CINEMARK USA, INC | H02 | C | 11/01/2023 | HO2 -- ANNUAL 9/23 -- KONE W/SCHINDLER LOCKBOX -- WAS ON-SITE TO CHECK M.C.P. LOGS, TEST FIREFIGHTERS SERVICE & TEST EMERGENCY PHONE IN THE ELEVATOR (Receipt #2004343) | BENH | BENH | | H02 | C | 7906315 |
CINEMARK USA, INC | H01 | C | 05/15/2023 | ANNUAL 10/22 -- KONE W/ SCHINDLER SERVICE & LOCKBOX -- EMERGENCY LIGHT NONFUNCTIONAL WHEN CAB 110V IS DISCONNECTED -- NON ELEVATOR RELATED ITEMS TO BE REMOVED FROM MACHINE ROOM -- SECURITY KEY SWITCH IS MISSING AT 3RD FLOOR HALL CALL STATION -- MONTHLY FIREFIGHTERS LOG & QUARTERLY EMERGENCY PHONE LOGS TO BE MAINTAINED FOR 2023 (Receipt #1954542) cat 1 9/23 BH | BENH | BENH | | H01 | C | 7744686 |
CINEMARK USA, INC | H02 | C | 11/01/2022 | HO2 -- ANNUAL 10/22 -- KONE W/ SCHINDLER SERVICE & LOCKBOX | BENH | BENH | | H02 | C | 7569039 |
CINEMARK USA, INC | H01 | C | 05/04/2022 | ANNUAL 9/21 -- KONE W/ SCHINDLER SERVICE & LOCKBOX -- COULD NOT ACCESS MACHINE ROOM DUE TO NO KEY BEING IN LOCKBOX -- COULD NOT ESTABLISH TWO WAY COMMUNICATION (Receipt #1864233) | BENH | BENH | | H01 | C | 7364030 |
CINEMARK USA, INC | H02 | C | 11/08/2021 | HO2 -- ANNUAL 9/21 -- KONE W/ TKE SERVICE & SCHINDLER LOCKBOX | BENH | BENH | | H02 | C | 7168260 |
CINEMARK USA, INC | H01 | C | 05/05/2021 | ANNUAL 10/2020 -- KONE W/ TKE SERVICE & SCHINDLER LOCKBOX (Receipt #1770460) | RANDYB | RANDYB | | H01 | C | 6958548 |
CINEMARK USA, INC | H02 | C | 11/20/2020 | ANNUAL 10/2020 -- KONE W/ SCHINDLER SERVICE & LOCKBOX -- / FRONT AND REAR DOOR "PEAK-A-BOO" OPERATION NONFUNCTIONAL | RANDYB | RANDYB | | H02 | C | 6784715 |
CINEMARK USA, INC | H01 | C | 05/05/2020 | BUILDING CLOSED DUE TO COVID-19. WILL SCHEDULE A FOLLOW UP INSPECTION. (Receipt #1678196) | RANDYB | RANDYB | | H01 | C | 6561398 |
CINEMARK USA, INC | H02 | C | 11/21/2019 | 5YR 5/19--KONE W/ SCHINDLER SERVICE--HO2 | CALE | CALE | | H02 | C | 6406550 |
CINEMARK USA, INC | H06 | C | 05/13/2019 | WITNESSED 5YR HYDRO SAFETY TEST W/ SCHINDLER 5/10/19--KONE--SCHINDLER SERVICE--MACHINE ROOM DOOR NEEDS TO BE SELF CLOSING | CALE | CALE | | H06 | C | 6196418 |
CINEMARK USA, INC | H01 | C | 01/31/2019 | RP--KONE --9--17--ANNUAL AND RELIEF PRESSURE TEST EXPIRED (Receipt #1573426) | JOHNW | JOHNW | | H01 | C | 6094438 |
CINEMARK USA, INC | H02 | C | 07/06/2018 | RP 9/17 KONE, HO2 | ERIC | ERIC | | H02 | C | 5895342 |
CINEMARK USA, INC | H01 | C | 01/16/2018 | RP -- 9/17 -- KONE (Receipt #1476311) | ROBERTV | ROBERTV | | H01 | C | 5737854 |
CINEMARK USA, INC | H02 | C | 07/06/2017 | RP 9/16 KONE, HO2 | ERIC | ERIC | | H02 | C | 5555570 |
CINEMARK USA, INC | H01 | C | 01/13/2017 | RP 9/16 KONE. (Receipt #1394895) | ERIC | ERIC | | H01 | C | 5388335 |
CINEMARK USA, INC | H02 | C | 07/01/2016 | H02 | ROBERTV | ROBERTV | | H02 | C | 5235861 |
CINEMARK USA, INC | H01 | C | 01/27/2016 | RP 7/15 KONE. NEED CODE COMPLIANT MAINTENANCE CONTROL PROGRAM ON SITE (Receipt #1310341) | ERIC | ERIC | | H01 | C | 5123976 |
CINEMARK USA, INC | H02 | C | 07/15/2015 | RP 7/14 KONE | ERIC | ERIC | | H02 | C | 4993308 |
CINEMARK USA, INC | HE16 | C | 02/12/2015 | FIRE FIGHTERS PHASE II "HOLD" POSITION STILL NOT WORKING, OTHER REPAIRS OK | ROBERTV | ROBERTV | | HE16 | C | 4901220 |
CINEMARK USA, INC | H01 | C | 01/28/2015 | RP -- 6/14 -- KONE. STOP SWITCH IN PIT STILL NOT WORKING, EMERGENCY LIGHTS OR ALARM NOT WORKING, STILL MISSING BRAILLE AND FLOOR DESIGNATION SIGNS ON DOOR JAMBS, FIRE FIGHTERS PHASE II STILL NOT WORKING CORRECTLY, MAINTAIN FIRE SERVICE LOG --- THESE ITEMS HAVE BEEN NOTED MULTIPLE TIMES AND NOW NEED ADDRESSED WITHIN 10 DAYS OR ELEVATOR WILL BE RED TAGGED AND REMOVED FROM SERVICE. (Receipt #1242972) | ROBERTV | ROBERTV | | H01 | C | 4891800 |
CINEMARK USA, INC | H02 | C | 07/17/2014 | RP -- 6/14 -- KONE. STOP SWITCH IN PIT NOT WORKING, MISSING FIRE SIGN AT MAIN FLOOR, MISSING BRAILLE AND FLOOR SIGNS ON MAIN AND 2ND REAR LANDINGS, PHASE II STILL NOT WORKING CORRECTLY, LIGHTING IN CAR WORKING INTERMITTENTLY, NEED BARREL KEY FOR 3RD FLOOR ACCESS (APPEARS PHASE II DOES NOT BYPASS ACCESS SWITCH), REPAIRS NEED TO BE MADE WITHIN 30 DAYS OR ELEVATOR WILL BE RED TAGGED. | ROBERTV | ROBERTV | | H02 | C | 4778453 |
CINEMARK USA, INC | H06 | C | 06/16/2014 | WITNESSED WORKING PRESSURE, RELIEF AND STOP RING TEST W/ KONE FOLLOWING VALVE REPLACEMENT. | ROBERTV | ROBERTV | | H06 | C | 4891792 |
CINEMARK USA, INC | H01 | C | 01/21/2014 | KONE, RELIEF PRESSURE TEST EXPIRED, LAST TEST 6/12, WILL REQUIRE 5 YEAR WITNESSED TEST, CAR DOES NOT RETURN TO EGRESS LANDING WHEN REMOVED FROM FIRE FIGHTERS PHASE 2 (Receipt #1175936) | ERIC | ERIC | | H01 | C | 4675354 |
CINEMARK USA, INC | H02 | C | 07/24/2013 | HO2 | ERIC | ERIC | | H02 | C | 4570051 |
CINEMARK USA, INC | H01 | C | 01/04/2013 | RP 6/12 MKE. CAR DOES NOT RETURN TO EGRESS LEVEL WHEN REMOVED FROM FIRE FIGHTERS PHASE 2 (Receipt #1103876) | ERIC | ERIC | | H01 | C | 4449492 |
CINEMARK USA, INC | H02 | C | 07/10/2012 | RP 6/12 KONE. FIRE FIGHTERS SERVICE STILL NOT FUNCTIONING CORRECTLY | ERIC | ERIC | | H02 | C | 4339051 |
CINEMARK USA, INC | H01 | C | 01/06/2012 | RP 6/11 KONE. CAR WILL NOT RETURN TO EGRESS LEVEL WHEN REMOVED FROM FIRE FIGHTERS PHASE 2 OPERATION (Receipt #1021514) | ERIC | ERIC | | H01 | C | 4257024 |
CINEMARK USA, INC | HE16 | C | 09/07/2011 | CORRECTIONS MADE TO FIRE SERVICE ACCESS, ELEVATOR BACK IN SERVICE PER KONE | ERIC | ERIC | | HE16 | C | 4204334 |
CINEMARK USA, INC | H02 | C | 07/19/2011 | RP 6/11 KONE. ELEVATOR RED TAGGED FOR FAILURE TO CORRECT FIRE FIGHTERS SERVICE ALLOWING ACCESS TO ALL FLOORS WHEN PHASE 2 FUNCTION IS ENGAGED.THEATRE MANAGER AND SERVICE CONTRACTOR HAVE BEEN NOTIFIED 3 TIMES PRIOR. | ERIC | ERIC | | H02 | C | 4180133 |
CINEMARK USA, INC | H01 | C | 01/07/2011 | RP 3/10 KONE. CAR OUT OF SERVICE (Receipt #954120) | ERIC | ERIC | | H01 | C | 4095985 |
CINEMARK USA, INC | H02 | C | 07/15/2010 | RP 3/10 KONE MUST HAVE ACCESS TO 3RD FLOOR WHEN FIRE FIGHTERS PHASE 2 IS ENABLED- 3RD AND FINAL NOTIFICATION-THIS MUST BE CORRECTED BY THE ANNUAL INSPECTION OR ELEVATOR WILL BE RED TAGGED. | ERIC | ERIC | | H02 | C | 4010350 |
CINEMARK USA, INC | H01 | C | 01/06/2010 | KONE RP 7/09. MUST HAVE ACCESS TO 3RD FLOOR WHEN FIRE FIGHTERS SERVICE IS USED. 2ND NOTIFICATION (Receipt #891723) | ERIC | ERIC | | H01 | C | 3929706 |
CINEMARK USA, INC | H02 | C | 07/23/2009 | KONE. RELIEF PRESSURE TEST EXPIRED, LAST TEST 4/08, CAR WILL NOT RETURN TO DESIGNATED LANDING WHEN REMOVED FROM FIRE FIGHTERS PHASE 2 SERVICE, NEED ACCESS TO ALL FLOORS ON FIRE FIGHTERS SERVICE, CLEAN PIT | ERIC | ERIC | | H02 | C | 3862381 |
CINEMARK USA, INC | H01 | C | 01/29/2009 | MONTGOMERY RP 4/08. EMERGENCY PHONE INOPERABLE (Receipt #844352) | ERIC | ERIC | | H01 | C | 3796495 |
CINEMARK USA, INC | H02 | C | 07/03/2008 | RP 4-08 [ 625 ] MONTGOMERY | LES | LES | | H02 | C | 3703196 |
CINEMARK USA, INC | H01 | C | 01/31/2008 | MONTGOMERY--RP EXP--LAST TEST 7-06--PHONE INOP-- MGR WILL CALL FOR RP TEST--NEED M/R DOOR SIGN | TOM | TOM | | H01 | C | 1951504 |
CINEMARK USA, INC | H02 | C | 07/31/2007 | RP 7-06--MONTGOMERY | TOM | TOM | | H02 | C | 1951495 |
CINEMARK 16 & I-MAX | H01 | C | 01/30/2007 | RP 7-06--MONTGOMERY--CK TOP KEY SWITCH | TOM | TOM | | H01 | C | 1951488 |
CINEMARK 16 & I-MAX | H02 | C | 07/27/2006 | RP 7-06 --- MONTGOMERY --- 3RD AND FINAL NOTICE, REPAIR 3RD FLOOR KEY SECURITY SWITCH | LES | LES | | H02 | C | 1951481 |
CINEMARK 16 & I-MAX | H01 | C | 01/20/2006 | RP 7-05 --- MONTGOMERY --- 3RD FLOOR HALL CALL STATION LOCK OUT SWITCH IS MISSING [ 2ND NOTICE ] | LES | LES | | H01 | C | 1951474 |
CINEMARK 16 & I-MAX | H02 | C | 07/29/2005 | RP 7-05 --- MONTGOMERY --- 3RD FLOOR HALL CALL STATION LOCK OUT SWITCH IS MISSING | LES | LES | | H02 | C | 1951467 |
CINEMARK 16 & I-MAX | H01 | C | 01/06/2005 | RP 7-04--MONTGOMERY | TOM | TOM | | H01 | C | 1951460 |
CINEMARK 16 & I-MAX | H02 | C | 06/18/2004 | RP 7-03--KONE | TOM | TOM | | H02 | C | 1951453 |
CINEMARK 16 & I-MAX | H01 | C | 12/02/2003 | RP 7-03--KONE | TOM | TOM | | H01 | C | 1951446 |
CINEMARK 16 & I-MAX | H02 | C | 06/20/2003 | RP 7-02--MONTGOMERY | TOM | TOM | | H02 | C | 1951433 |
CINEMARK 16 & I-MAX | H03 | C | 06/20/2003 | | TOM | TOM | | H03 | C | 1951439 |
CINEMARK 16 & I-MAX | H01 | P | 12/19/2002 | RP 7-02--KONE--PHONE INOP | TOM | TOM | | H01 | P | 1951426 |
CINEMARK 16 & I-MAX | H02 | C | 06/28/2002 | RP 12-01 | LES | LES | | H02 | C | 1951419 |
CINEMARK 16 & I-MAX | H01 | P | 12/21/2001 | RP 12-01--KONE--PHONE INOP--MACH RM STORAGE--PIT LIGHT OUT | TOM | TOM | | H01 | P | 1951412 |
CINEMARK 16 & I-MAX | H02 | C | 06/29/2001 | RP 12-01--KONE | TOM | TOM | | H02 | C | 1951405 |
CINEMARK 16 & I-MAX | H01 | C | 12/19/2000 | FINAL INSPECTION--ALL ITEMS CORRECTED--PERMIT ISSUED | TOM | TOM | | H01 | C | 1951304 |