CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/05/2024 | ANNUAL 12/23 -- MONTGOMERY W/ TKE LOCKBOX AT P1 -- / PERFORMED SIX MONTH INSPECTION TO ONLY VERIFY CODE COMPLIANT MCP, LOGS, FIRE FIGHTERS SERVICE OPERATION AND ELEVATOR TWO-WAY COMMUNICATION. / (Receipt #2040164) | DUSTINS | DUSTINS | | H02 | C | 8015098 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/19/2023 | ANNUAL 10/22 -- MONTGOMERY W/ TKE LOCKBOX AT P1 -- / UNABLE TO GET CAR TO RUN AT TIME OF INSPECTION / PERMIT TO OPERATE WILL NOT BE ISSUED UNTIL ITEM/S ARE ADDRESSED AND OWNER/CONTRACTOR CONTACTS PPRBD FOR RE-INSPECTION (Receipt #1989689) (Cat1 - 12/2023 RV) | DUSTINS | DUSTINS | | H01 | C | 7861093 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/23/2023 | HO2 -- ANNUAL 10/22 --MONTGOMERY W/ TKE LOCKBOX -- SEE PREVIOUS NOTES | BENH | BENH | | H02 | C | 7695743 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/19/2022 | ANNUAL 5/21 -- MONTGOMERY W/ TKE LOCKBOX -- / REQUIRED ANNUAL HYDRAULIC CATEGORY 1 TESTING IS PAST DUE, 10 BUSINESS DAYS TO ADDRESS TO AVOID RED TAG AND POSSIBLE SERVICE INTERRUPTION / BUILDING TO PROVIDE UP TO DATE MONTHLY FIREFIGHTERS' EMERGENCY OPERATION AND QUARTERLY EMERGENCY PHONE TEST LOGS / BUILDING TO PROVIDE TYPE "ABC" FIRE EXTINGUISHER WITHIN MACHINE ROOM / (Receipt #1900463) Cat 1 -- 10/22, check other items at next inspection | DUSTINS | DUSTINS | | H01 | C | 7522143 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/22/2022 | H02 -- CAT 1 -- 5/21 -- MONTGOMERY W/ TKE LOCKBOX | DUSTINS | DUSTINS | | H02 | C | 7309634 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/27/2021 | ANNUAL 5/2021 -- MONTGOMERY W/ TKE LOCKBOX -- / PROVIDE KEY FOR INSPECTION SWITCH WITHIN CAR, REPLACE KEY SWITCH, OR REPAIR THE CAR TOP INSPECTION STATION TO WORK CORRECTLY / ESCAPE HATCH TO BE MECHANICALLY FASTENED (Receipt #1809834) | RANDYB | RANDYB | | H01 | C | 7120181 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/17/2021 | H02 -- CAT1 -- 3/20 -- MONTGOMERY W/ TKE LOCKBOX cat 1 5/21 | ROBERTV | ROBERTV | | H02 | C | 6902258 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/30/2020 | CAT1 -- 3/20 -- MONTGOMERY W/ TKE LOCKBOX. NEED QUARTERLY EMERGENCY PHONE TESTING LOG ONSITE (Receipt #1717650) | ROBERTV | ROBERTV | | H01 | C | 6725473 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/31/2020 | RP--3--20--MONTGOMERY--TKE AND LOCKBOX | JOHNW | JOHNW | | H02 | C | 6526765 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 03/30/2020 | WITNESSED | JOHNW | JOHNW | | H06 | C | 6524730 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/27/2019 | RP -- 10/18 -- MONTGOMERY W/ OTIS LOCKBOX. REPAIR AND SECURE TOP OF CAR ESCAPE HATCH SO IT CLOSES AND LOCKS CORRECTLY. (Receipt #1633362) (Cat. 1 Performed 11/19) | ROBERTV | ROBERTV | | H01 | C | 6350410 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/07/2019 | RP -- 10/18 -- MONTGOMERY W/ OTIS LOCKBOX. REPAIR AND SECURE TOP OF CAR ESCAPE HATCH SO IT CLOSES AND LOCKS CORRECTLY. | ROBERTV | ROBERTV | | H02 | C | 6126370 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2018 | STILL OUT OF SERVICE (Receipt #1542238) / (Elevator back in service / cat 1 performed 10-18, see images) | ERIC | ERIC | | H01 | C | 5979561 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/29/2018 | OUT OF SERVICE AT TIME OF INSPECTION | ERIC | ERIC | | H02 | C | 5803025 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/26/2017 | RP 5/16 MONTGOMERY, PEAK SERVICE. ELEVATOR OUT OF SERVICE. ANNUAL HYDRAULIC CAT 1 TESTING PAST DUE, NEED MCP ON SITE (Receipt #1455383) | ERIC | ERIC | | H01 | C | 5637409 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/14/2017 | RP 5/16 MONTGOMERY, HO2 | ERIC | ERIC | | H02 | C | 5439878 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/26/2016 | RP -- 5/16 -- MKE. (NO ISSUES) | ROBERTV | ROBERTV | | H01 | C | 5301941 |
CUSHMAN & WAKEFIELD OF COLO. | HE16 | C | 05/05/2016 | HYDRAULIC TANK UNIT REPLACED BY PEAK ELEVATOR---SEE PERMIT K10779 | ERIC | ERIC | | HE16 | C | 5192676 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/31/2016 | RP -- 3/15 -- MKE. CAR TOP INSPECTION STATION IS STILL MISSING INSP/AUTO SWITCH, NEED DEFINITIVE DATE FOR REPAIR / REPLACEMENT OF VALVE AND/OR COMPONENTS. NEED MAINTENANCE CONTROL PROGRAM ONSITE. (30 DAY FOLLOW UP SCHEDULED) | ROBERTV | ROBERTV | | H02 | C | 5166425 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/30/2015 | NO REPAIRS HAVE BEEN MADE TO ELEVATOR FROM VIOLATIONS PREVIOUSLY REPORTED -- (RELISTED): CAB CEILING HATCH DOOR HINGE NEEDS REPAIRED, NEED OPERABLE HOISTWAY DOOR PULL CHAINS, CAR TOP INSPECTION STATION NEEDS TO BE OPERATIONAL, RELIEF VALVE CANNOT BE ADJUSTED (CURRENTLY OPERATING AT 175% OF WORKING PRESSURE), CYLINDER PACKING AND VALVE ARE LEAKING EXCESSIVELY, DOOR JAMB NUMBERING REQUIRED AT ALL FLOOR LANDINGS. THESE ITEMS CONTINUE TO BE NON-ADDRESSED, AND NOW REPAIRS MUST BE COMPLETED WITHIN 30 DAYS OR ELEVATOR WILL BE REMOVED FROM SERVICE. Update: Talked with Ann Sebastian 9/30, at minimum Valve is to be Replaced no later than January 15, 2016. Will follow up December 1st, 2015 (Receipt #1290442) | ROBERTV | ROBERTV | | H01 | C | 5047728 |
CUSHMAN & WAKEFIELD OF COLO. | H06 | C | 03/19/2015 | WITNESSED 5 YEAR HYDRO SAFETY TEST W/ KONE -- CAB CEILING HATCH DOOR HINGE NEEDS REPAIRED, NEED OPERABLE HOISTWAY DOOR PULL CHAINS, CAR TOP INSPECTION STATION NEEDS TO BE OPERATIONAL, RELIEF VALVE CANNOT BE ADJUSTED (CURRENTLY OPERATING AT 175% OF WORKING PRESSURE), CYLINDER PACKING IS LEAKING EXCESSIVELY, DOOR JAMB NUMBERING REQUIRED AT ALL FLOOR LANDINGS. - ITEMS NEED TO BE REPAIRED WITHIN 90 DAYS, FOLLOW UP SCHEDULED FOR 6/2015. (Talked with Ann Sebastian 7/14/2015, Repairs / Replacement are out for Bid) | ROBERTV | ROBERTV | | H06 | C | 4920028 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/11/2015 | MONTGOMERY. ANNUAL PRESSURE RELIEF TEST IS WAY PAST DUE---12/13. 5 YEAR WITNESSED TEST MUST BE COMPLETED WITHIN 30 DAYS, OIL LEAK AT PUMP UNIT MUST BE REPAIRED, CYLINDER PACKING LEAKS EXCESSIVELY. | ERIC | ERIC | | H02 | C | 4916599 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/18/2014 | RP 3/12 KONE. RELIEF PRESSURE TEST EXPIRED, LEAK AT TANK/PUMP UNIT, DRIVE BELTS ARE OIL SOAKED, EXCESSIVE PACKING LEAKAGE, 3RD NOTIFICATION, PACKING MUST BE REPLACED. NEED WITNESSED 5 YEAR TEST. (Receipt #1220766) | ERIC | ERIC | | H01 | C | 4818691 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/31/2014 | H02 | ERIC | ERIC | | H02 | C | 4711396 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/10/2013 | KONE--RP EXPIRED LAST TEST 3-12 / CLEAN PIT / PACKING LEAKING (2ND NOTICE) | TOM | TOM | | H01 | C | 4612687 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/26/2013 | RP 3/12 KONE. BOTTOM GUIDE ASSEMBLY HAS FALLEN OFF OF CAR, FIX IT ASAP. EXCESSIVE LEAKAGE AT PACKING, MISSING HOISTWAY ACCESS PULL CHAIN AT BOTTOM LANDING, NEED FLOOR NUMBERS ON HOISTWAY DOORS AND ON DOOR JAMBS AT EACH LANDING | ERIC | ERIC | | H02 | C | 4493838 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/05/2012 | RP 3-12--MONTGOMERY--NUMBER DOORS IN HOISTWAY / POST FLOOR DESIGNATION NUMBERS AT ALL LANDINGS / PULL CHAIN MISSING FOR HOISTWAY ACCESS @ "M" LANDING (Receipt #1082505) | TOM | TOM | | H01 | C | 4390959 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/24/2012 | RP 9-11--MONTGOMERY | TOM | TOM | | H02 | C | 4289932 |
CUSHMAN & WAKEFIELD OF COLO. | HE16 | C | 02/02/2012 | RP TEST COMPLETED 9/11 KONE | ERIC | ERIC | | HE16 | C | 4267292 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2011 | RP TEST EXPIRED--LAST TEST 10-09--MONTGOMERY-ELEVATOR WILL BE TAKEN OUT OF SERVICE FOR NON-COMPLIANCE (Receipt #1002986) | TOM | TOM | | H01 | C | 4215161 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/02/2011 | RP EXPIRED LAST TEST 10-09 / NO PIT LIGHT / A LOT OF OIL & TRASH IN PIT-CLEAN | TOM | TOM | | H02 | C | 4128910 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/20/2010 | RP 10-09--MONTGOMERY (Receipt #936087) | TOM | TOM | | H01 | C | 4049068 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/19/2010 | MONTGOMERY, RP 10/09. CLEAN PIT, BOLTS HAVE FALLEN OUT OF BOTTOM GUIDE SHOE BRACKET. | ERIC | ERIC | | H02 | C | 3956152 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/30/2009 | MONTGOMERY. RELIEF PRESSURE TEST EXPIRED, 2ND NOTIFICATION, (Receipt #878619) | ERIC | ERIC | | H01 | C | 3892196 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/12/2009 | MONTGOMERY, KONE SERVICE. RELIEF PRESSURE TEST EXPIRED, NEED PIT ACCESS. CALL MANAGEMENT FOR MACHINE ROOM ACCESS. | ERIC | ERIC | | H02 | C | 3811828 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/29/2008 | rp--12--07--montgomery freight--otis service (Receipt #828409) | TOM | TOM | | H01 | C | 3747835 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/25/2008 | RP 12-O7 --- MONTGOMERY | LES | LES | | H02 | C | 1912794 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 11/15/2007 | MONTGOMERY | LES | LES | | H01 | C | 1912787 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/21/2007 | RP 10-06 --- NO KEY ON SITE FOR EMERGENCY DOOR ACCESS --- CLEAN PIT | LES | LES | | H02 | C | 1912779 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/28/2006 | RP TEST DUE --- MONTGOMERY --- OTIS LOCKBOX | LES | LES | | H01 | C | 1912772 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/27/2006 | RP 8-05 --- MONTGOMERY --- OTIS LOCKBOX | LES | LES | | H02 | C | 1912765 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/30/2005 | RP 8-05 --- MONTGOMERY | LES | LES | | H01 | C | 1912758 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/08/2005 | RP 6-04 --- MONTGOMERY --- OTIS LOCKBOX | LES | LES | | H02 | C | 1912750 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/29/2004 | RP 6-04 --- MONTGOMERY | LES | LES | | H01 | C | 1912745 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | C | 03/30/2004 | RP 6-03 --- MONTGOMERY | LES | LES | | H02 | C | 1912736 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/27/2002 | RP 5-02--MONTGOMERY | TOM | TOM | | H01 | C | 1912721 |
CUSHMAN & WAKEFIELD OF COLO. | H03 | C | 09/27/2002 | | TOM | TOM | | H03 | C | 1912728 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | P | 03/20/2002 | RP EXP--LAST TEST 10-00 | TOM | TOM | | H02 | P | 1912709 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 09/21/2001 | RP 10-00--NEED 2-WAY COMM--REPAIR CENTER GUIDE WHEEL ON NORTH RAIL | TOM | TOM | | H01 | C | 1912700 |
CUSHMAN & WAKEFIELD OF COLO. | H02 | P | 03/15/2001 | RP 10-00-- | TOM | TOM | | H02 | P | 1912693 |
CUSHMAN & WAKEFIELD OF COLO. | H01 | C | 10/23/2000 | INITIAL INSPECTION --- PERMIT ISSUED --- THIS ELEVATOR WAS PUT BACK IN SERVICE WITHOUT A PERMIT | LES | LES | | H01 | C | 1912686 |