800768 |
RIVIERA ELECTRIC, INC. | E= | P | 07/12/2000 | partial sand lab | MIKEC | MIKEC | | E= | P | 1800762 |
RIVIERA ELECTRIC, INC. | ER | P | 06/26/2000 | rest of ceiling phase 1 | MIKEC | MIKEC | | ER | P | 1800755 |
RIVIERA ELECTRIC, INC. | ER | P | 06/23/2000 | secure support wires at both ends | MIKEC | MIKEC | | ER | P | 1800748 |
RIVIERA ELECTRIC, INC. | ES | C | 06/12/2000 | new transformer and panels | MIKEC | MIKEC | | ES | C | 1800741 |
RIVIERA ELECTRIC, INC. | ES | P | 06/08/2000 | tighten all connections, remove bonding jumper in main | MIKEC | MIKEC | | ES | P | 1800734 |
RIVIERA ELECTRIC, INC. | ER | P | 05/30/2000 | rest of walls | MIKEC | MIKEC | | ER | P | 1800727 |
RIVIERA ELECTRIC, INC. | ER | P | 05/11/2000 | rest of hard lid ceiling, partial raised floor area | MIKEC | MIKEC | | ER | P | 1800720 |
RIVIERA ELECTRIC, INC. | ER | P | 04/17/2000 | walls on concrete floors | MIKEC | MIKEC | | ER | P | 1800713 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 07/13/2000 | | JOHNW | JOHNW | | H= | C | 1800707 |
HEATING & PLUMBING ENGINEERS, INC | HD | C | 06/21/2000 | AHU 2.01 and associated duct complete and OK to insulate. | LYNNS | LYNNS | | HD | C | 1800694 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 06/21/2000 | Area 2 "SAN LAB" and main lobby, register and grilles complete. | LYNNS | LYNNS | | H= | P | 1800687 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 05/18/2000 | additional firedamper framing | JOHNW | JOHNW | | HD | P | 1800681 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 05/15/2000 | area 2 lobby above ceiling complete except for 1 firesmoke damper in coridor | JOHNW | JOHNW | | HD | P | 1800675 |
HEATING & PLUMBING ENGINEERS, INC | HWP | C | 05/12/2000 | CHILLED WATER LINES COMPLETE / 100PSI | JOHNW | JOHNW | | HWP | C | 1800668 |
HEATING & PLUMBING ENGINEERS, INC | HWP | P | 05/08/2000 | 80# test OK on supply and return lines to VAV's. | LYNNS | LYNNS | | HWP | P | 1800655 |
HEATING & PLUMBING ENGINEERS, INC | HRP | P | 05/01/2000 | 80# test ok | JOHNW | JOHNW | | HRP | P | 1800648 |
HEATING & PLUMBING ENGINEERS, INC | HRP | R | 04/28/2000 | 55# test on a system pressure of 30#, need to test at 80#. | LYNNS | LYNNS | | HRP | R | 1800641 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 04/19/2000 | Above ceiling in area 2, OK to insulate. Still need VAV's and mixing boxes installed. | LYNNS | LYNNS | | HD | P | 1800635 |
HEATING & PLUMBING ENGINEERS, INC | P= | C | 06/27/2000 | | JIMV | JIMV | | P= | C | 1800701 |
HEATING & PLUMBING ENGINEERS, INC | PTO | C | 05/09/2000 | | JIMV | JIMV | | PTO | C | 1800661 |
HEATING & PLUMBING ENGINEERS, INC | PB | C | 04/18/2000 | | JIMV | JIMV | | PB | C | 1800629 |