GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | C | 01/08/2001 | | DANF | DANF | | B= | C | 1891283 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | B= | R | 01/02/2001 | 1) FIRE FINAL 2) POST MAX OCCUPANCY SIGN IN FOUR CONFERENCE ROOM AREAS 3) NEED PANIC HARDWARE AT CONFERENCE ROOMS 5) CORRECT EXIT SIGN WITH ARROWS IN CORRECT DIRECTION AND ONE IN CORRIDOR NOT WORKING 6) ASTRICAL MISSING AT RATED DBL DOORS 7) 90 MIN LABLE ON DOOR IN TWO HR WALL 8) 2HR PROCTION AT TRAYS IN TWO AREAS AND 6" NIPLE IN 2 HR WALL | DANF | DANF | | B= | R | 1891275 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | C | 12/28/2000 | AT FINAL CHECK SEAL OF CABLE TRAYS AT WEST END OF 2HR WALL IN TWO AREAS | DANF | DANF | | BFR | C | 1891266 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BSP | R | 12/14/2000 | 1) 2HR MASONRY WALL NEED GROUTING AT PENETRATIONS 2) FIRETAPE TOP OF TUNNE 3) SEAL END OF WALL PIPE PENETRATIONS; OK TO DROP TILE EXCEPT AREAS NOTED ABOVE | DANF | DANF | | BSP | R | 1891259 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 12/14/2000 | | DANF | DANF | | BFR | P | 1891250 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 12/12/2000 | COMPLETE FIRECAULKING IN RATED WALLS; ENTRY TUNNELS NEED TO BE COMPLETED | DANF | DANF | | BFR | P | 1891242 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 12/01/2000 | SEE APPROVED PLANS FOR WALL INSPECTED | DANF | DANF | | BFR | P | 1891234 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/22/2000 | See approved plans for areas inspected, Walls highlighted with orange felt tip and dated this date. | LEEG | LEEG | | BFR | P | 1891227 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 11/09/2000 | INTERIOR CORRIDOR WALLS FOR AREA 2; SEE APPROVED PLANS SHEET A2 | DANF | DANF | | BFR | P | 1891218 |
GE JOHNSON CONSTRUCTION COMPANY, INC. | BFR | P | 10/31/2000 | AREA 2; FRAMING SOUTH CORRIDOR WALL; SEE APPROVED PLANS SHEET A2 | DANF | DANF | | BFR | P | 1891210 |
RIVIERA ELECTRIC, INC. | E= | C | 12/21/2000 | | TIMA | TIMA | | E= | C | 1891424 |
RIVIERA ELECTRIC, INC. | ER | P | 12/18/2000 | ceilings rooms 226,215,216 ,220, 221,222,223, | RON | RON | | ER | P | 1891416 |
RIVIERA ELECTRIC, INC. | ER | P | 12/14/2000 | partial ceiling | MIKEC | MIKEC | | ER | P | 1891409 |
RIVIERA ELECTRIC, INC. | ER | P | 11/29/2000 | west bathrooms and lobby walls and ceiling | MIKEC | MIKEC | | ER | P | 1891402 |
RIVIERA ELECTRIC, INC. | ER | P | 11/06/2000 | panels rp16,rp 16-9, pp 16a and transformer t 16a | MIKEC | MIKEC | | ER | P | 1891392 |
RIVIERA ELECTRIC, INC. | ER | P | 10/30/2000 | walls [ check with foreman. high walls ] | MIKEC | MIKEC | | ER | P | 1891385 |
HEATING & PLUMBING ENGINEERS, INC | H= | C | 12/21/2000 | | JOHNW | JOHNW | | H= | C | 1891342 |
HEATING & PLUMBING ENGINEERS, INC | H= | P | 12/15/2000 | NEED EQUIPMENT TIED IN | JOHNW | JOHNW | | H= | P | 1891370 |
HEATING & PLUMBING ENGINEERS, INC | HD | C | 12/15/2000 | | JOHNW | JOHNW | | HD | C | 1891378 |
HEATING & PLUMBING ENGINEERS, INC | H= | R | 12/14/2000 | tried t.j.'s cell number several times and got no answer recall inspection | JOHNW | JOHNW | | H= | R | 1891334 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 11/21/2000 | firesmoke dampers frame ok | JOHNW | JOHNW | | HD | P | 1891319 |
HEATING & PLUMBING ENGINEERS, INC | HD | P | 11/14/2000 | column line 16 thru 19 above ceiling ok except for framing for firesmoke dampers need king studs on both sides of the dampers | JOHNW | JOHNW | | HD | P | 1891312 |
HEATING & PLUMBING ENGINEERS, INC | HD | R | 11/09/2000 | recall inspection / stopped by at lunch couldn't locate T.J. | JOHNW | JOHNW | | HD | R | 1891290 |
HEATING & PLUMBING ENGINEERS, INC | P= | C | 01/02/2001 | | LEE | LEE | | P= | C | 1891362 |
HEATING & PLUMBING ENGINEERS, INC | P= | P | 12/28/2000 | Mens w/c lacks 15" off stall side, need access to water hammer arrestor, gate valve and check reversed on sink that still has not been added to the approved plumbing drawings, Note: undercounter ejector pump system with air admittance valve located in cabinet, need approval thru RBD | LEE | LEE | | P= | P | 1891356 |
HEATING & PLUMBING ENGINEERS, INC | P= | R | 12/22/2000 | Phoned contractor about revised plan for additional sink, will reschedual, talked to Jim @ HPE | LEE | LEE | | P= | R | 1891349 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 11/30/2000 | All ok except lobby sink still has not been added to approved plans, also need approval to use air addmittance valve on same sink, ok to cover plumbing in walls | LEE | LEE | | PTO | P | 1891326 |
HEATING & PLUMBING ENGINEERS, INC | PB | C | 11/14/2000 | | LEE | LEE | | PB | C | 1891297 |
HEATING & PLUMBING ENGINEERS, INC | PTO | P | 11/14/2000 | 3- lavs on east wall in restrooms ok, need to have drawings submitted for additional breakroom sink, test ok | LEE | LEE | | PTO | P | 1891306 |